| 101 | IDLE MODE | Indicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. | Warning | |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Turn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required. |
| 1122 | Rated/Idle Trans | | Info | |
| 1123 | Shutdown After Battle Short | Shutdown fault occurred while Battle Short was enabled and then disabled. | Shutdown | Review Fault History and perform corrective action. |
| 1124 | Delayed Shutdown | Shutdown fault became active while Delayed Shutdown feature was enabled. | Warning | Review Fault History and perform corrective action. |
| 1131 | Battle Sh Active | Control is in Battle Short mode. | Warning | Warning status indicator is lit when Battle Short mode is enabled. Refer to Battle Short Mode description in Section 3. |
| 121 | Speed Signal Lost | Mag pickup speed indication is not being sensed. | Shutdown | Restart and check RPM on the digital display. |
| 1311 | Customer Input #1 | Default display name Customer Fault 1; default status None | | The nature of the fault is an optional customer selection (e.g. Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure). Each fault function can be programmed using service tool. |
| 1311, 1312, 1317, 1318 | CUSTOMER INPUT #1 - #4 | Optional customer-selected fault input is active. | Warning | Check external wiring and active input (closed/open) selection. |
| 1312 | Customer Input #2 | Default display name Ground Fault; default Warning | | The nature of the fault is an optional customer selection. Each fault function can be programmed using service tool. |
| 1317 | Customer Input #3 | Default display name Low Fuel; default Warning | | The nature of the fault is an optional customer selection. Each fault function can be programmed using service tool. |
| 1318 | Customer Input #4 | Default display name Rupture Basin Fault; default Warning | | The nature of the fault is an optional customer selection. Each fault function can be programmed using service tool. |
| 1334 | Crit Scaler Out Of Range | Incorrect feature or calibration entered into control. | Shutdown | Reload correct calibration. |
| 1335 | Noncrit Scaler Out Of Range | Incorrect feature or calibration entered into control. | Warning | Reload correct calibration. |
| 1337 | No Message | | Info | |
| 135 | Oil Pressure Sensor H | Engine oil pressure sender signal is shorted high. | Warning | Check sender/connectors/wires. |
| 141 | Oil Pressure Sensor L | Engine oil pressure sender signal is shorted low. | Warning | Check sender/connectors/wires. |
| 1416 | Fail To Shutdown | Genset continues to run after shutdown command. | Warning | With Battle Short mode enabled and an overridden shutdown fault occurring, the fault is announced but the genset does not shut down. Refer to Battle Short Mode description in Section 3. |
| 1417 | Powr Down Error | Controller cannot power down. | Warning | Indicates that the controller can not power down because of some unknown condition. Possible drain on battery. Contact an authorized service center for service. |
| 143 | Pre-Low Oil Pres | Engine oil pressure has dropped to an unacceptable level. | Warning | Indicates engine oil pressure has dropped below the warning trip point. If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure. |
| 1433 | Emergency Stop | Local Emergency Stop. | Shutdown | Pull button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto. |
| 1434 | Remote E-Stop | Remote Emergency Stop. | Shutdown | See code 1433 to reset. |
| 1435 | Low Coolant Temp | Warning LED illuminates when engine jacket water coolant temperature falls below 70°F (21°C); per NFPA 110 requirement, indicates engine may not accept load within 10 seconds | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. a. Coolant heater not connected to power supply; check for blown fuse or disconnected heater cord. b. Check for low coolant level and replenish if required; look for possible coolant leaks and repair. |
| 1438 | Fail To Crank | Engine failed to crank after PCC received a start signal. | Shutdown | Indicates possible fault with control, speed sensing or starting system. See code 441 for corrective action. |
| 144 | Coolant Sensor High | Engine coolant temperature signal is shorted high. | Warning | Check sender/connectors/wires. |
| 1442 | Weak Battery | Battery voltage at or below weak battery warning trip point during cranking. | Warning | See code 441 for corrective action. |
| 1443 | Battery Failed | Dead battery - engine will not start. | Shutdown | See code 441 for corrective action. |
| 1444 | KW Overload | Generator output power exceeded 105% of genset rating. | Warning | Check load and load lead connections; check CTs. |
| 1445 | Short Circuit | Generator output current has exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 1446 | High AC Voltage | One or more phase voltages exceeded 130% of nominal. | Shutdown | Check fault simulation, load removal, threshold settings, Base board/generator. |
| 1447 | Low AC Voltage | Phase voltages dropped below 85% of nominal for 10 seconds. | Shutdown | Check overload, output terminal connections, PMG/field wiring, rectifier diodes. |
| 1448 | Under Frequency | Engine speed dropped below 90% of nominal for 10 seconds. | Shutdown | Check fuel supply, intake air supply and load. |
| 1449 | Over Frequency | Frequency is 10% above base frequency for 20 seconds. | Warning | Check fuel or air delivery; check connections. |
| 145 | Coolant Sensor Low | Engine coolant temperature signal is shorted low. | Warning | Check sender/connectors/wires. |
| 1452 | Gen CB Not Close | Genset circuit breaker (S2) failed to close when PTC is enabled. | Warning | Refer to Section 5 troubleshooting charts. |
| 1453 | Gen CB Not Open | Genset circuit breaker (S2) failed to open when PTC is enabled. | Warning | Refer to Section 5 troubleshooting charts. |
| 1459 | Reverse Power | Improper CT phasing. | Shutdown | Check wiring to voltage sense circuit; refer to CT Installation in Section 6. |
| 146 | Pre-High Coolant Temp | Engine has begun to overheat. | Warning | Reduce load; check air inlets/outlets; follow code 151 if engine can be stopped. |
| 1461 | Loss Of Field | Loss of field (electric) due to reverse kVAR. | Shutdown | Check excitation circuit. |
| 1466 | Modem Failure | Control cannot communicate with the modem. | Warning | Check for open, short to ground and loose connections to the modem. |
| 1468 | Network Error | Momentary loss of communication from the LonWorks Network. | Warning | Refer to LonWorks Network publications. |
| 1469 | Speed/Hz Match | Measured speed and measured AC output frequency do not agree. | Shutdown | Check calibration file. |
| 1471 | Over Current | Generator output current exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 1472 | Over Current | Output current exceeded 110% of rated and time/current calculation initiated shutdown. | Shutdown | Check load and load lead connections. |
| 151 | High Coolant Temp | Engine has overheated above the shutdown trip point. | Shutdown | Indicates engine has overheated (coolant temperature above shutdown trip point). Allow engine to cool down completely. a. Check coolant level and replenish if low; look for coolant leaks and repair. b. Check for obstructions to cooling airflow. c. Check fan belt and repair or tighten if necessary. d. Check blower fan and circulation pumps on remote radiator installations. e. Reset control and restart after locating and correcting problem. |
| 197 | Low Coolant Level | Optional | Warning | Indicates engine coolant level has fallen below the warning trip point. If generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. Oil pressure limits are listed in Table 4-3. |
| 204 | OIL PRES SENDER | Indicates that the control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Set is not operating. Warning occurs when engine coolant temperature is 70° F (21° C) or lower. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary. | Warning | Reduce load if possible by turning off non-critical loads. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow 212-SHUTDOWN procedure. |
| 212 | Oil Temp Sensor H | Indicates engine has overheated (coolant temperature above 215° F (102° C) − standby or 207° F (97° C) − primary). | Warning | Check sender/connectors/wires. |
| 213 | Oil Temp Sensor L | Indicates that the resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender. Resistance should be 500 to 2k ohms. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Allow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Look for coolant leakage points and repair if necessary. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Shutdown | Allow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Reset control and restart after correcting problem. Shutdown will not occur if genset is in Idle mode (low coolant warning only). |
| 220 | MAG PICKUP | Indicates mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM on the digital display. |
| 221 | FAIL TO CRANK | Indicates possible fault with control or starting system. | Shutdown | Check fuse F3 on the Engine Interface board. Check for poor battery cable connections; clean battery cable terminals and tighten. Recharge or replace a discharged or defective battery. |
| 222 | OVERCRANK | Indicates possible fuel system problem. | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines. Check for dirty fuel filter and replace if necessary. Check for dirty or plugged air filter and replace if necessary. Reset the control and restart after correcting the problem. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed. (115% ±1% of nominal). | Shutdown | |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Check float level on battery charger if applicable (lower float level). Check engine DC alternator; replace if normal battery charging voltage is not obtained. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | Discharged or defective battery. See Warning message 230, LOW DC VOLTAGE. |
| 2327 | PTC Fault | PTC module or communication link is not working properly. | Warning | Check PTC module power, ground shield, cycle control power. |
| 2329 | Low S1 Frequency | Low utility (S1) frequency. | Warning | Check S1 AC inputs and wiring to PTC at TB5; check sensor set points. |
| 2331 | Low S1 Voltage | Low utility (S1) voltage. | Warning | Check S1 AC inputs and wiring to PTC at TB5; check pickup/dropout set points. |
| 2335 | Excitation Fault | Loss of all three voltage sense leads or failure in excitation circuit. | Shutdown | Check field wiring (X1 and X2) for shorts or opens. |
| 2336 | Memory Error | Control memory error; data corruption of critical operating parameters. | Shutdown | Try reloading calibration file. |
| 2337 | Pwr Tran Disabled | PTC module available but PTC feature not enabled. | Warning | Enable PTC feature with InPower; cycle control power. |
| 2338 | Pwr Tran Failure | Control could not communicate with the PTC module. | Warning | Check PTC module power and cable ground shield; cycle control power. |
| 2339 | Pwr Down Enabled | Power Down (sleep) enabled but PTC module or network board is active. | Warning | None required. |
| 234 | Overspeed | Engine has exceeded normal operating speed. | Shutdown | Check for large block load removal, flammable vapors or leaking turbocharger seals. |
| 2341 | High Control Temp | Control temperature above 158 F (70 C) for longer than set time. | Warning | Check genset room air flow. |
| 2342 | Too Long In Idle (10 min.) | Genset has been in Idle mode too long. | Warning | Indicates genset has been in Idle mode too long (10 minutes maximum). |
| 235 | Low Coolant Level | Optional | Shutdown | Indicates engine coolant level has fallen below the shutdown trip point. Allow engine to cool down completely. a. Check coolant level and replenish if low; look for possible coolant leakage points and repair. b. Reset control and restart. |
| 2358 | High S1 Voltage | Utility (S1) voltage increased above the over-voltage threshold. | Warning | Measure S1 AC inputs at PTC module; check sensor set points. |
| 2396 | S1 CB Not Close | Utility contact (S1) failed to close with PTC enabled. | Warning | Refer to Section 5 troubleshooting charts. |
| 2397 | S1 CB Not Open | Utility contact (S1) failed to open with PTC enabled. | Warning | Refer to Section 5 troubleshooting charts. |
| 240 | LOW FUEL−DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 241 | LOW FUEL | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 250 | EEPROM ERROR | Indicates PCC memory error. Data corruption of critical operating parameters. | Shutdown | |