Home›Controllers›PowerCommand PCC2100

PowerCommand PCC2100 Controller

The PowerCommand PCC2100 is a generator-set controller. It is used on generator sets from Cummins/Onan, including the DFGB, DFGE, DFLB and DFLC.

34
Generator sets
Cummins/Onan
Brand
35–1500 kW
Power range
3
Fuel types

Troubleshooting

60

Fault codes

CodeMeaningCauseRemedy
10Incorrect main fuel valve adjustment.Refer to Gaseous Fuel Adjustment (Type A or B) in Section 6.
101IDLE MODE — Warning; Engine continues to operate at reduced RPM.Indicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.When ground is removed from this input, the set returns to normal speed and voltage. When the engine idle function is enabled, the control automatically sets lower oil pressure warning and shutdown trip points to reflect the lower operating speed. When the engine idle function is removed and the set reverts to normal operating speed, the control automatically resets oil pressure warning and shutdown trip points to the normal settings.
102EMERGENCY STOP — Shutdown; Engine shuts down and will not crank.Indicates local or remote Emergency Stop.To reset the local Emergency Stop button: Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out; Move the Run/Off/Auto switch to Off; Press the Reset switch; Select Run or Auto, as required.
11Incorrect secondary regulator adjustment.Refer to Initial Secondary Regulator Adjustment in Section 6.
1122Rated/Idle Trans
1123A shutdown occurs immediately after moving the customer installed Battle Short switch to OFF with an active but overridden shutdown fault or a shutdown fault that was overridden at any time.
1123Shutdown After BS
1123Shutdown After BS — Shutdown
1123Shutdown After Battle ShortMoving the customer installed Battle Short switch to OFF with an active but overridden shutdown fault or a shutdown fault that was overridden at any time.
1123Shutdown After Battle Short — Battle Short is suspended and a shutdown occurs immediately if moving the customer installed Battle Short switch to OFF with an active but overridden shutdown fault or a shutdown fault that was overridden at any time.
1123Shutdown After Battle Short — ShutdownMoving the customer installed Battle Short switch to OFF with an active but overridden shutdown fault or a shutdown fault that was overridden at any time
1123Shutdown After Battle Short — displayed after the Battle Short feature is disabled following an overridden shutdown fault that occurred while in Battle Short mode
1124Delayed Shutdown
1124Delayed Shutdown — Warning
1131Battle Sh Active
1131Battle Sh Active — Warning
1131Battle Sh Active — Warning status indicator is lit.Battle Short mode is enabled.
1131Battle Sh Active — When Battle Short mode is enabled, the Warning status indicator is lit, along with displayed fault code 1131.
1131Battle Short ActiveBattle short function enabled
1131Battle Short Active — Warning status indicator lights and code 1131 is displayed
1131Battle Short mode is enabled.
121Speed Signal Lost
121Speed Signal Lost (Loss of Speed Sense) — Battle Short is suspended and a shutdown occurs immediately if this critical shutdown fault occurs
121Speed Signal Lost — Battle Short is suspended and a shutdown occurs immediately.
121Speed Signal Lost — Critical shutdown fault; Battle Short is suspended and a shutdown occurs immediately if this fault occurs.
121Speed Signal Lost — Shut downLoose or damaged magnetic pickup (MPU) wires/connector pins.Inspect the wires/connector pins, and repair or replace as necessary.
121Speed Signal Lost — Shutdown
1244Engine Normal Shutdown
1311Customer Input #1The nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Each of the fault functions can be programmed (using service tool), as follows: Enable/disable input (Default: enable); Status, Warning or Shutdown (Default: #1−None, #2 thru #4−Warning); Active closed or open (Default: closed [ground]); Change display name using up to 19 characters (Default: #1− Customer Fault 1, #2−Ground Fault, #3−Low Fuel, #4−Rupture Basin Fault).
1311Customer Input #1 - #3 — Status, warning or shutdownIf there is no actual fault, the problem may be an external wiring problem, active input (closed or open) selection is incorrectDisconnect the signal lead from TB1 and reset the control (CUST_IN1 − TB1-4, CUST_IN2 − TB1-5, CUST_IN3 − TB1-6); if the message drops out, the external wiring has a short or open circuit, or the active input selection (closed/open) is not correct for customer input (use the service tool to check the selection)
1311Customer Input #1 — The nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Each of the fault functions can be programmed (using service tool), as follows: enable/disable input (Default: enable); status, warning or shutdown (Default: #1−None, #2 thru #4−Warning); active closed or open (Default: closed [ground]); change display name using up to 19 characters (Default: #1− Customer Fault 1, #2−Ground Fault, #3−Low Fuel, #4−Rupture Basin Fault)
1311Customer Input #1 — Warning/Shutdown or none for status messageThe nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Each of the fault functions can be programmed (using service tool), as follows: Enable/disable input (Default: enable); Status, Warning or Shutdown (Default: #1−None); Active closed or open (Default: closed [ground]); Change display name using up to 19 characters (Default: #1− Customer Fault 1).
1312Customer Input #1 - #3 — Status, warning or shutdownIf there is no actual fault, the problem may be an external wiring problem, active input (closed or open) selection is incorrectDisconnect the signal lead from TB1 and reset the control (CUST_IN1 − TB1-4, CUST_IN2 − TB1-5, CUST_IN3 − TB1-6); if the message drops out, the external wiring has a short or open circuit, or the active input selection (closed/open) is not correct for customer input (use the service tool to check the selection)
1312Customer Input #2The nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Each of the fault functions can be programmed (using service tool), as follows: Enable/disable input (Default: enable); Status, Warning or Shutdown (Default: #1−None, #2 thru #4−Warning); Active closed or open (Default: closed [ground]); Change display name using up to 19 characters (Default: #1− Customer Fault 1, #2−Ground Fault, #3−Low Fuel, #4−Rupture Basin Fault).
1312Customer Input #2 — The nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Each of the fault functions can be programmed (using service tool), as follows: enable/disable input (Default: enable); status, warning or shutdown (Default: #1−None, #2 thru #4−Warning); active closed or open (Default: closed [ground]); change display name using up to 19 characters (Default: #1− Customer Fault 1, #2−Ground Fault, #3−Low Fuel, #4−Rupture Basin Fault)
1312Customer Input #2 — Warning/Shutdown or none for status messageThe nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Each of the fault functions can be programmed (using service tool), as follows: Enable/disable input (Default: enable); Status, Warning or Shutdown (Default: #2 thru #4−Warning); Active closed or open (Default: closed [ground]); Change display name using up to 19 characters (Default: #2−Ground Fault).
1313-1316Network Fault 1 through 4
1313-1316Network Fault 1 thru 4
1313-1316Network Fault 1 thru 4 — Shutdown/Warning/None
1317Customer Input #1 - #3 — Status, warning or shutdownIf there is no actual fault, the problem may be an external wiring problem, active input (closed or open) selection is incorrectDisconnect the signal lead from TB1 and reset the control (CUST_IN1 − TB1-4, CUST_IN2 − TB1-5, CUST_IN3 − TB1-6); if the message drops out, the external wiring has a short or open circuit, or the active input selection (closed/open) is not correct for customer input (use the service tool to check the selection)
1317Customer Input #3The nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Each of the fault functions can be programmed (using service tool), as follows: Enable/disable input (Default: enable); Status, Warning or Shutdown (Default: #1−None, #2 thru #4−Warning); Active closed or open (Default: closed [ground]); Change display name using up to 19 characters (Default: #1− Customer Fault 1, #2−Ground Fault, #3−Low Fuel, #4−Rupture Basin Fault).
1317Customer Input #3 — The nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Each of the fault functions can be programmed (using service tool), as follows: enable/disable input (Default: enable); status, warning or shutdown (Default: #1−None, #2 thru #4−Warning); active closed or open (Default: closed [ground]); change display name using up to 19 characters (Default: #1− Customer Fault 1, #2−Ground Fault, #3−Low Fuel, #4−Rupture Basin Fault)
1317Customer Input #3 — Warning/Shutdown or none for status messageThe nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Each of the fault functions can be programmed (using service tool), as follows: Enable/disable input (Default: enable); Status, Warning or Shutdown (Default: #2 thru #4−Warning); Active closed or open (Default: closed [ground]); Change display name using up to 19 characters (Default: #3−Low Fuel).
1318Customer Input #4The nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Each of the fault functions can be programmed (using service tool), as follows: Enable/disable input (Default: enable); Status, Warning or Shutdown (Default: #1−None, #2 thru #4−Warning); Active closed or open (Default: closed [ground]); Change display name using up to 19 characters (Default: #1− Customer Fault 1, #2−Ground Fault, #3−Low Fuel, #4−Rupture Basin Fault).
1318Customer Input #4 — The nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Each of the fault functions can be programmed (using service tool), as follows: enable/disable input (Default: enable); status, warning or shutdown (Default: #1−None, #2 thru #4−Warning); active closed or open (Default: closed [ground]); change display name using up to 19 characters (Default: #1− Customer Fault 1, #2−Ground Fault, #3−Low Fuel, #4−Rupture Basin Fault)
1318Customer Input #4 — Warning/Shutdown or none for status messageThe nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Each of the fault functions can be programmed (using service tool), as follows: Enable/disable input (Default: enable); Status, Warning or Shutdown (Default: #2 thru #4−Warning); Active closed or open (Default: closed [ground]); Change display name using up to 19 characters (Default: #4−Rupture Basin Fault).
1318Service Engine Fault — No action is taken by the PCC. A Service Engine message appears on the control display.Intermittent faultReset the control (this fault must be cleared manually); check for loose connections at the heated exhaust gas oxygen sensor and at the fuel trim valve (air fuel control)
1318Service Engine — WarningEmissions criteria might not be met due to one of the following: engine running in open loop; lean mixture; rich mixture; failed fuel system component
1334Crit Scaler OR
1334Crit Scaler OR — Shutdown
1334Crit Scaler Out Of Range
1334Crit Scaler Out Of Range — Shutdown
1335Non-Crit Scaler ORAn incorrect feature or calibration was entered into the control
1335Noncrit Scaler OR
1335Noncrit Scaler OR — Warning
1335Noncrit Scaler Out Of Range
1335Noncrit Scaler Out Of Range — Warning
1337No Message
135Oil Pressure Sensor H
135Oil Pressure Sensor H — Warning

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.