Home›Repair guides›Cummins/Onan›Servicing the PMG - Testing

Cummins/Onan PCC 3100 — Servicing the PMG - Testing

Testing & diagnosis · PMG (permanent magnet exciter)

For the Cummins/Onan PCC 3100, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DGBB, Cummins/Onan DGBC, Cummins/Onan DGCA, Cummins/Onan DGCB, Cummins/Onan DGCC, Cummins/Onan DGDA, Cummins/Onan DGDB, Cummins/Onan DGDK, Cummins/Onan DGEA, Cummins/Onan DGFA, Cummins/Onan DGFC, Cummins/Onan PCC 3100

Before you start

  • HAZARDOUS VOLTAGE. Touching uninsulated high voltage parts inside the control and power output boxes can result in severe personal injury or death.

Procedure

  1. Disconnect leads P2, P3 and P4 from the voltage regulator.
  2. Start the engine at the set and let the speed stabilize.
  3. Measure voltage across lead pairs P2-P3, P3-P4 and P4-P2.
  4. Voltage should be at least 150 VAC for 50 Hz sets and at least 180 VAC for 60 Hz sets.
  5. Stop the set and measure electrical resistance across lead pairs P2-P3, P3-P4 and P4-P2 with a Wheatstone bridge or digital ohmmeter.
  6. Each winding should have a resistance of approximately 4.4 ohms.

Tools required

  • Wheatstone bridge or digital ohmmeter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • PMG voltage at least 150 VAC (50 Hz) / at least 180 VAC (60 Hz)
  • PMG winding resistance approximately 4.4 ohms

Full service-parts list: Cummins/Onan DGBB →, Cummins/Onan DGBC →, Cummins/Onan DGCA →, Cummins/Onan DGCB →, Cummins/Onan DGCC →, Cummins/Onan DGDA →, Cummins/Onan DGDB →, Cummins/Onan DGEA →, Cummins/Onan DGFA →, Cummins/Onan DGFC →, Cummins/Onan PCC 3100 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.