The Cummins/Onan QSX15-G8 is a turbocharged with air-to-air charge air cooling engine rated at 1500 rpm. It powers generator sets from Cummins/Onan, including the 352DFEH and DFE. It holds 83.3 L (22.0 gal) of oil.
Also known as: Cummins QSX15-G8
Part of the Cummins/Onan QSX15 engine family — 7 variants share parts & fitment.
| Oil capacity | 83.3 L |
|---|---|
| Aspiration | Turbocharged with air-to-air charge air cooling |
| Rated speed | 1500 rpm |
How to read your Cummins/Onan engine serial & model number →
Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan QSX15-G8.
| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Air cleaner | Check | 250 hr | 6 mo | X1; replace as necessary; refer to QSX15 engine manual |
| All hardware (fittings, clamps, fasteners, etc.) | Check | 100 hr | Daily or after 8 hours | |
| Anti-freeze and DCA concentration | Check | 250 hr | 6 mo | X1; refer to QSX15 engine manual |
| Coolant heater(s) | Check | 100 hr | Daily or after 8 hours | |
| Drive belt | Check | 250 hr | 6 mo | X1; refer to Cummins QSX15 Series Engine Operation and Maintenance Manual for interval/procedure |
| Engine oil level | Check | 8 hr | Daily or after 8 hours | |
| Fuel filter(s) | Drain | 250 hr | 6 mo | X1; refer to QSX15 engine manual |
| Genset | Inspect | 8 hr | Daily; check for oil, fuel, cooling and exhaust system leaks | |
| Radiator hoses for wear and cracks | Check | 250 hr | Daily or after 8 hours | |
| Charge Air Piping | Check | 50 hr | Weekly | |
| Coolant heater | Check | 50 hr | Weekly or after 50 hours | |
| Coolant level | Check | 50 hr | Weekly or after 50 hours | |
| Exhaust condensate trap | Drain | 100 hr | Drain water to prevent it flowing back into the engine | |
| Fuel level | Check | 50 hr | Weekly or after 50 hours | |
| Oil level | Check | 50 hr | Weekly or after 50 hours | |
| Air cleaner | Clean | 100 hr | Monthly or after 100 hours; clean if required, perform more often in dusty conditions | |
| Battery charging system | Check | 100 hr | Monthly or after 100 hours | |
| Battery electrolyte level | Check | 200 hr | Monthly or After 100 Hrs | |
| Fuel tank water and sediment | Drain | 100 hr | Monthly or after 100 hours | |
| General set inspection | Inspect | 100 hr | Monthly or after 100 hours (Table 5-1, footnote X2): check for oil, fuel, cooling and exhaust system leaks; check exhaust system audibly and visually with set running | |
| Generator air outlet | Check | 100 hr | Monthly or After 100 Hrs | |
| Radiator hoses | Check | 500 hr | 12 mo | Monthly or After 100 Hrs; check for wear and cracks |
| Starting batteries | Check | 100 hr | Check condition and terminals | |
| Air cleaner | Replace | 250 hr | Check air cleaner; replace as necessary. Refer to QSX15 manual. | |
| Crankcase oil and filter | Change | 250 hr | 12 mo | Prime power: every 6 months or 250 hours; standby: every 12 months or 250 hours, whichever comes first |
| Drive belt tension | Check | 250 hr | 6 mo | Visually check belt for wear or slippage; replace if hard or brittle |
| Engine oil and filter | Replace | 250 hr | 6 mo | X1; 6 Months or After 250 Hrs; refer to QSX15 engine manual |
| Radiator Hoses | Inspect | 250 hr | 6 mo | Check for wear & cracks |
| Water coolant filter | Replace | 250 hr | 6 mo | X1; 6 Months or After 250 Hrs |
| Air cleaner element | Change | 500 hr | 12 mo | Yearly or after 500 hours; clean if required more often |
| Coolant filter | Change | 500 hr | 12 mo | Yearly or after 500 hours; refer to engine operation and maintenance manual |
| Cooling system | Clean | 500 hr | 12 mo | Yearly or after 500 hours; drain and replace coolant mixture |
| Crankcase breather | Clean | 500 hr | 12 mo | Yearly or after 500 hours |
| Engine oil and filter | Change | 500 hr | 12 mo | Table 5-1, footnote X1 |
| Fuel filter | Change | 500 hr | 12 mo | Table 5-1, footnote X1 |
| Fuel filters | Change | 500 hr | 12 mo | Yearly or after 500 hours |
| Generator insulation resistance | Test | 500 hr | 12 mo | Follow periodically throughout life of set or if generator has set idle with no heaters; contact authorized service center |
| Water coolant filter | Change | 500 hr | 12 mo | Table 5-1, footnote X1 |
| Cooling systems | Clean | 500 hr | 12 mo | X1; 1 Year |
| Fuel filter | Replace | 12 mo | X1; 1 Year |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Exhaust pipe clearance from combustible wall or partition | 12 | inches (305 mm) | minimum |
| Clearance | Exhaust pipe clearance to combustible wall/partition | 12 | inches (305 mm) | |
| Clearance | Float switch assembly float lift clearance below C-clip stop | 1/8 | inch (3 mm) | use a feeler gauge |
| Clearance | Fuel line clearance from electrical wiring | 1/2 | inch (12.7 mm) | |
| Clearance | Fuel line clearance from hot exhaust parts | 2 | inch (51 mm) | |
| Clearance | Generator mount pre-load steel spacer thickness | 1 3/4 | inch | two spacers under both stator foot brackets |
| Clearance | Generator-to-engine angular alignment (T.I.R.) | .001 in. per inch of radius (center of shaft to indicator axis), maximum | in | 750 kW gensets and larger |
| Clearance | MPU installation gap adjustment | back out 1/4 turn after touching gear tooth | turn | |
| Clearance | Vibration isolator base elevation difference | 0.25 | inch (6 mm) | shimmed or grouted within this of each other |
| Clearance | Vibration isolator clearance | 0.25 | inch (6 mm) | |
| Clearance | Vibration isolator nominal clearance (leveling bolt) | 0.25 | inch (6 mm) | minimum, or greater |
| Gap | Coolant level below radiator cap lower sealing surface | 3/4 inch (18 mm) | inch (mm) | |
| Other | AVR Droop setting | 5 | % at full load, 0 PF | |
| Other | AVR voltage regulation (load regulation) | approximately ±0.5 | % RMS | |
| Other | Ambient temperature below which coolant heaters recommended (NFPA 110) | 40 | °F | |
| Other | Battery CCA (minimum) | 1400 | CCA | Cold Soak @ 0° F (-18° C) |
| Other | Battery specific gravity (fully charged) | 1.26 | specific gravity | at 80 F (27 C) |
| Other | Battery specific gravity (high ambient, above 95F/35C) | 1.225 | recommended to reduce electrolyte loss | |
| Other | Battery specific gravity (recharge threshold) | below 1.260 | ||
| Other | Battery specific gravity charge threshold | 1.215 | corrected | charge battery if reading below |
| Other | Battery specific gravity fully charged | 1.260 | corrected | add 0.004 per 10 F above 80 F (27 C) |
| Other | Battery terminal cleaning solution | 1/4 pound baking soda to 1 quart water | ||
| Other | CAN datalink main trunk maximum length | 40 | meters | no more than 30 devices |
| Other | CAN datalink stub maximum length | 1 | meter | stub from main trunk to each module |
| Other | CAN datalink transmission speed | 250 | KBaud | |
| Other | Charge battery if specific gravity below | 1.215 | specific gravity | |
| Other | Fully charged battery corrected specific gravity | 1.260 | specific gravity | corrected reading @ 80 F (27 C) |
| Other | GOV GAIN default value for paralleling applications | 70 | % | |
| Other | Mounting bolt size | 5/8 | inch or 16 mm | |
| Other | Mounting bolts | 5/8 inch or 16 mm | inch / mm | anchored mounting bolts |
| Other | Output frequency adjustment (PCC) | +/- 5 | % | set running under normal parameters |
| Other | Over current warning threshold | 110 | % of rated | |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal | 55 | Hz | reset 53 Hz |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal | 65 | Hz | reset 63 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal | 45 | Hz | reset 47 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal | 55 | Hz | reset 57 Hz |
| Other | Over/Under Voltage Sensor Module time delay | typically 25 percent, approximately 2.5 | seconds | |
| Other | Overcrank cranking limit | 75 | seconds | three 15-second cranking cycles with two 15-second rest periods |
| Other | REG VHZ (underfrequency roll-off) adjustable range | 1 through 50; normal range 7 through 21 | ||
| Other | Short circuit shutdown threshold | 175 | % of rated current | |
| Other | Specific gravity correction | 0.004 | gravity point per 10 F above 80 F (27 C) | |
| Other | Start delay adjustment range | 0 to 300 | seconds | |
| Other | Start delay adjustment range (PCC) | 0 to 300 | seconds | Auto mode remote starting |
| Other | Stop delay adjustment range | 0 to 600 | seconds | |
| Other | Stop delay adjustment range (PCC) | 0 to 600 | seconds | Auto mode remote stopping |
| Other | Under Frequency Roll Off (UFRO) knee point, 50 Hz units | 48 to 49 | Hz | |
| Other | Under Frequency Roll Off (UFRO) knee point, 60 Hz units | 58 to 59 | Hz | |
| Pressure | Air cleaner element cleaning compressed air pressure | 30 | psi (207 kPa) | nozzle held at least 1 inch (25 mm) away |
| Pressure | Engine oil pressure (displayed example) | 75 | PSI | |
| Pressure | Engine oil pressure - K19 normal | 50-70 | psi (345-482 kPa) | run mode |
| Pressure | Engine oil pressure - K38 normal | 45-65 | psi (310-448 kPa) | run mode |
| Pressure | Engine oil pressure - K50 normal | 50-70 | psi (345-482 kPa) | run mode |
| Pressure | Engine oil pressure - L10/M11 normal | 30-50 | psi (207-345 kPa) | run mode |
| Pressure | Engine oil pressure - NTA 855 normal | 35-50 | psi (241-345 kPa) | run mode |
| Pressure | Engine oil pressure - V28 normal | 50-90 | psi (345-620 kPa) | run mode |
| Pressure | Engine oil pressure shutdown limit - L10/M11 | 20 | psi (138 kPa) | run mode value |
| Pressure | Engine oil pressure shutdown limit - L10/M11 | 8 | psi (55 kPa) | idle mode value |
| Pressure | Engine oil pressure warning limit - L10/M11 | 12 | psi (83 kPa) | idle mode value |
| Pressure | Engine oil pressure warning limit - L10/M11 | 25 | psi (172 kPa) | run mode value |
| Pressure | Fuel transfer pump maximum inlet restriction capability | 16 | inch Hg | approximately equivalent to 20 feet of diesel |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | Refer to Cummins QSX15 Series Engines Operation and Maintenance Manual for coolant recommendations/specifications | 58.0 L | Cooling System (Capacity Std. Radiator) printed as 15.3 Gal (58 L); check anti-freeze and DCA concentration | ||
| Coolant | Balanced coolant mixture of water and antifreeze | Refer to Cummins engine Operation and Maintenance Manual | 90.0 L | Capacity with standard radiator 24 Gal (90 L); drain and replace mixture every year or after 500 hours; add until 3/4 inch (18 mm) below radiator cap lower sealing surface | |
| Coolant | soft water / E.G. / DCA mixture | Cooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist). | |||
| Engine oil | Refer to Cummins QSX15 Series Engines Operation and Maintenance Manual for lubricating oil classification/viscosity | 58.0 L | Oil Cap. w/Filters printed as 26 Gallons (58 L); gense is shipped filled with correct type and quantity of oil | ||
| Fuel | ASTM No. 2 diesel | Cummins engines normally use ASTM No. 2 diesel fuel. | |||
| Fuel | Diesel | Day tank fuel transfer pump maintains reservoir of diesel fuel in the day tank. | |||
| Fuel | diesel | Refer to Cummins QSX15 Series Engines Operation and Maintenance Manual for fuel recommendations; do not use zinc coated or copper fuel lines with diesel fuel; keep fuel supply tanks as full as possible | |||
| Grease | Lithium based grease, Mobilux No. 2 or Shell Alvania R3 | -30°C to 120°C | 2.74 oz (81 ml) | End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity. | |
| Other | Donaldsons D1400 solvent | Soak air cleaner filter element at least 15 minutes in water and D1400 solvent to remove soot, carbon and dirt |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 101 | IDLE MODE | Indicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. | Warning | Remove ground from engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Local or remote Emergency Stop; engine shuts down and will not crank | Shutdown | Turn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required. |
| 111 | Internal ECM error | Internal ECM error | Shutdown | |
| 1118 | Prelube relay driver | Warning | ||
| 112 | Actuator not responding | Category A | Shutdown | |
| 1121 | Failed to Disconnect | Warning | ||
| 1122 | Rated/Idle Trans | Info | ||
| 1123 | Shutdown After Battle Short | A shutdown fault occurred while Battle Short was enabled and Battle Short transitioned from enabled to disabled | Warning | Review the Fault History and perform corrective action |
| 1124 | Delayed Shutdown | Provides advanced warning of an impending generator set shutdown to loads which cannot handle sudden power loss | Warning | A shutdown fault is present; review fault history |
| 113 | Actuator sensor fault | Category B | Warning | |
| 1131 | Battle Short Active | Battle short mode has been activated | Warning | Battle short function enabled |
| 115 | No speed signal | No speed signal | Shutdown | |
| 116 | Time press sensor high | Time press sensor high | Shutdown | |
| 117 | Time press sensor low | Time press sensor low | Shutdown | |
| 118 | Pump press sensor high | Pump press sensor high | Warning | |
| 119 | Pump press sensor low | Pump press sensor low | Warning | |
| 121 | Speed Signal Lost | No engine speed signal | Warning | |
| 1219 | Utility CB tripped | Warning | ||
| 122 | Manifold air press sensor | Manifold air press sensor | Warning | |
| 1222 | Power transfer not in auto | Warning | ||
| 1223 | Utility frequency sensor | Warning | ||
| 1224 | Gen over voltage sensor | Warning | ||
| 1225 | Gen under voltage sensor | Warning | ||
| 1226 | genset frequency sensor | Warning | ||
| 123 | Manifold air press sensor | Manifold air press sensor | Warning | |
| 1245 | CAN - Engine Shutdown | The PCC received a shutdown message from the ECM | Shutdown | Refer to the E-Controls service tool and the engine service manual |
| 1246 | CAN - Unknown Engine Fault | The PCC received an unknown message from the ECM | Warning | Refer to the E-Controls service tool and the engine service manual |
| 1247 | CAN - Engine Unannounced Fault | The PCC received an unknown message from the ECM | Warning | Refer to the E-Controls service tool and the engine service manual |
| 1248 | CAN - Engine Warning Fault | The PCC received an unknown message from the ECM | Warning | Refer to the E-Controls service tool and the engine service manual |
| 1311 | Customer input #1 | Optional customer-selected fault, e.g. Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic/Air Pressure | Programmable via service tool: enable/disable, status/warning/shutdown, active closed/open, custom display name | |
| 1311, 1312, 1317, 1318 | Customer Input | Nature of the fault is an optional customer selection | Disconnect signal lead from TB1 (CUST_IN1 TB1-4, CUST_IN2 TB1-5, CUST_IN3 TB1-6, CUST_IN4 TB1-7) and reset the control; if the message clears, external wiring has a short/open or the active input selection (closed/open) is not correct | |
| 1312 | Customer input #2 | Optional customer-selected fault | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1313 | Network Fault 1 thru 4 | Network Fault 1 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1313-1316 | Network Fault 1 Through 4 | Indicates network input (#1-#4) is in an active state | Each fault function can be programmed (using the service tool) as Status, Warning, or Shutdown; change display name using up to 19 characters | |
| 1314 | Network Fault 2 | Network Fault 2 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1315 | Network Fault 3 | Network Fault 3 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1316 | Network Fault 4 | Network Fault 4 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1317 | Customer input #3 | Customer input #3 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1318 | Customer input #4 | Customer input #4 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1319 | High alternator temp | High alternator temp | Warning | |
| 1321 | Common warning driver | Common warning driver | Warning | |
| 1322 | Load gov kW setpoint oor hi | Load gov kW setpoint oor hi | Shutdown | |
| 1323 | Load gov kW setpoint oor lo | Load gov kW setpoint oor lo | Shutdown | |
| 1324 | Load gov kVAR oor hi | Load gov kVAR oor hi | Warning | |
| 1325 | Load gov kVAR oor lo | Load gov kVAR oor lo | Warning | |
| 1326 | Backup starter disconnect | Category B | Warning | |
| 1327 | Load gov kW analog oor | Load gov kW analog oor | Shutdown | |
| 1328 | Genset CB tripped | Genset CB tripped | Warning | |
| 1329 | AVR DC power failure | Category B | Warning | |
| 1331 | AVR driver shorted | Category A | Shutdown | |
| 1332 | Manual switch oor lo | Manual switch oor lo | Shutdown | |
| 1333 | Manual switch oor hi | Manual switch oor hi | Shutdown | |
| 1334 | Critical scaler oor | Critical scaler oor | Shutdown | Correct the feature/calibration entered into the control |
| 1335 | Noncrit Scaler Out Of Range | Non critical scaler oor | Warning | Correct the feature/calibration entered into the control |
| 1336 | Cooldown complete | Cooldown complete | Shutdown | |
| 1337 | No Message | Network wink | Info | |
| 1341 | Load demand stop | Load demand stop | Shutdown | |
| 1342 | Slot 0 card | Slot 0 card | Shutdown | |
| 1343 | Slot 1 card | Slot 1 card | Shutdown | |
| 1344 | Slot 2 card | Category A | Shutdown | |
| 1345 | Slot 3 card | Slot 3 card | Shutdown | |
| 1346 | Slot 4 incorrect | Slot 4 incorrect | Shutdown | |
| 1347 | Slot 5 card | Category A | Shutdown | |
| 1348 | Slot 6 card | Category A | Shutdown | |
| 1349 | Slot 7 card | Category A | Shutdown | |
| 135 | Oil pressure sensor | Oil pressure sensor | Warning | Verify fault simulation not enabled (InPower); inspect sensor and engine harness connector pins; use oil pressure sensor simulator to check control response, replace sensor if it responds; check P7-13, 17, 21 for short (>200k ohms OK) and open (10 ohms or less OK) |
| 1351 | Slot 4 / network enabled | Slot 4 / network enabled | Warning | |
| 141 | Oil pressure sensor | Oil pressure sensor | Warning | Verify fault simulation not enabled; inspect sensor/harness connector pins; use simulator to check control response; check P7-13, 17, 21 short/open |
| 1414 | Run relay contact | Run relay contact | Warning | |
| 1415 | Run relay driver | Run relay driver | Warning | |
| 1416 | Fail to shutdown | Fail to shutdown | Warning | Status - indicates the Fault Bypass mode is enabled (used primarily by service personnel for troubleshooting). The genset ignores the majority of system shutdown faults. |
| 1417 | Powr Down Error | The control has failed to go to sleep | Warning | Possible base board fault |
| 1419 | Fuel rail driver | Fuel rail driver | Warning | |
| 1421 | Timing rail driver #1 | Timing rail driver #1 | Warning | |
| 1422 | Timing rail driver #2 | Timing rail driver #2 | Warning | |
| 1424 | High side driver | High side driver | Warning | |
| 1427 | Overspeed relay driver | Overspeed relay driver | Warning | |
| 1428 | LOP shutdown relay driver | LOP shutdown relay driver | Warning | |
| 143 | Pre-Low Oil Pressure | Low oil pressure | Warning | Verify fault simulation not enabled; check oil level, lines and filters; use oil pressure sensor simulator; check +5 VDC at sensor (E1-A) and at P7-21; use simulator to P7-13 (OP OUT) and P7-17 (OP COMM); isolate to harness or base board |
| 1433 | Emergency stop - local | Local Emergency Stop | Shutdown | Pull the Emergency stop button out; move the O/Manual/Auto switch to O; press the front panel Fault Acknowledge/Reset button; select Manual or Auto as required |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.
Tools: Dial indicator, Shims
⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.
⚠ Do not bar engine over by prying on fan blade.
Tools: dial indicator
Tools: dial indicator holding device with magnetic base or clamp
Tools: dial indicator
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.
Tools: two 1 3/4 inch T x 2 inch W x 6 inch L steel spacers, adequate lifting device
Tools: calibrated voltmeter
⚠ Accidental starting can cause severe personal injury or death; disconnect negative (-) battery cable with insulated wrench.
⚠ Set generator set to off mode before disconnecting/connecting harness connectors.
Tools: True RMS meter, Insulated wrench, Jumper leads
⚠ HIGH VOLTAGE. Touching uninsulated high voltage parts inside the control box can result in severe personal injury or death.
Tools: Voltmeter, Jumpers, 12 volt battery
Tools: calibrated ammeter
⚠ Contacting high voltage components can cause electrocution, resulting in severe personal injury or death.
Tools: calibrated RMS multimeter (Fluke 87 or 8060A recommended)
⚠ The windings of medium-voltage (601 through 15,000 volts) generator sets must be dry before the generator is operated.
Tools: Megger or insulation resistance meter, Grounding cluster, High voltage gloves
⚠ Medium-voltage (601 to 15,000 volts) windings must be dry before the generator is operated.
Tools: Megger or Insulation Resistance Meter, Wheatstone bridge or digital ohmmeter, Grounding Cluster
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12 lead generator sets | Load wires are routed through the CTs | Reconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage). | ||
| 6 lead generator sets | Generator output leads are routed through the CTs | Non-reconnectable gensets (6 leads) have single secondary CTs (2 pins). | ||
| Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F) | Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100). | |||
| A (U) | CT21 | U load leads (A phase) | CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground. | |
| B (V) | CT22 | V load leads (B phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. | |
| C (W) | CT23 | W load leads (C phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Part # | Description | Category |
|---|---|---|
| AF25544 | Recommended air cleaner element - (heavy duty) primary element | air_filter |
| AF25545 | Recommended air cleaner element - (heavy duty) secondary element | air_filter |
| 0908-0101 | Lead Acid Battery | battery |
| 3375044 | Torque Wrench | belt |
| 19802521 | ECM Dataplate | ecm |
| 3331096 | Cummins, Part No. 3331096 | fuel_filter |
| 3376807 | Engine coolant and fuel filter wrench | fuel_filter |
| FS1007 | Fleetguard® Nelson®, Part No. FS1007 | fuel_filter |
| M-4376220 | Juego Junta Superior N. ° de Pieza | gasket |
| M-4376221 | Juego Junta Inferior N. ° de Pieza | gasket |
| 3375049 | Oil Filter Wrench | oil_filter |
| 3406810 | Combination Full-Flow/Bypass Lubricating Oil Filter Cummins Part No. 3406810 | oil_filter |
| 0908-0203 | operator_manual | |
| 0908-0204 | operator_manual | |
| 0908-0230 | Generator Set Operator Manual | operator_manual |
| 0908-0107 | Radiator Information | other_service |
| 0908-0110 | Health and Safety (Diesel Generator Sets) | other_service |
| 0908-0219 | Alarm Module (option) | other_service |
| 17200015 | Engine Shutdown | other_service |
| 17690172 | Engine Braking System | other_service |
| 17800006 | Engine Model | other_service |
| 3163156 | Service cable for InPower™ | other_service |
| 3666423 | other_service | |
| 3822735 | Plastic bead blasting media | other_service |
| 3886301 | InPower™ electronic service tool | other_service |
| 960-0174B | other_service | |
| A035H139 | Switch, Pushbutton | other_service |
| A040U808 | Harness, Control − Door (Includes Items 30 & 31) | other_service |
| A046Y204 | Shield, Wiring | other_service |
| M-3685996 | Intake Valve | other_service |
| M-5473065 | 150mm Kit de Motor M-5473066 | other_service |
| M-5473069 | 152mm Kit de Motor M-5473070 | other_service |
| M-5473074 | Kit de Motor M-5473075 | other_service |
| TB3-5 | Generator Set Control Panel Terminal Block | other_service |
| TB3-6 | Generator Set Control Panel Terminal Block | other_service |
| ol204vt | Torque Peak | other_service |
| M-5473087 | Piston Kit | piston_kit |
| M-5484414 | Piston Pin | piston_pin |
| M-3686661 | Valvula de escape - M-3686661 | valve |
Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.
The Cummins/Onan QSX15-G8 engine has an oil capacity of 83.3 liters.
The Cummins/Onan QSX15-G8 powers 2 generator set(s), including Cummins/Onan 352DFEH, Cummins/Onan DFE.
A commonly reported issue on generators using the Cummins/Onan QSX15-G8 is: Over Current.