Home›Engines›Cummins/Onan VTA28-G7

Cummins/Onan VTA28-G7 Engine

The Cummins/Onan VTA28-G7 is a 28 L 12-cylinder turbocharged and aftercooled engine rated at 1800 rpm. It powers generator sets from Cummins/Onan, including the 750DFGE, DFGE and DFGE 60 Hz. It holds 84 L (22.2 gal) of oil and 167 L (44.1 gal) of coolant.

Also known as: Cummins VTA28-G7

Part of the Cummins/Onan VTA28 engine family — 8 variants share parts & fitment.

28.0 L
Displacement
12
Cylinders
1800 rpm
Rated speed
84.0 L
Oil capacity

Engine specifications

Oil capacity84.0 L
Coolant capacity167.0 L
Displacement28.0 L
Cylinders12
AspirationTurbocharged and Aftercooled
Rated speed1800 rpm

Common problems

15
  • Weak Battery — Indicates that during cranking, the battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time. 1442
    Fix: See code 441 for corrective action.
  • The generator set produces low voltage output. 402
    Cause: Possible causes include: dirty or clogged air filter, malfunctioning alternator, or a faulty voltage regulator.
    Fix: Clean the air filter and check for any blockages. Inspect the alternator for signs of damage or wear. Test the voltage regulator to ensure it is functioning correctly.
  • The generator set produces high temperature warnings. 403
    Cause: Possible causes include: insufficient coolant, malfunctioning thermostat, or a clogged radiator.
    Fix: Check the coolant level and top up if necessary. Inspect the thermostat for any signs of failure. Clean the radiator to ensure proper airflow.
  • The generator set does not start. 401
    Cause: Possible causes include: low fuel level, faulty starter motor, or a malfunctioning ignition system.
    Fix: Check the fuel level and refill if necessary. Test the starter motor for functionality. Inspect the ignition system for any issues.
  • Speed Signal Lost — Critical shutdown fault; Battle Short is suspended and a shutdown occurs immediately if this fault occurs. 121
  • Shutdown After Battle Short — Battle Short is suspended and a shutdown occurs immediately if moving the customer installed Battle Short switch to OFF with an active but overridden shutdown fault or a shutdown fault that was overridden at any time. 1123
  • Remote Emergency Stop — Critical shutdown fault; Battle Short is suspended and a shutdown occurs immediately if this fault occurs. 1434
  • Remote E-Stop — Indicates remote Emergency Stop. 1434
    Fix: See code 1433 to reset.
  • Pre-Low Oil Pres — Indicates engine oil pressure has dropped below the warning trip point. 143
    Fix: If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure.
  • Pre-High Cool Tmp — Indicates engine is operating near cooling system capacity. Increase in load or higher ambient temperature may cause High Coolant Temp (151) shutdown. 146
    Fix: Review 151 correction list for other possible causes.
  • Power Down Error — Indicates that the controller can not power down because of some unknown condition. 1417
    Cause: Possible drain on battery.
    Fix: Contact an authorized service center for service.
  • Overspeed — Critical shutdown fault; Battle Short is suspended and a shutdown occurs immediately if this fault occurs. 234
  • Oil Temp — Indicates engine has begun to overheat (oil temperature has risen to an unacceptable level). 421
    Fix: If generator is powering non-critical and critical loads and cannot be shut down, use the following: Reduce load if possible by turning off non-critical loads; Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow code 151 procedure and also check engine oil level.
  • Low Oil Pressure — Indicates engine oil pressure has dropped below the shutdown trip point. 415
    Fix: Check oil level. If oil level is low, replenish. Reset control and restart.
  • Low Coolant Temp — Set is not operating. Warning occurs when engine coolant temperature is 70° F (21° C) or lower. NOTE: In applications where the ambient temperature falls below 40 F (4 C), Low Coolant Temp may be indicated even though the coolant heaters are operating. 1435
    Cause: Engine coolant heater is not operating or is not circulating coolant; Coolant heater not connected to power supply; Low coolant level
    Fix: Check for blown fuse or disconnected heater cord and correct as required; Check for low coolant level and replenish if required. Look for possible coolant leaks and repair as required.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan VTA28-G7.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter140-3288-02 Amazon eBay
Fuel filter—
Oil filter102-1335 Amazon eBay
Coolant—
Oil—

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

3
ItemActionHoursMonthsNotes
Battery Electrolyte LevelCheck200 hrCheck level of electrolyte at least every 200 hours of operation.
Crankcase Oil and FilterChange250 hr12 moX6: If genset is used for standby applications, change oil every 12 months or 250 hours, whichever comes first.
Rupture basin leak detect switchTest12 moSome areas may require weekly inspections by safety code.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceFloat switch assembly float lift clearance below C-clip stop1/8inch (3 mm)use a feeler gauge
ClearanceGenerator-to-engine angular alignment (T.I.R.).001 in. per inch of radius (center of shaft to indicator axis), maximumin750 kW gensets and larger
ClearanceMPU sensor to gear tooth adjustmentback out one quarter turnturnafter contacting gear tooth
GapFloat switch lift to test open1/8inchbelow C-clip stop
OtherB+ output fuse10ampF1, Base board, 12/24 volt
OtherCustomer Output relay contact rating2amps at 30 VDCTB1 customer outputs 1-4, normally open
OtherGenset frequency / RPM nameplate rating50 or 60 Hz / 1500 or 1800 RPM
OtherGround Fault Relay current setting5 to 1200amperesoptional GFR
OtherGround Fault Relay time delay setting0 to 1secondoptional GFR
OtherOptional control relay (K11/K12/K13) contact rating10amps at 600 VAC
OtherSwitched B+ output fuse5ampF2, Base board, 12/24 volt
PressureAir cleaner element cleaning compressed air30psi
PressureEngine oil pressure - K19 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - K38 normal45-65psi (310-448 kPa)run mode
PressureEngine oil pressure - K50 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - L10/M11 normal30-50psi (207-345 kPa)run mode
PressureEngine oil pressure - NTA 855 normal35-50psi (241-345 kPa)run mode
PressureEngine oil pressure - V28 normal50-90psi (345-620 kPa)run mode
PressureEngine oil pressure shutdown limit - L10/M1120psi (138 kPa)run mode value
PressureEngine oil pressure shutdown limit - L10/M118psi (55 kPa)idle mode value
PressureEngine oil pressure warning limit - L10/M1112psi (83 kPa)idle mode value
PressureEngine oil pressure warning limit - L10/M1125psi (172 kPa)run mode value
PressureIdle Oil Pressure20psiidle
PressureIdle Oil Pressure Shutdown Limit10psiidle
PressureIdle Oil Pressure Warning Limit15psiidle
PressureMax. Allowable Exhaust Back Pressure27in. H2O (6.7 kPa)6 in. NPT outlet
PressureMax. Allowable Exhaust Back Pressure41in. H2O (10.2 kPa)5 in. NPT outlet (DFGB/DFGE), 6 in. NPT outlet (DFLB/DFLC)
PressureMax. Fuel Inlet Restriction4in. Hg (13.5 kPa)
PressureMax. Fuel Return Restriction6.5in. Hg (22 kPa)
PressureNormal Oil Pressure50-90psi
PressureOil Pressure Shutdown Limit35psi
PressureOil Pressure Warning Limit40psi
PressureRadiator cleaning compressed air35psimaximum
ResistanceBattery specific gravity, fully charged1.260specific gravitycorrected to 80 F (27 C)
ResistanceCharge battery if specific gravity below1.215specific gravity
ResistanceCoolant heater coil resistance10 to 60ohmsthermostat closed
ResistanceCoolant temperature sender resistance500 to 2kohms
ResistanceCurrent transformer (PT) primary1K-2.5Kohms
ResistanceCurrent transformer (PT) secondary140-225ohms
ResistanceExciter stator winding - frame size 4C/4D/4E/4F0.136ohmsat 68°F (20°C) + 10%
ResistanceExciter stator winding insulation resistance1megohmreplace if less than
ResistanceFuel solenoid coil resistance30ohmsindicates coil OK
ResistanceGovernor actuator circuit resistance7.5ohmsindicates OK
ResistanceHarness open-circuit check10 or lessohmsOK
ResistanceHarness short-circuit checkmore than 200kohmsOK
ResistanceMain rotor winding insulation resistance1megohmreplace if less than
ResistanceMain stator winding insulation resistance1megohmreplace if less than
ResistancePMG stator resistance2/6ohms
ResistancePMG stator resistance4.6ohms
ResistancePMG stator resistance - frame size HC42/6ohms
ResistancePMG stator resistance - frame size HC5/HC6/HC74.6ohms
ResistancePT/CT module 3-ohm resistors3ohmsJ8-15 to 14, J8-22 to 23, J8-7 to 8
ResistanceThermistor relay trip point (thermistor chain resistance)3000 ±500ohms
SpeedFrequency Adjust range±5percent of nominal frequencyexample: 60.0 Hz nominal adjustable 57.0-63.0 Hz
SpeedIdle speed adjust700 to 1100RPMdefault 800 RPM
SpeedIdle speed adjustment800 ±100RPMdefault 800 RPM
SpeedOverspeed shutdown threshold115% ±1%% of nominal
TemperatureCold Soak for battery CCA rating0F-18 C
TemperatureEngine Cold warning threshold (Code 1435)70°F (21°C)jacket water coolant temperature
TemperatureEngine jacket water coolant heater minimum maintained temperature90°F (32°C)per NFPA 110

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
FuelASTM No. 2 dieselASTMAlternate diesel fuels per Cummins engine O&M Manual specifications
FuelDieselDo not use zinc coated or copper fuel lines with diesel fuel. Be sure all fuel supplies have a positive shutoff valve.
Fuelnumber 2 dieselDirect injection; automatic electric fuel shutoff
GreaseLithium based-30°C to 120°C81.0 mlMobilux No. 2 or Shell Alvania R3; generator end bearing; temperature range -22 F to +248 F (-30 C to +120 C); grease divided between bearing, bearing cap cavity and cartridge cavity.
GreaseLithium based grease, Mobilux No. 2 or Shell Alvania R3-30°C to 120°C81.0 mlGenerator end bearing lubricant; temperature range -22°F to +248°F (-30°C to +120°C); 2.74 oz. (81 ml) equally divided between the bearing, the bearing cap cavity, and the bearing cartridge cavity.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
101IDLE MODEIndicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.Warning
102EMERGENCY STOPIndicates local or remote Emergency Stop.ShutdownTurn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
121SPEED SIGNAL LOSTMag pickup speed indication is not being sensed.ShutdownRestart and check RPM on the digital display.
135OIL PRESSURE SENSOR HEngine oil pressure sender signal is shorted high.WarningCheck sender/connectors/wires.
141OIL PRESSURE SENSOR LEngine oil pressure sender signal is shorted low.WarningCheck sender/connectors/wires.
143PRE-LOW OIL PRESEngine oil pressure has dropped to an unacceptable level.WarningIf critical loads, wait until next shutdown period and follow code 415.
144COOL SENSOR HIGHEngine coolant temperature signal is shorted high.WarningCheck sender/connectors/wires.
145COOL SENSOR LOWEngine coolant temperature signal is shorted low.WarningCheck sender/connectors/wires.
146PRE-HIGH COOL TMPEngine has begun to overheat.WarningReduce load; check air inlets/outlets; follow code 151 if engine can be stopped.
151HIGH COOLANT TEMPEngine has overheated above the shutdown trip point.ShutdownAllow cool down; check coolant level, cooling airflow, fan belt, blower fan and circulation pumps.
197Low Coolant LevelOptionalWarningIndicates engine coolant level has fallen below the warning trip point. If generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure.
200LOW OIL PRESSUREIndicates engine oil pressure has dropped to an unacceptable level.WarningIf generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault.
201LOW OIL PRESSUREIndicates engine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. Oil pressure limits are listed in Table 4-3.
204OIL PRES SENDERIndicates that the control has sensed that the engine oil pressure sender is out of its working range.WarningCheck that the engine oil pressure sender is properly connected.
210LOW COOLANT TEMPSet is not operating. Warning occurs when engine coolant temperature is 70° F (21° C) or lower.WarningIndicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw.
211HIGH COOLANT TEMPIndicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary.WarningReduce load if possible by turning off non-critical loads. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow 212-SHUTDOWN procedure.
212HIGH COOLANT TEMPIndicates engine has overheated (coolant temperature above 215° F (102° C) − standby or 207° F (97° C) − primary).ShutdownAllow engine to cool down completely. Check for obstructions to cooling airflow; check fan belt; check coolant mixture; check blower fan and circulation pumps on remote radiator installations. Reset control and restart.
213COOLANT SENDERIndicates that the resistance of the coolant temperature sender is out of range.WarningCheck the resistance of the sender. Resistance should be 500 to 2k ohms.
214LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.WarningAllow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Look for coolant leakage points and repair if necessary.
215LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.ShutdownAllow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Reset control and restart after correcting problem. Shutdown will not occur if genset is in Idle mode (low coolant warning only).
220MAG PICKUPIndicates mag pickup speed indication is not being sensed or does not match generator set output frequency.ShutdownRestart and check RPM on the digital display.
221FAIL TO CRANKIndicates possible fault with control or starting system.ShutdownCheck fuse F3 on the Engine Interface board. Check for poor battery cable connections; clean battery cable terminals and tighten. Recharge or replace a discharged or defective battery.
222OVERCRANKIndicates possible fuel system problem.ShutdownCheck for empty fuel tank, fuel leaks, or plugged fuel lines. Check for dirty fuel filter and replace if necessary. Check for dirty or plugged air filter and replace if necessary. Reset the control and restart after correcting the problem.
223OVERSPEEDIndicates engine has exceeded normal operating speed. (115% ±1% of nominal).Shutdown
230LOW DC VOLTAGEIndicates battery voltage is below 10 VDC.WarningRecharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable.
231HIGH DC VOLTAGEIndicates battery voltage exceeds 32 VDC.WarningCheck float level on battery charger if applicable (lower float level). Check engine DC alternator; replace if normal battery charging voltage is not obtained.
232WEAK BATTERYIndicates battery voltage drops below 60% of nominal for two seconds, during starting.WarningDischarged or defective battery. See Warning message 230, LOW DC VOLTAGE.
234OVERSPEEDEngine has exceeded normal operating speed.ShutdownCheck for large block load removal, flammable vapors or leaking turbocharger seals.
235Low Coolant LevelOptionalShutdownIndicates engine coolant level has fallen below the shutdown trip point. Allow engine to cool down completely. a. Check coolant level and replenish if low; look for possible coolant leakage points and repair. b. Reset control and restart.
240LOW FUEL−DAYIndicates day tank fuel supply is running low.WarningCheck fuel supply and replenish as required.
241LOW FUELIndicates day tank fuel supply is running low.WarningCheck fuel supply and replenish as required.
250EEPROM ERRORIndicates PCC memory error. Data corruption of critical operating parameters.Shutdown
251EEPROM ERRORIndicates PCC memory error. Data corruption of noncritical operating parameters.Warning
252EEPROM ERRORIndicates PCC memory error. Data corruption of noncritical operating parameters.Warning
260CUSTOMER FAULT 1When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningFault functions can be programmed to initiate a shutdown or a warning.
261GROUND FAULTWhen a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningFault functions can be programmed to initiate a shutdown or a warning.
262RUPTURE BASINWhen a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningFault functions can be programmed to initiate a shutdown or a warning.
263HIGH GEN TEMPWhen a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningFault functions can be programmed to initiate a shutdown or a warning.
301HIGH AC VOLTAGEIndicates that one or more of the phase voltages has exceeded 130% of nominal, or has exceeded 110% of nominal for 10 seconds.Shutdown
303LOW AC VOLTAGEIndicates that one or more of the phase voltages has dropped below 85% of nominal for 10 seconds.Shutdown
313UNDER FREQUENCYIndicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown, a Load Dump signal is initiated.ShutdownCheck fuel supply, intake air supply and load.
320OVERCURRENTIndicates that generator output current has exceeded 110% of rated for 60 seconds.WarningCheck load and load lead connections.
321OVERCURRENTIndicates that generator output current has exceeded 110% of rated, and that a PCC time/current calculation has initiated an overcurrent shutdown.ShutdownCheck load and load lead connections.
322SHORT CIRCUITIndicates that generator output current has exceeded 175% of rated.ShutdownCheck load and load lead connections.
330OVERLOADIndicates that three-phase power output exceeds 105% of standby (or 115% of prime) rating. After five seconds, the Load Dump output is activated. After 60 seconds, the OVERLOAD warning is activated.WarningCheck load and load lead connections.
335REVERSE POWERIndicates improper CT or PT phasing. (Non-parallel units only.)ShutdownCheck CT / PT wiring. Refer to CT Installation in Section 5.
359Fail To StartEngine cranks but fails to startShutdownIndicates possible fuel system or air induction problem. a. Check for empty fuel tank, fuel leaks, or plugged fuel lines. b. Check for dirty fuel filter and replace if necessary. c. Check for dirty or plugged air filter and replace if necessary. d. Reset the control and restart.
415LOW OIL PRESSUREEngine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters; replenish if low; reset control.
421Oil TempOptionalWarningIndicates engine has begun to overheat. a. Reduce load if possible by turning off non-critical loads. b. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow code 151 procedure and also check engine oil level.
441LOW BAT VOLTAGEBattery voltage supply to the control is approaching a low level.WarningRecharge or replace battery; check charger fuse, connections and DC alternator.
442HIGH BAT VOLTAGEBattery voltage supply is approaching a high level.WarningCheck battery charger float level; check battery wiring/calibration.
1122Rated/Idle TransInfo
1123SHUTDOWN AFTER BSShutdown fault occurred while Battle Short was enabled and then disabled.ShutdownReview Fault History and perform corrective action.
1124DELAYED SHUTDOWNShutdown fault became active while Delayed Shutdown feature was enabled.WarningReview Fault History and perform corrective action.
1131BATTLE SHORT ACTIVEControl is in Battle Short mode.WarningBypasses several critical fault shutdowns for emergency operation.
1311Customer Input #1Default display name Customer Fault 1; default status NoneThe nature of the fault is an optional customer selection (e.g. Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure). Each fault function can be programmed using service tool.
1311, 1312, 1317, 1318CUSTOMER INPUT #1 - #4Optional customer-selected fault input is active.WarningCheck external wiring and active input (closed/open) selection.
1312Customer Input #2Default display name Ground Fault; default WarningThe nature of the fault is an optional customer selection. Each fault function can be programmed using service tool.
1317Customer Input #3Default display name Low Fuel; default WarningThe nature of the fault is an optional customer selection. Each fault function can be programmed using service tool.
1318Customer Input #4Default display name Rupture Basin Fault; default WarningThe nature of the fault is an optional customer selection. Each fault function can be programmed using service tool.
1334CRIT SCALER ORIncorrect feature or calibration entered into control.ShutdownReload correct calibration.
1335NONCRIT SCALER ORIncorrect feature or calibration entered into control.WarningReload correct calibration.
1337No MessageInfo
1416FAIL TO SHUTDOWNGenset continues to run after shutdown command.WarningCheck Battle Short feature enabled condition.
1417POWER DOWN ERRORController cannot power down.WarningCheck for possible battery drain.
1433EMERGENCY STOPLocal Emergency Stop.ShutdownPull button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto.
1434REMOTE E-STOPRemote Emergency Stop.ShutdownSee code 1433 to reset.
1435Engine ColdWarning LED illuminates when engine jacket water coolant temperature falls below 70°F (21°C); per NFPA 110 requirement, indicates engine may not accept load within 10 secondsWarningCheck coolant heaters for proper operation; other precautions may be necessary to warm engine before applying load
1438FAIL TO CRANKEngine failed to crank after PCC received a start signal.ShutdownCheck starter, fuse F3, K4 relay, E-Stop switch and MPU circuit.
1442WEAK BATTERYBattery voltage at or below weak battery warning trip point during cranking.WarningSee code 441 for corrective action.
1443BATTERY FAILEDDead battery - engine will not start.ShutdownSee code 441 for corrective action.
1444KW OVERLOADGenerator output power exceeded 105% of genset rating.WarningCheck load and load lead connections; check CTs.
1445SHORT CIRCUITGenerator output current has exceeded 175% of rated.ShutdownCheck load and load lead connections.
1446HIGH AC VOLTAGEOne or more phase voltages exceeded 130% of nominal.ShutdownCheck fault simulation, load removal, threshold settings, Base board/generator.
1447LOW AC VOLTAGEPhase voltages dropped below 85% of nominal for 10 seconds.ShutdownCheck overload, output terminal connections, PMG/field wiring, rectifier diodes.
1448UNDER FREQUENCYEngine speed dropped below 90% of nominal for 10 seconds.ShutdownCheck fuel supply, intake air supply and load.
1449OVER FREQUENCYFrequency is 10% above base frequency for 20 seconds.WarningCheck fuel or air delivery; check connections.
1452GEN CB NOT CLOSEGenset circuit breaker (S2) failed to close when PTC is enabled.WarningRefer to Section 5 troubleshooting charts.
1453GEN CB NOT OPENGenset circuit breaker (S2) failed to open when PTC is enabled.WarningRefer to Section 5 troubleshooting charts.
1459REVERSE POWERImproper CT phasing.ShutdownCheck wiring to voltage sense circuit; refer to CT Installation in Section 6.

Showing the first 80 of 105 codes.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Aligning Generator with Engine (Angular Alignment) adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.

Tools: Dial indicator, Shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with the sensing point on the capscrew head or flat surface of the drive disc at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
  4. Determine the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one revolution.
  5. Measure the distance from the center of the generator shaft to the indicator measuring point.
  6. Measure the distance from the generator side of the flex discs to the center of the generator mounting bolt.
  7. Compare the distances; multiply this ratio times one half the T.I.R. to approximate the amount of shims to remove or add.
Angular Alignment Procedure (750 kW gensets and larger) adjustment

⚠ Accidental starting during this procedure presents hazard of severe injury or death

⚠ Do not bar engine over by prying on fan blade

Tools: dial indicator

  1. Disconnect negative battery cable(s) before beginning
  2. Fasten dial indicator to generator shaft or cooling fan, sensing point on capscrew head or drive disc flat surface
  3. Bar engine over in clockwise rotation as viewed from flywheel, do not allow roll-back at end of travel
  4. Record total indicator reading (T.I.R.) as sum of max positive and negative readings over one revolution
  5. Calculate shim correction using ratio of generator shaft-to-indicator distance vs generator mounting bolt distance
  6. Add or remove shims from both generator mounting feet as calculated
Angular Alignment Procedure (Generator to Engine) adjustment

⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.

⚠ Do not bar engine over by prying on fan blade.

Tools: dial indicator

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with sensing point resting on the drive disc capscrew head/flat surface at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from the engine flywheel; do not allow it to roll back on compression at the end of travel of each reading.
  4. Record the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one engine revolution.
  5. Compare the measured T.I.R. to the maximum allowed (.001 in. per inch of radius from center of shaft to indicator axis); add or remove shims under the generator mounting feet to correct.
Axial Alignment Procedure (750 kW gensets and larger) adjustment

Tools: dial indicator

  1. Check axial alignment only when objectionable vibration is present after angular alignment
  2. Fasten dial indicator holding device to skid base/engine block/generator shell, sensor on generator shaft hub
  3. Bar engine over clockwise through a couple of rotations, recording readings at eight equally spaced points
  4. If out of tolerance, remove capscrews connecting drive discs and flywheel, mark discs, reposition holes 180 degrees
  5. Reinstall capscrews and retorque; recheck alignment; try 30/60/90 degree repositioning if unchanged
Axial Alignment Procedure (Generator to Engine) adjustment

Tools: dial indicator

  1. Fasten a dial indicator holding device to the skid base, engine block, or generator shell with the sensor point resting on the generator shaft hub.
  2. Bar the engine over in a clockwise rotation through a couple of rotations, recording indicator readings at eight equally spaced points around the shaft diameter to obtain axial T.I.R.
  3. Reduce the measured T.I.R. runout by one half if excessive vibration remains after angular alignment.
Generator/Base Board Isolation Procedure diagnostic

⚠ This test involves unregulated excitation of the generator.

⚠ Hazardous voltage; use insulated tools and stand on dry platform.

Tools: Voltmeter, Jumper leads, 12V battery

  1. Throw line circuit breaker OFF and shut down the set.
  2. Disconnect exciter stator leads X and XX from AC harness.
  3. Prepare to measure output voltage across generator terminals.
  4. Bring 12V battery jumpers to X (Field +) and XX (Field -).
  5. Verify polarity is correct before connecting.
  6. Start set; connect battery negative to XX lead.
  7. If rated voltage and balanced phases, generator is OK.
  8. If unbalanced troubleshoot main stator; if low troubleshoot exciter circuits.
Generator/PCC Control Isolation Procedure diagnostic

⚠ This test involves unregulated excitation of the generator; make sure all loads have been disconnected.

⚠ HIGH VOLTAGE: touching uninsulated high voltage parts inside the control box can result in severe personal injury or death.

Tools: 12 volt battery, Jumper leads, Voltmeter

  1. Throw the line circuit breaker OFF and shut down the set.
  2. Remove the accessory box housing cover and remove plug P10 from connector J10 of A37.
  3. Prepare to measure output voltage across the generator terminals while the set is running.
  4. Bring two jumpers from a 12 volt battery for connection to X (Field +) and XX (Field -) pins of plug P10.
  5. Check polarity again; polarity must be correct or the test will be inconclusive.
  6. Start the set and connect the jumper from the battery negative terminal to the XX lead.
  7. If rated output voltage or higher is obtained and all phases are balanced, generator circuitry is probably okay; refer to Section 4.
  8. If voltages are unbalanced, troubleshoot the main stator first; if uniformly low, troubleshoot exciter and field circuits first.
Ground Fault Relay Test diagnostic
  1. Verify N-G Fault Indicator on GFR is not lit; if lit, install bonding jumper at facility service entrance
  2. Move control switch to Run position
  3. Press TEST switch on ground fault relay
  4. Verify control panel warning message displayed and Fault Indicator (>I) lit on GFR
  5. Reset the control panel fault (also resets ground fault relay)
Megger and PI Test diagnostic

⚠ Medium-voltage (601 to 15,000 volts) windings must be dry before the generator is operated.

Tools: Megger or Insulation Resistance Meter, Wheatstone bridge or digital ohmmeter, Grounding Cluster

  1. Perform the Generator Set Grounding Procedure.
  2. Disconnect plug J10 from the voltage regulator output module and the AC control leads (marked 4, 5, 6, 7, 8).
  3. If RTD option installed, ground all six RTD temperature leads (18 leads total).
  4. Perform the Winding Resistance Test for the desired windings.
  5. Perform the Insulation Resistance (Megger) Test and PI Test for the desired windings.
  6. Megger test: apply voltage for up to one minute.
  7. PI test: apply voltage for ten minutes; record resistance at one minute and ten minutes.
  8. PI is the ten-minute reading divided by the one-minute reading; ratio of two or greater is good.
Testing the Float Switch Assembly diagnostic

Tools: Ohmmeter, Feeler gauge

  1. Remove the fuel pump control cover, disconnect the wiring jack and unscrew the assembly from the top of the day tank.
  2. With an ohmmeter, test for electrical continuity between each pair of colored leads while holding the assembly vertical; all readings should be zero.
  3. Lift each float, in turn, to 1/8 inch (3 mm) below the C-clip stop above it and test for continuity; all readings should be infinity.
  4. Use pipe thread sealant when replacing the assembly.
Testing the PMG diagnostic

⚠ HIGH VOLTAGE. Touching uninsulated high voltage parts inside the control and power output boxes will result in severe personal injury or death.

Tools: Wheatstone bridge or digital ohmmeter, Voltmeter, Elbow length insulating gloves

  1. Disconnect plug J10 from the voltage regulator output stage module.
  2. Start the engine at the set and let the speed stabilize.
  3. Measure voltage across lead pairs J10-1 & J10-4, J10-4 & J10-5, and J10-5 & J10-1.
  4. Voltage should be at least 150 VAC for 50 Hz sets and at least 180 VAC for 60 Hz sets, approximately the same for each set of leads.
  5. If voltages are low or uneven, check all leads and connections between A37 and the PMG and repair as necessary.
  6. Stop the set and measure electrical resistance across lead pairs J10-1 & J10-4, J10-4 & J10-5, and J10-5 & J10-1 with a Wheatstone bridge or digital ohmmeter.
Current Transformer (CT) Installation installation

⚠ Improper installation of CT's will cause a 335 Reverse Power shutdown error (non-parallel units only).

  1. Orient the CT dot toward the generator (conventional current flowing into the dot); dot also indicates pin 1 of the CT.
  2. CT21 - U load leads (A phase); CT22 - V load leads (B phase); CT23 - W load leads (C phase).
  3. Route the appropriate leads through each CT: 6-lead gensets route generator output leads; 12-lead gensets route load wires.
  4. For 12 lead (reconnectable) gensets, connect CT secondary wire marked 1 to pin 1; secondary wire marked 2/3 to pin 2 for high voltage or pin 3 for low voltage.
  5. For 6 lead (non-reconnectable) gensets, connect lead from CT terminal #1 to metering circuitry and lead from CT terminal #2/3 to ground.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
110 V - 120 V L-N1Single phase, 2-wirePTC module jumper locations
110/1903Three Phase Reconnectable
120/2083Three Phase Reconnectable
127/2203Three Phase Reconnectable
139/2403Three Phase Reconnectable
190 V - 240 V L-L3Three phaseUse PTC module 0300-5382-01; 50/60 Hz
200 V - 240 V L-L1Single phase, 3-wirePTC module jumper locations
220/3803Three Phase Reconnectable
240/4163Three Phase Reconnectable
254/4403Three Phase Reconnectable
277/4803Three Phase Non-Reconnectable
277/4803Three Phase Reconnectable
347/6003Three Phase Non-Reconnectable
380 V - 600 V L-L3Three phaseUse PTC module 0300-5382-02; 50/60 Hz

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan VTA28 family

119
Part #DescriptionCategory
140-2301Cleaner, Air (Includes Replacement Elements) 140−2465Air filter
140-3288-02Cleaner, AirAir filter
140-3349-02Bracket, Air CleanerAir filter
M-1627BOLT DIAGRAMBattery
130-3839-01Guard, Belt − Right SideBelt
130-3839-02Guard, Belt − Left SideBelt
130-3840Guard, Belt − TopBelt
130-3841Guard, Belt − BottomBelt
130-3842Guard, Belt − FrontBelt
130-3843Guard, Belt − Right SideBelt
130-3844Guard, Belt − Bottom BackBelt
130-3845Guard, Belt − Top BackBelt
130-3846Guard, Belt − Left SideBelt
511-0105Belt−VBelt
M-1761AIR CLEANERSCleaner
EXS-1583-3CONTROL HEATERControl heater
960-0630CPCC2100 PowerCommand ControlController
CS-1075-1COOLANT FILTERSCoolant filter
CS-1367-2TYPICAL COOLANT HEATERCoolant heater
0300-4623-18DFGB (600V)Current transformer
0300-4623-34DFGB BR (0-480V)Current transformer
ES-1779-1VOLTAGE REGULATOR AND EXCITATION SWITCHExcitation switch
FS1304FILTERFilter
130-4552Cover, Coolant HeaterFluid
333-0407-05Heater, Oil (300 Watt, 480 Volt)Fluid
502-1337Adapter, Coolant HeaterFluid
FF202Fuel, Spin-OnFuel filter
FS1216Fuel/Water Sep Spin-OnFuel filter
130-1193Gasket, Outlet AdapterGasket
130-4354Radiator (Includes Cap, Sight Gauge And Overflow Hose) (Also Includes Cover Plates, Gaskets, Screws And Lock Washers For All Water Outlets)Gasket
330-0141-04Gasket, CoverGasket
330-0142Box, Terminal (Includes Cover and Gasket − Ref No. 19 and 20)Gasket
128-0108Insulation, Hose – Bulk (Order By The Foot – 12 Feet Required)Hose
130-3874Base, Mounting * − Parts Used On Heat Exchanger Installations With Automatic Water Regulator + − Parts Used On Heat Exchanger Installations Without Automatic Water Regulator # − Cut Off And Discard Swivel Connector End Of Hose So That 1/8 NPT Connector End Measures Length As Indicated AboveHose
130-3875Tube, OutletHose
130-4576TubeHose
130-4577TubeHose
130-4581TubeHose
416-0680Cable, Battery (10")Hose
501-0537-22Hose, Oil (86”)Hose
501-0537-23Hose, Oil (22”)Hose
501-0744-01Hose, CoolantHose
501-0744-05Hose, CoolantHose
502-0313Elbow, Hose − 90° (1/8” Pipe to 1/4” Hose)Hose
502-0395Connector, HoseHose
502-0971Connector, HoseHose
502-1530Union, Hose (1”) − NylonHose
502-1531Connector, HoseHose
503-0189Clamp, HoseHose
503-0249Hose − Bulk (Order by the Foot − 3 Feet Required)Hose
503-0569Hose (3−1/2” ID) Bulk (Order By The Foot − 2 Feet Required)Hose
503-0685Clamp, HoseHose
503-0856Hose, Radiator − Lower (3−1/2” ID x 5−1/2”)Hose
503-1418Hose − Bulk (1/4” ID) (Order By The Foot − 18 Feet Required)Hose
503-1620Hose – Bulk (3/8" ID) (Order by the Foot)Hose
503-1634Hose, Silicon RubberHose
503-1634-01Hose, Rubber (3/4” ID x 4”)Hose
503-1728Hose (3” ID x 5–1/2”)Hose
503-1779Hose − Bulk (1” ID) (Order By The Foot − 1 Foot Required)Hose
503-1870-07Clamp, HoseHose
503-1870-11Clamp, HoseHose
503-1870-12Clamp, HoseHose
503-1870-14Clamp, HoseHose
503-1872-01Clamp, HoseHose
503-1872-05Clamp, HoseHose
503-1872-07Clamp, HoseHose
503-2157-01Clamp, HoseHose
503-2276Elbow, HoseHose
503-2350-04Hose, Coolant (1” x 5‘)Hose
503-2350-05Hose, Coolant (1” x 8‘)Hose
505-0759Adapter − Pipe to Hose (1” x 1”)Hose
518-0548-20Clamp, HoseHose
518-0548-24Clamp, HoseHose
122-0702Head, Oil FilterOil filter
122-0777Filter, Lube OilOil filter
098-7954Label, Information − Element ReplacementService part / kit
102-1335Plug, Oil DrainService part / kit
130-1430Exchanger, HeatService part / kit
130-1515Tank, WaterService part / kit
130-4582Bracket, MountingService part / kit
130-5666-02Tube, Water HeaterService part / kit
130-5852-02Tube, Water HeaterService part / kit
140-1260Fitting, Safety FilterService part / kit
140-1260-01Fitting, Safety FilterService part / kit
193-0128Gauge, Fuel Pressure (0-200 Lbs)Service part / kit
307-2621-02Relay, Start Solenoid (K4)Service part / kit
307-2859Relay, Power - 24VDC (K11)Service part / kit
323-1491* Pin, Contact (Used With Inline G)Service part / kit
323-1492* Socket, Contact (Used In Stations 18, 19)Service part / kit
323-1718* Pin, Contact (Used In Station 17)Service part / kit
332-2634Clamp, HoseService part / kit
333-0639-01Heater, Coolant (4990 Watt)Service part / kit
333-0639-02Heater, Coolant (6420 Watt)Service part / kit
416-0446Cable, Battery - JumperService part / kit
504-0171Valve, ShutoffService part / kit
505-0100Nipple, Pipe - Close (1/2”)Service part / kit
505-1071Coupling, Flexible (For 2" Pipe)Service part / kit
505-1072Valve, WaterService part / kit
518-0548-42Clamp, Retainer 4 Prior To December 1996 Production (Mounted On Top And Side Of Control Box Wrapper)Service part / kit
870-0257Nut, Locking (5/16−18) * − Parts Used On Heat Exchanger Installations With Automatic Water Regulator # − Cut Off And Discard Swivel Connector End Of Hose So That 1/8 NPT Connector End Measures Length As Indicated Above + − Parts Used On Heat Exchanger Installations Without Automatic Water RegulatorService part / kit
898-1254-25Sleeving – Heater Leads (59”)Service part / kit
EXS-1036-1RAIN CAPService part / kit
M-1808-4TYPICAL INSTALLATIONService part / kit
M-CK4911685PCylinder KitService part / kit
MCB4911685Piston KitService part / kit
M-1759INJECTION PUMPPump
323-1445* Seal, Cable (Used With Station 17)Seal
508-0292Washer, Sealing - CopperSeal
151-0411Pickup, MagneticSensor
193-0432Sender, Oil Temperature (S2 Engine Block, E4 Oil Pan)Sensor
193-0444Sender, Oil Pressure (S1)Sensor
193-0468Sender, Low CoolantSensor
193-0481Sender Assembly - Low Coolant LevelSensor
193-0529-01Sender, Oil TemperatureSensor
309-0269Sender, Temperature-Lo EngineSensor
M-1760PRE-HIGH AND HIGH COOLANT TEMPERATURE SENSORSensor
960-0504PCC Control Service ManualService manual
960-0507Detector Control Service ManualService manual
309-0649Thermostat (Includes Connector Socket) (S11)Thermostat

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan VTA28-G7?

The Cummins/Onan VTA28-G7 engine has an oil capacity of 84.0 liters.

What is the displacement of the Cummins/Onan VTA28-G7?

The Cummins/Onan VTA28-G7 has a displacement of 28.0 liters with 12 cylinders.

Which generators use the Cummins/Onan VTA28-G7 engine?

The Cummins/Onan VTA28-G7 powers 3 generator set(s), including Cummins/Onan 750DFGE, Cummins/Onan DFGE, Cummins/Onan DFGE 60 Hz.

What is a common problem with the Cummins/Onan VTA28-G7 engine?

A commonly reported issue on generators using the Cummins/Onan VTA28-G7 is: Weak Battery — Indicates that during cranking, the battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time.. Fix: See code 441 for corrective action..