Cummins/Onan — Manual System Operation (paralleling verification)
Operation · PowerCommand paralleling system
From a Cummins/Onan service manual — check it applies to your exact model before use.
Applies to: Cummins/Onan DGBB, Cummins/Onan DGBC, Cummins/Onan DGCA, Cummins/Onan DGCC, Cummins/Onan DGDA, Cummins/Onan DGDB, Cummins/Onan DGEA, Cummins/Onan DGFA, Cummins/Onan DGFC
Before you start
- Use extreme caution when performing phase relationship testing.
Procedure
- Place all generator set RUN/OFF/AUTO switches in OFF and master control switch in manual mode.
- Start one generator set in RUN and allow it to reach rated speed and voltage.
- Manually close the paralleling breaker using the breaker close pushbutton.
- Check phase relationship of the generator set output to its Bus PT module (voltage difference between L1 of Bus PT and generator PT/CT should be zero).
- Start a second set and verify voltage and frequency match the bus; observe the digital synchroscope.
- Check phase relationship across the open breaker on two phases simultaneously with a digital voltmeter when synchronized.
- Close the oncoming breaker and observe voltage, frequency, amp and kW metering on all sets.
- Apply load and verify proportional load sharing within plus or minus 5%.
- Remove load and return RUN/OFF/AUTO switches to AUTO.