Home›Engines›Cummins/Onan QMS11−G2 NR3

Cummins/Onan QMS11−G2 NR3 Engine

The Cummins/Onan QMS11−G2 NR3 is an engine. It powers generator sets from Cummins/Onan, including the DQHAB.

Also known as: Cummins Inc. QMS11−G2 NR3

Part of the Cummins/Onan QMS11 engine family — 2 variants share parts & fitment.

Engine specifications

Common problems

15
  • LOW BAT VOLTAGE — Warning 441
    Cause: Battery voltage supply to the control is approaching a low level at which unpredictable operation will occur; discharged or defective battery
    Fix: Check the battery charger fuse. Recharge or replace the battery
  • Overspeed — Shtdn 234
  • LOW COOLANT TEMP — Warning 1435
    Cause: Engine coolant heater is not operating or is not circulating coolant; coolant heater not connected to power supply
    Fix: Check for blown fuse or disconnected heater cord and correct as required
  • J1939 time out error — Wrng 285
  • WEAK BATTERY — Warning 1442
    Cause: During cranking, the battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time
    Fix: See code 441 for corrective action
  • Water in fuel high — Wrng 1852
  • VGT comm timeout — Wrng 1894
  • Under Frequency — Shtdn 1448
  • Unack fault warn — Wrng 2962
  • TRB in temp sen low — Wrng 692
  • TRB in temp sen high — Wrng 691
  • TOO LONG IN IDLE — Warning 2342
    Cause: Genset has been in Idle mode too long (10 minutes maximum)
  • Speed/Hz Match — Shtdn 1469
  • Speed Signal Lost — Shtdn 115
  • Speed Signal Lost 121

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan QMS11−G2 NR3.

Common questions

Which generators use the Cummins/Onan QMS11−G2 NR3 engine?

The Cummins/Onan QMS11−G2 NR3 powers 1 generator set(s), including Cummins/Onan DQHAB.

What is a common problem with the Cummins/Onan QMS11−G2 NR3 engine?

A commonly reported issue on generators using the Cummins/Onan QMS11−G2 NR3 is: LOW BAT VOLTAGE — Warning. Cause: Battery voltage supply to the control is approaching a low level at which unpredictable operation will occur; discharged or defective battery. Fix: Check the battery charger fuse. Recharge or replace the battery.