Specifications
| Fuel | diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 125 kW |
| Standby kVA | 156 |
| Prime power | 113 kW |
| Emissions | Tier 1 |
| Controller | PowerCommand, PowerCommand 2100, PowerCommand PCC 3100, PowerCommand PCC2100 |
| Oil capacity | 16.0 L |
| Alternator | Not specified |
| Voltage options | 12 V |
| Phase | 1 or 3 |
| Rated current | 434 A |
| Power factor | 1.0 |
| Circuit breaker | 434 A |
| Battery group | 4D |
| Battery cranking | 1080 (minimum) CCA |
| Battery voltage | 12 Volts DC V |
| Battery quantity | 1 |
| Coolant capacity | 31.5 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 2662×1016×1252 mm |
| Dry weight | 1141 kg |
| Sound level | 75.0 dBA @ 7 m |
| Fuel tank | 60.2 L |
| Tank runtime | 3.3 hr |
Filters for the Cummins/Onan 6BTA5.9
7Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Oil filter | P558615 | Lube Filter, Spin-On Full Flow | CUMMINS 10521, CUMMINS 3865405, NAPA 1607, NAPA 61607 | buy |
| Oil filter | P558616 | Lube Filter, Spin-On Full Flow | CUMMINS 3290712, CUMMINS 3890709, NAPA 1602, BALDWIN BT427 | KuduParts $11.00 FridayParts $13.20 |
| Fuel filter | P550440 | Fuel Filter, Spin-On Secondary | CUMMINS 3831063, CUMMINS 3890707, NAPA 3358, BALDWIN BF788 | FridayParts $356.80 |
| Fuel filter | P553004 | Fuel Filter, Spin-On | CUMMINS 3903640, CUMMINS 53C0045, NAPA 3358, RENAULT VI 0000150564 | FridayParts $18.20 |
| Fuel / water separator | P551329 | Fuel Filter, Water Separator Spin-On Twist&Drain | CUMMINS 11E170210, CUMMINS 3890063, NAPA 3357, BALDWIN BF1280 | FridayParts $151.00 |
| Fuel / water separator | P550248 | Fuel Filter, Water Separator Spin-On Twist&Drain | CUMMINS 1492827, CUMMINS 3286503, NAPA 3472, BALDWIN BF1226 | FridayParts $229.00 |
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Coolant filter | P554071 | Coolant Filter, Spin-On | CUMMINS 209604, CUMMINS 209606, NAPA 4071, WALGAHN-MOTORENTECHN 00811412 | FridayParts $397.60 |
Maintenance & consumables
for the Cummins/Onan 6BTA5.9| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Normal duty air filter. | — | |||
| Fuel filter | Oil and fuel filter fitted, water separator. | — | |||
| Oil filter | Oil and fuel filter fitted, water separator. | — | |||
| Battery | not stated | — | |||
| Belt | not stated | — | |||
| Coolant | Coolant capacity (only engine) | 9.9 l | — | ||
| Oil | Lubrication system oil capacity | 16.4 l | — | ||
| Spark plug | not stated | — |
Service intervals
29| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Coolant Heater | Check | 50 hr | Verify hot coolant is being discharged from the outlet hose. | |
| Coolant Level | Check | 8 hr | ||
| Coolant Level (Recovery Tank) | Check | 8 hr | Table 5-1 | |
| Exhaust Condensate Trap | Drain | 8 hr | Table 5-1 | |
| Fuel Level | Check | 8 hr | Table 5-1 | |
| Fuel Tanks (water and sediment) | Drain | 8 hr | Drain 1 cup or more of fuel to remove water and sediment. | |
| General Genset Inspection | Inspect | 8 hr | Table 5-1; also indicated for weekly/50 hours (X1, X2) | |
| Inspect Genset | Check | 8 hr | Check for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually with set running and repair any leaks immediately. | |
| Oil Level | Check | 8 hr | Table 5-1 | |
| Water and Sediment from Fuel Tank | Drain | 8 hr | Table 5-1; drain 1 cup or more of fuel to remove water and sediment | |
| Air Cleaner | Clean | 50 hr | Table 5-1; X3 perform more often in dusty conditions | |
| Battery Charging System | Check | 50 hr | Table 5-1 | |
| Charge Air Piping | Check | 50 hr | Table 5-1 | |
| Crankcase Oil | Drain | 50 hr | First service — Break-in: drain and replace the crankcase oil after the first 50 hours of operation on new generator sets. | |
| Starting Batteries | Check | 50 hr | Table 5-1 | |
| Battery Electrolyte Level | Check | 200 hr | Check at least every 200 hours of operation; disregard for maintenance-free battery | |
| Air Cleaner Element | Change | 500 hr | 6 mo | Table 5-1; replace yearly or sooner if service indicator button pops up |
| Anti-freeze and DCA Concentration | Check | 250 hr | 6 mo | Table 5-1 |
| Coolant Filter | Change | 500 hr | 6 mo | Table 5-1 |
| Cooling System | Clean | 500 hr | 6 mo | Table 5-1 |
| Crankcase Breather | Clean | 500 hr | 6 mo | Table 5-1 |
| Crankcase Oil and Filter | Change | 250 hr | 12 mo | Table 5-1 X6: if genset is used for standby applications, change oil every 12 months or 250 hours, whichever comes first |
| Drive Belt Tension | Check | 250 hr | 6 mo | Visually check belt for evidence of wear or slippage. Replace if hard or brittle. Refer to engine operation and maintenance manual. |
| Fuel Filter(s) | Drain | 250 hr | 6 mo | Table 5-1 |
| Fuel Filters | Change | 250 hr | 6 mo | Table 5-1 |
| Governor Adjustment | Check | 250 hr | 3 mo | |
| Radiator Hoses for Wear & Cracks | Check | 250 hr | 6 mo | Table 5-1 |
| Valve Lash | Adjust | 1000 hr | Table 5-1: after 1000 hours; contact an authorized service center for service | |
| Generator Set Exercise | Test | 1 mo | Exercise the generator set at least once a month for a minimum of 30 minutes, under not less than 30 percent of the nameplate rating |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
60| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Clearance around generator set for maintenance and service access | 1 | meter (3 feet) | |
| Clearance | Exhaust pipe clearance from combustible wall or partition | 12 | inches (305 mm) | minimum |
| Clearance | Float switch lift below C-clip stop | 1/8 | inch (3 mm) | |
| Clearance | Fuel line clearance from electrical wiring | 1/2 | inch (12.7 mm) | minimum |
| Clearance | Fuel line clearance from hot exhaust parts | 2 | inch (51 mm) | minimum |
| Clearance | Vibration isolator base elevation (max difference between isolator bases) | 0.25 | inch (6 mm) | |
| Clearance | Vibration isolator top plate to base clearance | 0.25 | inch (6 mm) | nominal, minimum |
| Other | Battery electrolyte corrected specific gravity (fully charged) | 1.260 | electrolyte temperature corrected | |
| Other | Battery electrolyte specific gravity (fully charged) | 1.260 | specific gravity | corrected to 80 F (27 C) |
| Other | Battery electrolyte specific gravity charge threshold | 1.215 | specific gravity | charge battery if reading is below this value |
| Other | Battery recharge threshold specific gravity | 1.215 | ||
| Other | Battery specific gravity temperature correction | four gravity points (0.004) for every ten degrees above 80 F (27 C) | ||
| Other | Cool-down at idle | 0−30 | min | |
| Other | Customer output relay contacts rating (TB1 outputs 1-4) | 2 | amps at 30 VDC | normally open contacts |
| Other | Cycle crank crank and rest time | 7 to 20 | seconds | |
| Other | Cycle crank number of cycles | 3, 4, or 5 | ||
| Other | Default start cycles | 3 | cycles | 15 seconds of cranking and 15 seconds of rest |
| Other | Frequency Adjust range | 5 | percent of nominal frequency | e.g. 60.0 Hz adjustable 57.0 to 63.0 Hz |
| Other | Frequency adjustment range | ±5% | % | genset running |
| Other | Fuse A31-F1 (control B+) | 5 | Amp | Engine Interface board |
| Other | Fuse A31-F3 (auxiliary B+) | 5 | Amp | Engine Interface board; panel lights, run and start relays |
| Other | Fuse A38-F1 (Network B+) | 10 | Amp | Governor Output Module |
| Other | Fuse A38-F2 (Switched B+) | 10 | Amp | Governor Output Module |
| Other | Fuse A38-F3 (Governor B+) | 10 | Amp | Governor Output Module |
| Other | Fuse TB-Bat F1 (Customer B+) | 20 | Amp | Engine Harness Assembly |
| Other | GOV RAMP adjustment range | 0 through 10 | seconds | |
| Other | Low oil pressure / high engine temperature fault time delay | about 10 | seconds | following starter disconnect and inhibited during cranking |
| Other | Mounting bolts used to secure vibration isolators to base | 5/8 inch or 16 mm | anchored mounting bolts | |
| Other | Optional control relay (K11, K12, K13) contacts rating | 10 | amps at 600 VAC | |
| Other | Overcrank limit (Sentinel) | 60 | seconds | |
| Other | Overcrank option limit (Detector) | 75 | seconds | |
| Other | REG VHZ adjustment range | 1 through 50 (normal range 7 through 21) | ||
| Other | Rated To Idle delay | 0−10 | sec | Beginning Version 2.303; default = 0 |
| Other | Setup/calibration menu access code | 574 | ||
| Other | Specific gravity correction factor | 0.004 | gravity points | per 10 degrees electrolyte temperature above 80 F (27 C) |
| Other | Standard cycle cranking (Detector) | three 15-second cranking cycles with two 15-second rest periods | ||
| Other | Start delay adjustment range | 0 to 300 | seconds | remote starting in Auto mode |
| Other | Stop delay adjustment range | 0 to 600 | seconds | remote stopping in Auto mode |
| Other | Time Delay To Start | 0−300 | sec | default = 0 |
| Other | Time Delay To Stop (Stop Delay) | 0−600 | sec | default = 0 |
| Other | Voltage adjustment range | ±5% | % | genset running |
| Other | Warm-up at idle time delay | 0−300 | sec | manual mode |
| Pressure | Engine Oil Pressure (Normal) | 276-483 | kPa | normal operating |
| Pressure | Engine Oil Pressure (Normal) | 40-70 | psi | normal operating |
| Pressure | Engine oil pressure (normal) | 30 to 65 | psi (207 to 449 kPa) | at normal operating temperature |
| Pressure | Engine oil pressure range (low oil pressure troubleshooting) | 25 to 65 | psi (172 to 449 kPa) | |
| Pressure | Fuel shutoff valve rating (TB1-8 and TB1-5) | not more than 0.5 | amps | 120 or 240 VAC |
| Pressure | Idle Oil Pressure | 10-30 | psi | idle |
| Pressure | Idle Oil Pressure | 69-207 | kPa | idle |
| Pressure | Idle Oil Pressure Shutdown Limit | 55 | kPa | idle |
| Pressure | Idle Oil Pressure Shutdown Limit | 8 | psi | idle |
| Pressure | Idle Oil Pressure Warning Limit | 12 | psi | idle |
| Pressure | Idle Oil Pressure Warning Limit | 83 | kPa | idle |
| Pressure | Idle oil pressure | 10 - 30 | psi (69 - 207 kPa) | idle |
| Pressure | Idle oil pressure (normal) | 10-30 | psi (69-207 kPa) | Engine model 6C, idle |
| Pressure | Low oil pressure shutdown limit | 14 | psi (97 kPa) | |
| Pressure | Maximum allowable exhaust back pressure | 41 | in. H2O | |
| Pressure | Maximum fuel inlet restriction | 4 | in. Hg. (13.5 kPa) | |
| Pressure | Maximum fuel return restriction | 20 | in. Hg. (67.6 kPa) | |
| Pressure | Maximum radiator cleaning air/water pressure | 242 | kPa | cleaning radiator fins |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | Refer to the Cummins engine Operation and Maintenance Manual for coolant recommendations/specifications | 25.0 L | Capacity with standard radiator 6.5 Gal (25 L) DGDA/DGDB; 8.3 Gal (31.5 L) DGDK; heavy duty diesel engines require a balanced coolant mixture of water, antifreeze and coolant additives | ||
| Coolant | 50/50 mix of water and antifreeze | Balanced coolant mixture of water, antifreeze and coolant additives | Drain and replace the mixture every 6 months or after 500 hours of operation. Do not add cold coolant to a hot engine; allow engine to cool below 120 F (50 C) before adding coolant. | ||
| Engine oil | Refer to Cummins engine Operation and Maintenance Manual for lubricating oil recommendations/specifications | 16.0 L | Oil capacity with filters 17 Qts (16 L); gensets are shipped with oil added | ||
| Fuel | ASTM No. 2 diesel fuel | Cummins engines normally use ASTM No. 2 diesel fuel; will operate on alternate diesel fuels within specifications in Cummins engine Operation and Maintenance Manual. | |||
| Fuel | diesel | Do not use zinc coated or copper fuel lines with diesel fuel. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
80| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 101 | IDLE MODE | Indicates that the engine is operating in idle mode; generator build-up is inhibited and engine governed at 800 RPM. | Warning | Remove ground from the engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Pull the button out; move the Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Can only be reset at the PCC front panel. |
| 1122 | Rated/Idle Trans | Rated/Idle transition | Info | |
| 1123 | Shutdown After Battle Short | Shutdown after Battle Short | Shutdown | Review Fault History and perform corrective action. |
| 1124 | Delayed Shutdown | Delayed shutdown | Warning | Review Fault History and perform corrective action. |
| 1131 | Battle Sh Active | Control is in Battle Short mode (bypasses several critical fault shutdowns). | Warning | When Battle Short mode is enabled, the Warning status indicator is lit along with displayed fault code 1131. Refer to Battle Short Mode description in Section 3. |
| 121 | Speed Signal Lost | Speed signal lost | Shutdown | Restart and check RPM on digital display; inspect MPU wires/connector pins; check for 3.5 to 15 VAC at MPU while cranking. |
| 1311 | Customer Input #1 | Customer input #1 (optional customer selection) | Programmable (service tool): enable/disable input (default enable); status, warning or shutdown (default #1 = None); active closed or open (default closed [ground]); change display name up to 19 characters. | |
| 1311, 1312, 1317, 1318 | CUSTOMER INPUT #1 - #4 | Optional customer-selected fault input is active. | Disconnect signal lead from TB1 and reset the control; check external wiring/active input selection. | |
| 1312 | Customer Input #2 | Customer input #2 (optional customer selection) | Programmable (service tool): enable/disable input (default enable); status, warning or shutdown (default #2 = Warning); active closed or open (default closed [ground]); change display name. | |
| 1313−1316 | Network Fault 1 thru 4 | Network fault 1 through 4 | ||
| 1317 | Customer Input #3 | Customer input #3 (optional customer selection) | Programmable (service tool): enable/disable input; status, warning or shutdown; active closed or open; change display name. | |
| 1318 | Customer Input #4 | Customer input #4 (optional customer selection) | Programmable (service tool): enable/disable input; status, warning or shutdown; active closed or open; change display name. | |
| 1334 | Crit Scaler Out Of Range | Incorrect feature or calibration was entered into control. | Shutdown | Reload correct feature/calibration file. |
| 1335 | Noncrit Scaler Out Of Range | Non-critical scaler out of range | Warning | Reload correct feature/calibration file. |
| 1337 | No Message | No message | Info | |
| 135 | Oil Pressure Sensor H | Oil pressure sensor high | Warning | Check sender/connectors/wires; verify fault simulation not enabled; check 0.5 to 4.5 VDC at P7-13 (OP OUT) and P7-17 (OP COM). |
| 141 | Oil Pressure Sensor L | Oil pressure sensor low | Warning | Check sender/connectors/wires; check for shorts/open circuits at P7-13, 17, 21. |
| 1416 | Fail To Shutdown | Genset continues to run after receiving shutdown command (Battle Short feature enabled). | Warning | Refer to Battle Short Mode description in Section 3. |
| 1417 | Powr Down Error | The controller cannot power down because of some unknown condition; possible drain on battery | Warning | Contact an authorized service center for service. |
| 143 | Pre-Low Oil Pres | Engine oil pressure has dropped below the warning trip point | Warning | If generator is powering critical loads and cannot be shut down, wait until the next shutdown period and then follow code 415 procedure. |
| 1433 | Emergency Stop | Local Emergency Stop. | Shutdown | Pull the button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto. |
| 1434 | Remote E-Stop | Remote Emergency Stop. | Shutdown | See code 1433 to reset. |
| 1435 | Low Coolant Temp | Initiates a warning when the engine jacket water coolant temperature falls below 70 deg F (21 deg C); provided to meet NFPA 110 requirements, in conjunction with illumination of the Warning LED. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater connection to power supply: check for blown fuse or disconnected heater cord and correct. Check for low coolant level and replenish if required; look for possible coolant leaks and repair. |
| 1438 | Fail To Crank | Possible fault with control, speed sensing or starting system | Shutdown | Test for B+ at the starter; check fuse F3 (2 Amps); check K4 start pilot relay and starter circuitry; refer to code 121. |
| 144 | Coolant Sensor High | Engine coolant temperature signal is shorted high. | Warning | Check sender/connectors/wires; check resistance between P7-30 (IH20) and P7-34 (IH20 COM). |
| 1442 | Weak Battery | During cranking, battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time | Warning | See code 441 for corrective action. |
| 1443 | Battery Failed | Dead battery − engine will not start | Shutdown | See code 441 for corrective action. |
| 1444 | KW Overload | kW overload | Warning | Check load and load lead connections; check CTs and CT connections. |
| 1445 | Short Circuit | Short circuit | Shutdown | Check load and load lead connections (fault may not reset for several minutes). |
| 1446 | High AC Voltage | Phase voltage exceeded 130% of nominal, or 110% of nominal for 10 seconds. | Shutdown | Check fault simulation; clear fault and restart; refer to Generator/Base Board Isolation Procedure. |
| 1447 | Low AC Voltage | Phase voltage dropped below 85% of nominal for 10 seconds. | Shutdown | Check load; reconnect per reconnection diagram; check PMG/field wiring; check P8-21/P8-22 shunt connections. |
| 1448 | Under Frequency | Under frequency | Shutdown | Check fuel supply, intake air supply and load; check P8 connections. |
| 1449 | Over Frequency | Over frequency | Warning | Check fuel or air delivery problem; repair P7/P8 connections. |
| 145 | Coolant Sensor Low | Engine coolant temperature signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts at P7-30 and P7-34. |
| 1452 | Gen CB Not Close | Genset circuit breaker (S2) failed to close when PTC enabled. | Warning | Refer to Section 5. |
| 1453 | Gen CB Not Open | Genset circuit breaker (S2) failed to open when PTC enabled. | Warning | Refer to Section 5. |
| 1459 | Reverse Power | Reverse power | Shutdown | Check wiring to voltage sense circuit; refer to CT Installation in Section 6. |
| 146 | Pre-High Coolant Temp | Engine is operating near cooling system capacity | Warning | Reduce load; check air inlets/outlets and remove obstructions to airflow; if engine can be stopped follow code 151. |
| 1461 | Loss Of Field | Loss of field (electric) due to reverse kVAR. | Shutdown | Check field circuit. |
| 1466 | Modem Failure | Modem failure | Warning | Check for open, short circuit to ground, and loose connections to the modem. |
| 1468 | Network Error | Network error | Warning | Refer to the LonWorks Network publications. |
| 1469 | Speed/Hz Match | Speed/Hz match | Shutdown | Check calibration file. |
| 1471 | Over Current | Over current | Warning | Check load and load lead connections. |
| 1472 | Over Current | Over current | Shutdown | Check load and load lead connections (fault may not reset for several minutes). |
| 151 | High Coolant Temp | Engine has overheated (coolant temperature has risen above the shutdown trip point) | Shutdown | Allow engine to cool; check coolant level; check airflow obstructions; check fan belt; check blower fan/remote radiator pumps; reset control and restart. |
| 197 | Low Coolant Level | Engine coolant level has fallen below the warning trip point. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If powering critical loads, wait until next shutdown period and follow 201-SHUTDOWN procedure; check oil pressure via menu prior to clearing fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset control and restart. Oil pressure limits in Table 4-3. |
| 204 | OIL PRESS SENDER | The control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70°F (21°C) or lower, indicating the engine coolant heater is not operating or is not circulating coolant. | Warning | Check coolant heater power supply, fuse or disconnected heater cord; check for low coolant level and replenish; check for an open heater element by checking current draw of heater. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215°F (102°C) standby or 207°F (97°C) prime. | Warning | Reduce load if possible; check air inlets/outlets; follow 212-SHUTDOWN procedure if engine can be stopped. |
| 212 | Oil Temp Sensor H | Oil temperature sensor high | Warning | Check sender/connectors/wires; check resistance between P7-22 (OIL TEMP) and P7-26 (OIL TEMP COM). |
| 213 | Oil Temp Sensor L | Resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender; should be 500 to 2k ohms. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Check coolant level in radiator and coolant recovery bottle; look for leakage; reset control and restart. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. LOW COOLANT LVL Shutdown will not occur if genset is in Idle mode (low coolant warning only). | Shutdown | Check coolant level in radiator and bottle; check coolant bottle hose or radiator cap; reset control and restart. |
| 220 | MAG PICKUP | Mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM on the digital display; inspect/adjust MPU. |
| 221 | FAIL TO CRANK | Possible fault with control or starting system; engine will not crank. | Shutdown | Check fuse F3 on the Engine Interface board; check for poor battery cable connections; recharge or replace a discharged or defective battery. |
| 222 | OVERCRANK | Possible fuel system problem; engine stops cranking. | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines; check/replace dirty fuel filter and air filter; reset and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed (115% ±1% of nominal). | Shutdown | Inspect the mechanical fuel linkage and repair or replace; check the EFC for binding or damage; monitor the PCC duty cycle display and replace A32 or A38 as indicated. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace battery; clean/tighten connections; check engine DC alternator; check battery charger float level. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Check voltage float level on battery charger if applicable (lower float level); check engine DC alternator and replace if normal battery charging voltage is not obtained. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | Recharge or replace the battery; see 230 LOW DC VOLTAGE. |
| 2323−2326 | Network Fault 5 thru 8 | Network fault 5 through 8 | ||
| 2327 | PTC Fault | PTC module or communication link not working properly when PTC enabled. | Warning | Check blinking light on PTC module; check B+ TB3-3 to TB3-4; check PTC status voltage TB3-5 to TB3-6 (~0.2 VDC); repower control. |
| 2329 | Low S1 Frequency | Low utility (S1) frequency. | Warning | Check S1 AC inputs and wiring to PTC at TB5; check sensor set points. |
| 2331 | Low S1 Voltage | Low utility (S1) voltage. | Warning | Repower PCC 2100 control to clear; check S1 AC inputs at TB5; check S1 pickup/dropout set points. |
| 2335 | Excitation Fault | Loss of all three voltage sense leads or failure in excitation circuit. | Shutdown | Critical shutdown fault; suspends Battle Short and shuts down immediately. |
| 2336 | Memory Error | Memory error | Shutdown | Try reloading calibration file. |
| 2337 | Pwr Tran Disabled | Power transfer disabled | Warning | Use InPower to enable PTC feature; cycle power off for 5 seconds then repower. |
| 2338 | Pwr Tran Failure | Power transfer failure | Warning | Check blinking light and B+ TB3-3 to TB3-4; check connections between TB2 and TB3; cycle power. |
| 2339 | Pwr Down Enabled | Power down enabled | Warning | None required. |
| 234 | Overspeed | Overspeed shutdown | Shutdown | Critical shutdown fault; suspends Battle Short and shuts down immediately. |
| 2341 | High Control Temp | High control temperature | Warning | Check genset room air flow. |
| 2342 | Too Long In Idle | Genset has been in Idle mode too long. | Warning | Exit idle mode. |
| 235 | Low Coolant Level | Engine coolant level has fallen below the shutdown trip point. | Shutdown | Check coolant level and replenish; look for leaks; reset control and restart. |
| 2358 | High S1 Voltage | Utility (S1) voltage increased above over voltage threshold. | Warning | Measure S1 AC inputs at PTC module; check utility nominal voltage; check sensor set points. |
| 2396 | S1 CB Not Close | Utility contact (S1) failed to close with PTC enabled. | Warning | Refer to Section 5. |
| 2397 | S1 CB Not Open | Utility contact (S1) failed to open with PTC enabled. | Warning | Refer to Section 5. |
| 240 | LOW FUEL-DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Adjusting Default Settings (Controller Configuration Menu) adjustment
- Make sure Main Menu 1 is displayed and simultaneously press the Home Menu and Previous Main Menu buttons.
- Press the buttons next to the and symbols to navigate between the three submenus.
- Press the button next to the symbol until the + and − symbols are displayed.
- Press the button next to the + or − symbol to select the desired option.
- Press the symbol to save the changes.
Adjusting Values/Parameters (Adjust Menu) adjustment
⚠ If the Home button or Previous Main Menu button is pressed before pressing the save symbol, the changes are not saved.
⚠ Long periods of engine idling can eventually affect engine performance and may void engine warranty.
- Press the button next to the symbol in the display until the + and − symbols are displayed.
- If necessary, press the button next to the or symbols to move to the numeric character you wish to change.
- Press the button next to the + symbol to increase the value; press the button next to the − symbol to decrease the value.
- After adjusting, press the symbol to save; make sure the cursor is on the last numeric character before pressing.
Adjusting Values/Parameters (PowerCommand 2100 Control) adjustment
- Press the button next to the down arrow symbol until the + and - symbols are displayed.
- Press the button next to the arrow symbols to move to the numeric character to be changed.
- Press the button next to + to increase the value or select a parameter; press - to decrease.
- Press the save symbol to save the changes (make sure the cursor is on the last numeric character).
- If the Home button or Previous Main Menu button is pressed before the save symbol, the changes are not saved.
Controller Configuration (PowerCommand 2100 Control) adjustment
- Make sure Main Menu 1 is displayed.
- Simultaneously press the Home Menu and Previous Main Menu buttons to view the first Controller Configuration menu.
- Press the buttons next to the up and down symbols to navigate between menus.
- Press the button next to the + or - symbol to select the desired option.
- Press the save symbol to save changes; pressing Home or Previous Main Menu before the save symbol leaves changes unsaved.
Day Tank Controller Conversion 240 VAC to 120 VAC adjustment
- Remove the two jumpers between terminals TB1-6 and TB1-7 and connect one between TB1-5 and TB1-6 and the other between TB1-7 and TB1-8.
- Move selector switch S103 on the control PCB to the up position for 120V.
- On the control transformer, remove the two jumpers between terminals H2 and H3 and connect one between H1 and H3 and the other between H2 and H4.
Torque Tester / Current Transformer Installation Check adjustment
- Verify the dot on the CT faces toward the generator.
- Verify CT21 is on U load leads, CT22 on V load leads, CT23 on W load leads.
- Verify the correct CT secondary terminal (pin 2 high voltage / pin 3 low voltage) is used.
- Check CT/PT wiring if a 335 Reverse Power shutdown occurs.
Generator/Base Board Isolation Procedure diagnostic
⚠ This test involves unregulated excitation; disconnect all loads.
⚠ HAZARDOUS VOLTAGE.
Tools: Voltmeter, 12 volt battery, Jumpers
- Throw line circuit breaker OFF and shut down the set.
- Remove control housing side cover; disconnect exciter stator X and XX leads from AC harness.
- Prepare to measure output voltage across generator terminals while set runs.
- Connect a 12V battery jumper positive (+) to X lead (Field +).
- Check polarity again; polarity must be correct.
- Start the set and connect battery negative (-) jumper to XX lead.
- If rated output voltage or higher and all phases balanced, generator is likely OK.
- If unbalanced troubleshoot main stator; if uniformly low troubleshoot exciter and field circuits.
Servicing the PMG - Testing diagnostic
⚠ HAZARDOUS VOLTAGE. Touching uninsulated high voltage parts inside the control and power output boxes can result in severe personal injury or death.
Tools: Wheatstone bridge or digital ohmmeter
- Disconnect leads P2, P3 and P4 from the voltage regulator.
- Start the engine at the set and let the speed stabilize.
- Measure voltage across lead pairs P2-P3, P3-P4 and P4-P2 (at least 150 VAC for 50 Hz, at least 180 VAC for 60 Hz).
- If voltages are low or uneven, check all leads and connections before disassembling the PMG.
- Stop the set and measure electrical resistance across P2-P3, P3-P4 and P4-P2 (approximately 4.4 ohms each winding).
Testing the Float Switch Assembly diagnostic
Tools: Ohmmeter, Feeler gauge
- Remove fuel pump control cover, disconnect wiring jack, unscrew assembly from top of day tank.
- Holding assembly vertical, test continuity between each pair of colored leads; all readings zero.
- Lift each float to 1/8 inch (3 mm) below the C-clip stop and test continuity; all readings infinity.
- Use pipe thread sealant when replacing the assembly.
Testing the Generator Stator and Rotor Windings diagnostic
⚠ Disconnect the starting battery cables (negative [-] first) to make sure the engine will not start while performing these tests.
Tools: Wheatstone bridge or digital ohmmeter (0.001 ohm precision), Megger or insulation resistance meter
- Disconnect battery cables (negative first) so the engine will not start.
- Measure winding resistance with a Wheatstone bridge or digital ohmmeter and compare to Table 6-1.
- Measure winding insulation resistance between leads and laminations; replace if less than 1 megohm.
- For the main stator, measure across each pair of stator leads (U1-U2, U5-U6, V1-V2, V5-V6, W1-W2, W5-W6).
Testing the PMG diagnostic
⚠ HAZARDOUS VOLTAGE.
Tools: Voltmeter, Wheatstone bridge or digital ohmmeter
- Disconnect PMG leads PMG 2, 3 and 4 from AC harness connectors.
- Start engine and let speed stabilize.
- Measure voltage across PMG 2&3, PMG 3&4 and PMG 4&2.
- Voltage should be at least 150 VAC (50 Hz) or 180 VAC (60 Hz) and equal.
- Stop set and measure resistance across each pair; each winding approximately 4.4 ohms.
Testing the Rotating Rectifier Assembly Diodes diagnostic
⚠ Layers of dust can cause diodes to overheat and fail. Brush dust off regularly.
Tools: Ohmmeter
- Disconnect the diode pigtails from the terminal posts.
- Measure electrical resistance between each diode pigtail and the plate on which the diode is mounted.
- Reverse the meter test probes and repeat the tests.
- Replace the diode if resistance is high or low in both directions.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| CT1 - U load leads (A phase); CT2 - V load leads (B phase); CT3 - W load leads (C phase) | 6 lead gensets: generator output leads routed through CTs; 12 lead gensets: load wires routed through CTs | 12-lead sets have dual secondary CTs (3 pins); 6-lead sets have single secondary CTs (2 pins) | ||
| 110V - 120V L-N | Single phase, 2-wire | Jumper locations for single phase, 2-wire | PTC Module AC wiring (0300-5382-01, -02) | |
| 190, 200, 208, 220, 230, 240, 380, 416, 440, 460, 600 (L-L) | 3 (three phase) | 3 or 4 wires | Voltage Configuration submenu; default = 3Ph 208V 4W | |
| 190V - 240V L-L | Three phase | Jumper locations for three phase, 190V-240V L-L | Use 0300-5382-01 for 190V-240V L-L, 50/60 Hz | |
| 200, 220, 230, 240 (L-L) | 1 (single phase) | 3 wires | Voltage Configuration submenu (Governor/Regulator Setup) | |
| 200V - 240V L-L | Single phase, 3-wire | Jumper locations for single phase, 3-wire | PTC Module AC wiring | |
| 380V - 600V L-L | Three phase | Jumper locations for three phase, 380V-600V L-L | Use 0300-5382-02 for 380V-600V L-L, 50/60 Hz |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the Cummins/Onan DGDK?
The Cummins/Onan DGDK is rated 125 kW standby (156.0 kVA).
What engine is in the Cummins/Onan DGDK?
The Cummins/Onan DGDK is powered by the Cummins/Onan 6BTA5.9 engine.
What fuel does the Cummins/Onan DGDK use?
The Cummins/Onan DGDK runs on diesel.
What's the oil capacity on a Cummins/Onan DGDK?
The Cummins/Onan 6BTA5.9 engine in the Cummins/Onan DGDK has an oil capacity of 16.0 liters.
How much coolant does the Cummins/Onan DGDK hold?
The Cummins/Onan DGDK cooling system holds 31.5 liters (8.3 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Cummins/Onan DGDK?
The Cummins/Onan DGDK is rated 113 kW prime (141 kVA), against 125 kW standby.
How loud is the Cummins/Onan DGDK?
The Cummins/Onan DGDK is rated at 75.0 dBA at 7 m, per the manufacturer specification sheet.
How much does the Cummins/Onan DGDK weigh?
The Cummins/Onan DGDK has a dry weight of 1141 kg (2515 lb).
What size fuel tank does the Cummins/Onan DGDK have?
The Cummins/Onan DGDK has a 60.2 liter (16 US gallon) fuel tank, giving about 3.3 hours of runtime.
What voltages is the Cummins/Onan DGDK available in?
The Cummins/Onan DGDK is offered in 12 V, 1 or 3-phase.
What size battery does the Cummins/Onan DGDK need?
The Cummins/Onan DGDK uses 1 battery, 12 Volts DC V each, 1080 (minimum) CCA, group 4D, per the manufacturer specification sheet.
What alternator does the Cummins/Onan DGDK use?
The Cummins/Onan DGDK uses a Not specified alternator.
Troubleshooting
6Fault codes
| Code | Meaning |
|---|---|
| 234 | Overspeed |
| 1433 | Emergency Stop |
| 1434 | Remote Emergency Stop |
| 121 | Speed Signal Lost |
| 2335 | Excitation Fault |
| 1123 | Shutdown After Battle Short |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan DGDK troubleshooting guide (54 entries) →
Repair guides
26- Adjusting Default Settings (Controller Configuration Menu)
- Adjusting Values/Parameters (Adjust Menu)
- Adjusting Values/Parameters (PowerCommand 2100 Control)
- Changing the Air Cleaner Element (Type A Filter Assembly)
- Changing the Air Cleaner Element (Type B Filter Assembly)
- Controller Configuration (PowerCommand 2100 Control)
- Convert Day Tank Fuel Pump Control from 120 VAC to 240 VAC
- Convert Day Tank Fuel Pump Control from 240 VAC to 120 VAC
- Current Transformer (CT) Installation
- Day Tank Controller Conversion 240 VAC to 120 VAC
- Disassembling the PMG
- Fuel Transfer Pump Motor Connections
- Fuel Transfer Pump Motor Connections
- Generator Disassembly
- Generator Reassembly
- Magnetic Speed Pickup Unit (MPU) Installation
- Preventing Accidental Starting (Battery Disconnected)
- Replacing the Air Cleaner Element (Type A Filter Assembly)
- Replacing the Air Cleaner Element (Type B Filter Assembly)
- Servicing the PMG - Testing
Step-by-step procedures compiled from the Cummins/Onan service manual for this model.
Parts
3| Part # | Description | Qty | System | |
|---|---|---|---|---|
| S103 | Selector switch | Switch | Amazon eBay | |
| TB1-6 | Control box terminal (TB1-6) | * | Service part / kit | Amazon eBay NAPA $316.58 |
| TB1-7 | B+ OUTPUT | Service part / kit | Amazon eBay NAPA $13.85 |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 6.8 | 26.0 | |
| Prime | 3% | 5.2 | 20.0 |
| Prime | 25% | 11.0 | 3.0 |
| Prime | 50% | 19.0 | 5.0 |
| Prime | 75% | 25.0 | 6.7 |
| Prime | 100% | 33.0 | 8.6 |
| Standby | 7.6 | 29.0 | |
| Standby | 3% | 5.8 | 22.0 |
| Standby | 25% | 12.0 | 3.3 |
| Standby | 50% | 21.0 | 5.5 |
| Standby | 75% | 28.0 | 7.5 |
| Standby | 100% | 23.1 | 6.1 |