Cummins/Onan — Adjusting Values/Parameters (PowerCommand 2100 Control)
Adjustments · PCC2100 controller
From a Cummins/Onan service manual — check it applies to your exact model before use.
Applies to: Cummins/Onan DGDA, Cummins/Onan DGDB, Cummins/Onan DGDK, Cummins/Onan 6BT5.9 engine, Cummins/Onan 6BTA5.9 engine
Procedure
- Press the button next to the down arrow symbol until the + and - symbols are displayed.
- Press the button next to the arrow symbols to move to the numeric character to be changed.
- Press the button next to + to increase the value or select a parameter; press - to decrease.
- Press the save symbol to save the changes (make sure the cursor is on the last numeric character).
- If the Home button or Previous Main Menu button is pressed before the save symbol, the changes are not saved.
Specs & values
- Voltage Adjust: within plus or minus 5 percent of nominal (e.g., 208 V: 197 to 218 V)
- Frequency Adjust: within plus or minus 5 percent of nominal (e.g., 60.0 Hz: 57.0 to 63.0 Hz)
- Start Delay: 0 to 300 seconds (default = 0)
- Stop Delay: 0 to 600 seconds (default = 0)
- Rated To Idle delay: 0 to 10 seconds (default = 0; enter 1 or more to enable)
- Idle Start: Enable or Disable (default = Disable)
Full service-parts list: Cummins/Onan DGDA →, Cummins/Onan DGDB →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.