Home›Engines›Ford V-10 6.8L

Ford V-10 6.8L Engine

The Ford V-10 6.8L is a 6.8 L 10-cylinder engine rated at 1800 rpm. It powers generator sets from Cummins/Onan, including the GGHG and GGHH. It holds 5.5 L (1.5 gal) of oil.

Also known as: Ford V-10 6.8L

6.8 L
Displacement
10
Cylinders
1800 rpm
Rated speed
5.5 L
Oil capacity

Engine specifications

Oil capacity5.5 L
Displacement6.8 L
Cylinders10
Rated speed1800 rpm

Generator sets powered by this engine

2

Troubleshooting

1

Fault codes

CodeMeaning
E3Evaporative Emissions System Leak

Fault codes and symptom→remedy steps extracted from this engine’s service/owner documentation; verify against the official manual before servicing.

Common problems

15
  • The engine does not crank in Run mode
    Cause: The Emergency Stop switch has been used. (The switch button is lit.)
    Fix: Pull the Emergency Switch button. To reset the engine control, push the Run-Stop-Remote switch to Stop and the Reset switch to Reset. Then push the Run-Stop-Remote switch to Run to start the genset.
  • The engine cranks but does not start
    Cause: The engine is not getting fuel.
    Fix: Open any closed fuel shutoff valve. (Valves closed for maintenance or new installations may require several crank cycles to get fuel to genset); Fill the propane supply tank; For natural gas fueled sets, check with the gas utility; Check fuel pressure at regulator (refer to Fuel Pressure in Section 6.) (High fuel pressure will prevent solenoid from opening); Check fuel solenoid (VDC present at K1+ lead during cranking); Duel Fuel Sets Only: Check relay K99. Refer to wiring diagrams in Section 7; Check pressure switch wiring. Propane − normally closed connected to common. Natural gas − normally open connected to common; Check pressure switch function (@ 3.5 inch H2O or less, should switch from natural gas to LPG); Check S14 vacuum switch (optional) for proper operation.
  • No output voltage
    Cause: The line circuit breaker is OFF.
    Fix: Find out why the circuit breaker was turned OFF, make sure it is safe to reconnect power, and then throw the circuit breaker ON.
  • The engine lacks power or is unstable
    Cause: Current ambient conditions cause a derate, limiting power to less than rated power.
    Fix: Determine proper derates for ambient conditions. Refer to specification sheet for site derating factors.
  • The field circuit breaker keeps tripping
    Cause: The rotating rectifier assembly (diodes CR1 through CR6) is faulty
    Fix: Shut down the set and check each diode according to Section 7; Service as necessary
  • The engine does not crank in Remote mode
    Cause: The Run-Stop-Remote switch is at Stop. (The Switch-Off light will be flashing.)
    Fix: Push the Run-Stop-Remote switch to Remote.
  • Battery completely discharged
    Cause: Poor battery terminal connection
    Fix: Clean connections, replace and tighten.
  • Output voltage is too high or too low
    Cause: Engine speed is unstable
    Fix: Troubleshoot according to the chart, The Engine Lacks Power or is Unstable
  • Engine will not crank.
    Cause: Fault lamp on
    Fix: Correct fault and reset control.
  • Battery low charge
    Cause: Poor battery connection
    Fix: Clean connections, reconnect and tighten securely.
  • The phase currents are unbalanced
    Cause: The connected loads are distributed unevenly among the phases
    Fix: Shut down the set and redistribute the loads as evenly as possible
  • The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run. FAULT 1
    Cause: The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay.
  • Over Current 1477
  • Output voltage is unstable
    Cause: The voltage has been adjusted improperly
    Fix: Adjust output voltage according to Section 2, AC Control
  • Battery overcharged
    Cause: Charge alternator fault
    Fix: Contact your nearest Cummins Power Generation distributor.

Compiled from service & troubleshooting documentation across every generator set that uses the Ford V-10 6.8L.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterPaper-type element - do not clean, replace—500 hr
Fuel filter—
Oil filter—50 hr
BatteryDilute sulphuric acid (electrolyte) of correct specific gravity per battery label416-0823 Amazon
Belt—
Coolant50% Ethylene Glycol and water33.1 L—
OilHigh-quality multi-viscosity lubricating oil, e.g. Cummins Premium Blue® or equivalent6.2 L—
Spark plug—1000 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

40
ItemActionHoursMonthsNotes
Air cleaner (normal duty filter)Check100 hrPerform more often in extremely dusty conditions; replace element after 500 hours.
All exhaust components and hardware (fittings, clamps, fasteners)Check8 hrDaily; audibly and visually with generator set running
All hardware (fittings, clamps, fasteners, etc.)Check100 hrDaily or after 8 hours.
Bedframe fluid containment (where fitted)Drain8 hrDaily; drain if necessary
Coolant heater(s)Check8 hrDaily.
Coolant levelCheck8 hrDaily.
Coolant level of radiator(s) (water jacket & LTA)Check8 hrDaily
Cooling fan bladesCheck8 hrVisual inspection required daily
Drive belt condition and tensionCheck8 hrVisually check belt for wear or slippage; replace if hard or brittle (Service Engineer)
Engine oil levelCheck8 hrDaily.
Fuel level in tankCheck8 hrDaily or after 8 hours
Fuel lines and hosesCheck8 hrDaily; check for oil, fuel, coolant and exhaust system leaks (Table 5 note 1)
General setInspect8 hrCheck for oil, fuel, cooling and exhaust system leaks; inspect exhaust audibly/visually with set running and repair leaks immediately.
General set inspectionInspect8 hrDaily. Check for oil, fuel, cooling and exhaust system leaks; check exhaust audibly and visually with set running.
Crankcase oilChange50 hrFirst service — Drain and replace crankcase oil after the first 50 hours of operation on new generator sets (break-in).
Engine oil and filterChange250 hr6 moFirst service — Replace after the initial running-in period of 50 hours; contact your authorized distributor (Table 5 note 5)
Engine oil and filterDrain50 hrFirst service — Break-in: drain and replace crankcase oil after first 50 hours of operation on new generator sets.
Air cleanerCheck100 hrMonthly; replace as necessary. Perform more often in extremely dusty conditions.
Battery electrolyte levelCheck100 hr1 moMonthly.
Engine oil and filter (normal duty filter)Change100 hr12 moPerform more often in extremely dusty conditions; perform at least once a year.
Generator air outletCheck100 hr1 moMonthly.
Governor linkageCheck100 hrPerform more often in extremely dusty conditions.
All hardware (fittings, clamps, fasteners)Check250 hr6 mo
Drive beltCheck250 hr6 moVisually check for wear or slippage; replace if hard or brittle.
Engine coolant port capsCheck250 hr6 moReplace after 4 years or 1000 hours.
Exterior of radiatorInspect250 hr6 moInspect for obstructions.
Radiator exteriorInspect250 hr6 moInspect for obstructions.
Radiator hosesCheck500 hr12 moCheck for wear and cracks; replace if hard or brittle.
Radiator hosesInspect250 hr6 moReplace if hard or brittle.
AC generator and controlsCheck500 hr12 moYearly.
Anti-freezeCheck500 hr12 moYearly.
Anti-freeze concentrationCheck500 hr12 moYearly or after 500 hours.
Catalytic converter restrictionTest500 hr12 moMust be performed by a qualified mechanic; replace every 8 years or 2000 hours.
Cooling systemsClean500 hr12 moYearly.
Oxygen sensorInspect500 hr12 moMust be performed by a qualified mechanic; replace every 1,500 hours (recommended).
RadiatorDrain1000 hr24 moDrain and flush.
Spark plugsInspect500 hr12 moReplace every 1,000 hours.
Cylinder headsOther1000 hr24 moOverhaul cylinder heads.
Alternator vibration levelsCheck3000 hrTable 6 (3000 hours)
Fuel injectorsCheck3000 hrTable 6 (3000 hours); to be undertaken by a Service Technician

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceClearance around generator set for service1meter
ClearanceExhaust pipe clearance to combustible wall or partition305mm
ClearanceIsolator base elevation tolerance between isolators0.25inch (6 mm)
ClearanceVibration isolator top plate to base clearance0.25inch
ClearanceVibration isolator top plate-to-base clearance (nominal)0.25inch (6 mm)
GapSpark Plug Gap0.044in (1.1 mm)
GapSpark plug gap0.035in (0.9 mm)
GapSpark plug gap0.044 (1.1 mm)in (mm)
OtherAdjust - Frequency Adjust range5% of nominal frequency
OtherAdjust - Voltage Adjust range5% of nominal voltage
OtherAir cleaner bench/paper element cleaningNot recommendedCummins Inc. does not recommend cleaning paper-type air cleaner elements
OtherBattery charger output - 12 Volt15A
OtherBattery charger output - 24 Volt12A
OtherBattery electrolyte specific gravity (fully charged, corrected)1.260SGat 25 °C (77 °F)
OtherBattery specific gravity, charge required below1.215specific gravity
OtherBattery specific gravity, fully charged1.260corrected; add 0.004 per 10 F above 80 F (27 C)
OtherBattery specific gravity, fully charged (corrected)1.260specific gravitycorrected to 80°F (27°C)
OtherBattery specific gravity, recharge threshold1.215charge battery if reading is below this value
OtherBattery storage charging - further charge interval6monthsat the normal initial charge rate until voltage ceases to rise
OtherBoost Charge interval (if charger fitted with Boost switch)6monthsnormally around every six months per battery manufacturer
OtherCharge battery if specific gravity below1.215SG
OtherCooldown at idle timer0 - 30minutes
OtherLow Fuel warning (yellow lamp)5inches (127 mm) WC or lessdual or single fuel systems
OtherOutput voltage adjustment range (voltage adjust rheostat, optional)±5% of nominal voltage
OtherOvercrank timed cranking periodapproximately 75seconds, including two rest periods
OtherRated To Idle delay0 - 10secondsdefault = 0; Beginning Version 2.303
OtherSecondary regulator initial adjustment (distance from top of regulator to top of set screw), NG, 60 Hz12.1mm
OtherSecondary regulator initial adjustment, NG, 60 Hz13.35mm
OtherSecondary regulator initial adjustment, NG, 60 Hz15.9mm
OtherSpecific gravity temperature correction0.007SG per 10 °C (18 °F)subtract above 25 °C (77 °F), add below
OtherSpecific gravity, at end of charge, ambient frequently above 32 °C (90 °F)1.240 - 1.260SG
OtherSpecific gravity, at end of charge, ambient normally below 32 °C (90 °F)1.240SG
OtherSpecific gravity, electrolyte for filling new cells, ambient frequently above 32 °C (90 °F)1.270 - 1.290SG
OtherSpecific gravity, electrolyte for filling new cells, ambient normally below 32 °C (90 °F)1.270SG
OtherStart Delay0 - 300secondsdefault = 0
OtherStarting cycles (crank/rest)3start cyclesdefault: 3 cycles composed of 15 seconds of cranking and 15 seconds of rest
OtherStop Delay0 - 600secondsdefault = 0
OtherTime Delay To Stop0 - 600seconds
OtherWarm-up at idle time delay0 - 300seconds
PressureConcrete compressive strength for seismic anchors4000PSI
PressureExhaust Backpressure (Max. Allowed)25inch H2O (6.25 kPa)maximum
PressureExhaust backpressure (max allowed)20inch H2O (5.0 kPa)
PressureFuel inlet pressure (LPG liquid withdrawal)312psi (2,153 kPa)
PressureFuel inlet pressure maximum (LPG liquid withdrawal)312psi (2,153 kPa)liquid withdrawal
PressureFuel inlet pressure maximum (NG/LPG vapor withdrawal)13.6inch H2O (3.4 kPa)
PressureFuel inlet pressure minimum (NG/LPG)7.0inch H2O (1.7 kPa)
PressureGaseous fuel supply inlet pressure - maximum operating13.6in. water column (25.4 mmHg)
PressureGaseous fuel supply inlet pressure - minimum operating7.0in. water column (13.07 mmHg)
PressureLO FUEL lamp (fuel supply pressure marginally low)5 (127 mm) WC or lessinches WC
PressureLOP jumper alternate shutdown setting14psi (97 kPa)alternate jumper position (not recommended, see caution)
PressureLP gas pressure at full loadnegative 1.0inch WC (0.249 kPa)full load
PressureLP gas pressure at mixer, full load-1.0inch WC (0.249 kPa)full load
PressureLP gas pressure at mixer, no load-0.5inches WC (0.13 kPa)no load
PressureLP gas pressure at no loadnegative 0.5inches WC (0.13 kPa)no load
PressureLPG Liquid Withdrawal Fuel Flow Inlet Pressure Maximum312psi (2,153 kPa)maximum
PressureLPG gas pressure at mixer, full loadapproximately -1.0inches WC
PressureLPG gas pressure at mixer, no loadapproximately -0.5inches WC
PressureLow Oil Pressure shutdown (red lamp), LOP jumper set to 25 psiless than 25psi (173 kPa)
PressureLow fuel pressure alarm (engine control module)3 (76.2 mm) water columninches WCprimary fuel pressure falls below
PressureLow oil pressure shutdown25psi (172.4 kPa)~10 second time delay after starter disconnect

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50% Ethylene Glycol and waterFleetguard® Compleat ES low-silicate antifreeze, or equivalentStandard concentration 50% Ethylene Glycol and water; must be maintained. Fill cooling system to the bottom of the fill neck in the radiator or expansion tank. Some radiators have two fill necks, both must be filled.
Coolant50/50 coolant solution (50% pure water, 50% antifreeze); 65% antifreeze/35% water if below -37°F (-38°C)33.1 LCooling system capacity with standard radiator 8.8 Gal (33.1 L). Use clean, low-mineral soft water free of chloride, sulfate or acid. Do not use antifreeze containing anti-leak additives.
Coolant50/50 water/antifreeze (65% antifreeze/35% water below -37F/-38C); no anti-leak additivesabove -38°C8.8 Gal (33.1 L)Use soft water low in mineral content.
Coolant50/50 coolant solution (50% pure water and 50% antifreeze)Do not use antifreeze containing anti-leak additives; use soft, low-mineral waterabove -37°C33.1 LIf temperatures below -37 F (-38 C) are possible use 65% antifreeze and 35% water. Cooling system capacity with standard radiator 8.8 Gal (33.1 L).
Engine oilHigh-quality multi-viscosity lubricating oil such as Cummins Premium Blue® or its equivalentConsult your authorized distributor for correct lubricating oil specifications for your operating conditions. Special running-in oils are not recommended.
Engine oilRefer to oil viscosity chart (Figure 5-1)API SJ or SJ/CD6.2 LSelect grade right for the lowest ambient temperature expected.
Engine oilSAE 10W30, 5W30, 15W40API classification SJ, SH or SL6.2 LOil capacity with filters 6.5 Qts (6.2 L). Select viscosity grade for lowest expected temperature; if ambient is consistently below -13°F (-25°C), use a SAE 5W synthetic oil. Do not use oil that is too thick.
Engine oilAPI SJ, SH or SL; SAE 10W30, 5W30 or 15W40 per ambient temperature chartAPIabove -25°C6.5 Qts (6.2 L)Use SAE5W synthetic oil if ambient temperature is consistently below -13F (-25C).
Engine oilSAE 5W syntheticAPI SJ or SJ/CDabove -25°C6.2 LUse SAE 5W synthetic if ambient temperature is consistently below -13 F (-25 C). Pick viscosity grade for lowest temperature expected. Oil capacity with filters 6.5 Qts (6.2 L).
FuelNatural Gas and/or Propane (LPG, liquid or vapor withdrawal)Combination natural gas/LPG sets have separate shutoff solenoid valves and a fuel pressure switch for automatic changeover.
FuelNatural Gas and/or Propane (LPG, liquid or vapor)Gaseous fuel; engine has a gas mixer serving both fuels with separate shutoff solenoid valves and pressure switch for automatic changeover.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
121Speed Signal LostCategory AShutdown
135Oil Pressure Sensor HCategory CWarning
141Oil Pressure Sensor LCategory CWarning
143Pre-Low Oil PresCategory DWarningIf generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure.
144Coolant Sensor HighCategory CWarning
145Coolant Sensor LowCategory CWarning
146Pre-High Coolant TempCategory DWarningReduce load if possible by turning off non-critical loads; check air inlets/outlets for obstructions. If engine can be stopped, follow code 151 procedure.
151High Coolant TempCategory DShutdownAllow engine to cool. Check coolant level and leakage points, obstructions to cooling airflow, fan belt, blower fan/circulation pumps; reset control and restart.
197Low Coolant LevelCategory D (optional)WarningIf generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure.
234OverspeedCategory AShutdown
235Low Coolant LevelCategory D (optional)ShutdownAllow engine to cool. Check coolant level and replenish, look for leakage points and repair; reset control and restart.
359Fail To StartCategory DShutdownOpen any closed fuel shutoff valve; check for dirty/plugged air filter and replace if necessary; check gaseous fuel delivery; reset control and restart.
415Low Oil PressureCategory DShutdownCheck oil level, lines and filters; replenish oil if low; reset control and restart.
441Low Bat VoltageCategory DWarningCheck/recharge/replace discharged or defective battery; clean and tighten battery cable terminals; check battery charger float level.
442High Bat VoltageCategory DWarningCheck float level on battery charger if applicable (lower float level).
1123Shutdown After BSCategory AShutdown
1124Delayed ShutdownCategory EWarning
1131Battle Sh ActiveCategory EWarning
1311Customer Input #1Category EProgrammable via InPower service tool: enable/disable, status (warning/shutdown/none), active open/closed, and display name.
1312Customer Input #2Category EProgrammable via InPower service tool: enable/disable, status (warning/shutdown/none), active open/closed, and display name.
1313-1316Network Fault 1 thru 4Category E
1317Customer Input #3Category EProgrammable via InPower service tool: enable/disable, status (warning/shutdown/none), active open/closed, and display name.
1318Service EngineCategory B (begin spec J)WarningIndicates emissions criteria might not be met: engine running in open loop, lean mixture, rich mixture, or failed fuel system component.
1334Crit Scaler ORCategory AShutdown
1335Noncrit Scaler ORCategory BWarning
1416Fail To ShutdownCategory CWarning
1417Powr Down ErrorCategory DWarningIndicates controller cannot power down because of unknown condition; possible battery drain. Contact an authorized service center.
1433Emergency StopCategory DShutdownPull emergency stop button out; move O/Manual/Auto switch to O; press Fault Acknowledge/Reset button; select Manual or Auto as required.
1434Remote E-StopCategory DShutdownSee code 1433 to reset.
1435Low Coolant TempCategory DWarningCheck coolant heater power connection/fuse; check for low coolant level and replenish, repairing leaks as needed.
1438Fail To CrankCategory DShutdownPossible fault with control, speed sensing or starting system. See code 441 for corrective action.
1442Weak BatteryCategory DWarningBattery voltage at/below weak-battery trip point during cranking. See code 441 for corrective action.
1443Battery FailedCategory DShutdownDead battery, engine will not start. See code 441 for corrective action.
1444KW OverloadCategory BWarning
1445Short CircuitCategory AShutdown
1446High AC VoltageCategory AShutdown
1447Low AC VoltageCategory AShutdown
1448Under FrequencyCategory DShutdownCheck for dirty/plugged air filter and replace; check by disconnecting load and restarting; fuel system may require adjustment; check gaseous fuel delivery; reset and restart.
1449Over FrequencyCategory AWarning
1452Gen CB Not CloseCategory AWarning
1453Gen CB Not OpenCategory AWarning
1459Reverse PowerCategory AShutdown
1461Loss Of FieldCategory AShutdown
1466Modem FailureCategory CWarning
1468Network ErrorCategory CWarning
1469Speed/Hz MatchCategory AShutdown
1471Over CurrentCategory BWarning
1472Over CurrentCategory AShutdown
1477Over CurrentOver CurrentShutdown
2263Battery TemperatureBattery temperature too high (reaches 55 °C [131 °F]) - battery charger fault messageWarning
2323-2326Network Fault 5 thru 8Category E
2327PTC FaultCategory BWarning
2329Low S1 FrequencyCategory EWarning
2331Low S1 VoltageCategory EWarning
2335Excitation FaultCategory AShutdown
2336Memory ErrorCategory AShutdown
2337Pwr Tran DisabledCategory CWarning
2338Pwr Tran FailureCategory CWarning
2339Pwr Down EnabledCategory EWarning
2341High Control TempCategory BWarning
2342Too Long In Idle (10 min.)Category EWarningIndicates genset has been in Idle mode too long (10 minutes maximum).
2358High S1 VoltageCategory EWarning
2396S1 CB Not CloseCategory EWarning
2397S1 CB Not OpenCategory EWarning
2966PTC TimeoutCategory CWarning
2967Governor FaultCategory CWarning
2968AVR FaultCategory CWarning
2969LON FailureCategory CWarning
2972Field OverloadCategory AShutdown
Fault 1Fault 1 (red)Engine shut down because of a system fault; part of a 10-second time-delay shutdown circuit (customer-wired).Shutdown
FAULT 1FAULT 1Red lamp indicates an undedicated fault; may be field programmed as shutdown or non-shutdown and as timed or non-timed (normally set for timed shutdown).ShutdownNature of fault determined when set installation is designed.
Fault 2Fault 2 (red)Engine shut down because of a system fault; part of a non-time-delay shutdown circuit (customer-wired).Shutdown
FAULT 2FAULT 2Red lamp indicates same features as Fault 1 (normally set for non-timed shutdown).ShutdownNature of fault determined when set installation is designed.
HI ENG TEMPHI ENG TEMPRed lamp indicates engine has shut down because of critically high engine temperature (above 230 F / 110 C).ShutdownAllow engine to cool; check coolant level and airflow; reset control and restart.
High Engine TemperatureHigh Engine Temperature (red)Engine shut down due to excessively high coolant temperature (greater than 230°F / 110°C).Shutdown
LO FUELLO FUELYellow (optional) lamp indicates fuel supply pressure is marginally low (5 inches [127 mm] WC or less).WarningCheck for partially closed shutoff valve or empty propane supply tank; for natural gas check with the gas utility.
LO OIL PRESLO OIL PRESRed lamp indicates engine has shut down because of critically low oil pressure (below 25 psi / 172.4 kPa).ShutdownCheck oil level, lines and filters; replenish if low; reset control and restart.
LOW ENG TEMPLOW ENG TEMPYellow lamp lights if engine temperature is marginally low for starting (70 F / 21 C or lower); may indicate an inoperative coolant heater.WarningCheck coolant heater operation, power supply, fuse/cord and coolant level.
Low Engine TemperatureLow Engine Temperature (yellow)Engine temperature less than 65°F (18°C) or 90°F (32°C); possibility engine might not start.Warning
Low FuelLow Fuel (yellow, optional)Fuel supply pressure is 5 inches (127 mm) WC or less; also indicates operation on secondary fuel supply for dual-fuel sets.Warning

Showing the first 80 of 93 codes.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Gaseous Fuel Adjustments adjustment

⚠ Fuel is highly flammable; do not allow cigarettes, flame, pilot lights, arcing switches or equipment in area or areas sharing ventilation.

Tools: Exhaust gas analyzer (for emission sensitive areas)

  1. Start the engine and let set warm up under partial load (at least 1/4 rated load); start with natural gas if dual fuel.
  2. Connect full rated load and turn power adjust valve to full-rich.
  3. Slowly turn adjust valve towards lean until engine begins to lose speed, then back towards rich until engine carries full load smoothly.
  4. If equipped for natural gas and LPG, switch to LPG by closing manual shutoff valve in the natural gas supply line.
  5. Reconnect full rated load and turn LPG flow adjustment valve clockwise until engine loses speed, then slowly back counterclockwise until engine carries full load smoothly.
Gaseous Fuel System Adjustment adjustment

⚠ Fuel is highly flammable and may cause severe personal injury and property damage. Do not allow cigarettes, flame, pilot lights, arcing switches or equipment in area or areas sharing ventilation.

Tools: Exhaust gas analyzer (for emission sensitive areas)

  1. Start the engine and let the set warm up under a partial load (at least 1/4 rated load); on dual fuel sets start with natural gas.
  2. Connect full rated load and turn the manual fuel valve two turns counterclockwise.
  3. Slowly turn the manual fuel valve clockwise (lean) until the engine begins to lose speed.
  4. Slowly turn it counterclockwise (rich) until the engine carries the full load smoothly.
  5. On dual fuel sets, switch to LPG by closing the manual shutoff valve in the natural gas supply line.
  6. Reconnect full rated load and turn the LPG flow adjustment valve clockwise until the engine begins to lose speed.
  7. Slowly turn it back counterclockwise until the engine carries full load smoothly.
Magnetic Speed Pickup Unit Adjustment adjustment
  1. Measure MPU resistance; replace if not between 1,000 and 1,050 ohms.
  2. With MPU removed, rotate ring gear until a tooth lines up in the center of the mounting hole.
  3. Thread pickup in gently by hand until it just touches the ring gear tooth.
  4. Back the pickup out 1/4 turn and set the locknut.
  5. Verify MPU output voltage at cranking speed is at least 1.5 VAC; replace MPU if less.
Output Voltage Adjustment adjustment
  1. Adjust output voltage plus or minus five percent of nominal voltage using the Voltage Adjust rheostat (optional) on the control panel.
  2. Call your distributor if the required voltage cannot be obtained by this adjustment.
Type A Gaseous Fuel Adjustment (Naturally Aspirated) adjustment

⚠ Gaseous fuels are flammable and explosive

  1. Disconnect all loads, shut down set, and disconnect governor linkage at the carburetor.
  2. Start engine and hold throttle closed by hand to prevent overspeed.
  3. Adjust throttle idle position screw to obtain a frequency of 25-35 Hz.
  4. Turn idle adjusting screw counterclockwise until engine becomes unstable, then clockwise to regain stability.
  5. Reconnect governor linkage.
  6. Connect full rated load and turn main fuel valve to full-rich, then lean until engine loses speed, then back to rich.
  7. If equipped for LPG, switch to LPG and adjust LPG flow valve similarly under full load.
Vibration Isolator Installation and Adjustment Procedure adjustment
  1. Place vibration isolators on the generator set support structure; shim or grout so all isolator bases are within 0.25 inch (6 mm) elevation of each other.
  2. Loosen the side snubber lock nuts so the top plate is free to move vertically and horizontally; verify alignment with base and springs.
  3. Place the generator set onto the isolators while aligning the skid mounting with the threaded isolator hole.
  4. Adjust isolators with the leveling bolt to level the set; nominal clearance between top plate and base is 0.25 inch (6 mm) or greater.
  5. If radiator and engine/alternator are mounted on separate skids, make both skids level for proper fan belt alignment.
  6. If the set is not level, adjust leveling bolts until level with sufficient, roughly equal clearance on all isolators.
  7. Lock the leveling bolt in place with the lock nut.
  8. Leave snubber nuts loose to provide better isolation between the generator set and support structure.
Checking AC Electric System While Running diagnostic

⚠ High voltages are present inside the control box and generator output box when the set is running. Do not open the boxes while the set is running.

  1. Check the frequency meter; generator frequency should be stable and match the nameplate rating.
  2. Turn the phase selector switch to each line-to-line phase selection (L1-L2, L2-L3, L3-L1) and read the AC voltmeter; at no load voltage should match nameplate rating.
  3. Turn the phase selector switch to each phase (L1, L2, L3) and read the AC ammeter; at no load current should be zero.
  4. Push the Reset/Lamp switch; all indicator lamps should light, confirming all bulbs are on.
  5. Have any burned out bulbs replaced.
Verify Overspeed Fault Detection diagnostic

Tools: special tool P/N 420-0604

  1. For Type A sets, move the throttle lever/linkage to increase RPM to the overspeed shutdown range.
  2. For Type B sets, remove the two screws securing the throttle body cover and remove cover.
  3. Use special tool P/N 420-0604 to turn the end of the throttle shaft.
  4. With genset operating at no load, slowly rotate the shaft clockwise until RPM reaches the overspeed limit and shuts down.
  5. Replace the throttle body cover after completing the test.
Battery Connections (Prestart Preparation) installation

⚠ Accidental starting can cause severe personal injury or death.

⚠ Ignition of explosive battery gases can cause severe personal injury or death.

⚠ Ventilate battery area before working on or near battery. Arcing, flames, pilot lights and sparks can ignite battery gas.

  1. Make sure the Run/Off/Auto switch on the control panel is set to Off before connecting battery cables.
  2. Connect the positive battery cable before connecting the negative battery cable to prevent arcing.
  3. Connect the negative (–) battery cable last to prevent arcing.
  4. Service the battery as necessary; connect a separate battery charger if an ATS without built-in charge circuit is installed.
CT Installation Requirements installation

⚠ Each of the operations described should be done only by persons trained and experienced in electrical maintenance.

  1. The CT has a dot on one side; this dot must face toward the generator (conventional current flowing into the dot). A dot also indicates pin 1 of the CT.
  2. CT21 – U load leads (A phase); CT22 – V load leads (B phase); CT23 – W load leads (C phase).
  3. Route the appropriate load wires through each CT.
  4. The CTs have dual secondaries (3 pins). The secondary wire marked 1 connects to pin 1; wire marked 2/3 connects to pin 2 for high voltage gensets or pin 3 for low voltage gensets.
Connecting the Battery to the Generator Set installation

⚠ A battery must not be fitted to a generator set without charge if the specific charge of the electrolyte has fallen below 1.240 during storage.

⚠ Even momentary incorrect connection can cause damage to the electrical system.

Tools: Insulated wrench

  1. Secure the battery. Battery hold-down bolts must be tight, but not over-tight.
  2. Smear the terminals with petroleum jelly, if necessary.
  3. Fit the vents firmly in position and ensure that the battery is clean and dry.
  4. Verify correct polarity when connecting the battery to the set.
  5. Use an insulated wrench to connect the positive generator cable first, followed by the negative cable. Terminal connections must be tight, but not over-tight.
Installation Checklist - Prestart installation

⚠ Improper wiring can cause a fire or electrocution.

  1. Verify wattage capacity sufficient for anticipated load.
  2. Verify at least 3 feet clearance around generator set.
  3. Verify genset located away from flooding.
  4. Check fuel tanks, lines and shutoff valves meet codes and are free of leaks.
  5. Check exhaust system for leaks, secure connections, condensation drain, insulation.
  6. Check AC and DC wiring sizes, insulation, conduits and connections meet codes.
  7. Service engine with oil and coolant.
  8. Verify batteries installed, serviced and charged.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
Line 0 or NeutralN / N / NLoad terminal line designations
Line 1L1 / A / ULoad terminal line designations
Line 2L2 / B / VLoad terminal line designations
Line 3L3 / C / WLoad terminal line designations
TB1 Customer Faults1=Customer Fault 1, 2=Ground Fault, 3=Low Fuel, 4=Rupture Basin FaultDefault settings, beginning spec J customer input #4 not available
TB1 Customer Relays1=Common Warning, 2=Common Shutdown, 3=Not in Auto, 4=Ready to LoadDefault settings; NO contacts rated 2 amps at 30 VDC

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Aftermarket parts that fit this engine

2

Parts listed by aftermarket suppliers as fitting this engine — leads compiled from supplier catalogs; verify the exact part for your serial number.

Common questions

What is the oil capacity of the Ford V-10 6.8L?

The Ford V-10 6.8L engine has an oil capacity of 5.5 liters.

What is the displacement of the Ford V-10 6.8L?

The Ford V-10 6.8L has a displacement of 6.8 liters with 10 cylinders.

Which generators use the Ford V-10 6.8L engine?

The Ford V-10 6.8L powers 2 generator set(s), including Cummins/Onan GGHG, Cummins/Onan GGHH.

What is a common problem with the Ford V-10 6.8L engine?

A commonly reported issue on generators using the Ford V-10 6.8L is: The engine does not crank in Run mode. Cause: The Emergency Stop switch has been used. (The switch button is lit.). Fix: Pull the Emergency Switch button. To reset the engine control, push the Run-Stop-Remote switch to Stop and the Reset switch to Reset. Then push the Run-Stop-Remote switch to Run to start the genset..