Before you start
- Diesel fuel is highly combustible. Improper installation of this kit can lead to spillage of large quantities of fuel and loss of life and property if the fuel is accidentally ignited.
Procedure
- Remove the jumpers between terminals TB1-5 and TB1-6, and TB1-7 and TB1-8 in the control box.
- Connect the two jumpers between terminals TB1-6 and TB1-7.
- Move selector switch S103 on the control PCB to the down position for 240 VAC.
- If the control is equipped with a transformer, remove the jumpers between terminals H1 and H3, and H2 and H4, and connect the two jumpers between H2 and H3.
- Attach a tag to the control box indicating the supply voltage.
Specs & values
- Terminals TB1-8 Amazon eBay FridayParts $87.88 and TB1-5 Amazon eBay NAPA $30.91 FridayParts $20.80 available for connection of a 120 or 240 VAC electric fuel shutoff valve rated not more than 0.5 amps
Full service-parts list: Cummins/Onan DGDA →, Cummins/Onan DGDB →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.