| 27 | Low AC voltage shutdown | Voltage on any phase has dropped below a preset value. | Shutdown | Adjustable 50-95% of reference voltage, time delay 2-20 seconds; default 85% for 10 seconds. |
| 32 | Reverse power shutdown | Reverse power detected. | Shutdown | Adjustment range 5-20% of standby kW rating, delay 1-15 seconds; default 10%, 3 seconds. |
| 40 | Reverse Var shutdown | Reverse reactive power detected. | Shutdown | Adjustable 15-50% of rated Var output, delay 10-60 seconds; default 20%, 10 seconds. |
| 46 | Negative sequence overcurrent warning | Excessive imbalances in the three phase load currents and/or power factors. | Warning | Control protects generator from damage due to phase imbalance. |
| 51 | Overcurrent warning/shutdown | Implementation of the thermal damage curve with instantaneous trip level based on CT ratio and application power rating. | Shutdown | AmpSentry protective relay action; see document R1053 time over current curve. |
| 51G | Ground fault overcurrent | Detects a ground fault via external ground fault relay contact input or measured ground current from external CT. | Shutdown | Time delays and thresholds adjustable via InPower or HMI. |
| 59 | High AC voltage shutdown | Output voltage on any phase exceeds preset values; trip time inversely proportional to amount above threshold. | Shutdown | Adjustable 105-125% of nominal voltage, time delay 0.1-10 seconds; default 110% for 10 seconds. |
| 81 o | Over frequency shutdown/warning | Generator set is operating at a potentially damaging frequency level. Settings adjustable from 2-10 Hz above nominal governor set point for a 1-20 second time delay. Default: 6 Hz, 20 seconds, disabled. | Warning | |
| 81 u | Under frequency shutdown | Generator set output frequency cannot be maintained. Settings adjustable from 2-10 Hz below reference governor set point, for a 5-20 second time delay. Default: 6 Hz, 10 seconds. | Shutdown | |
| 81o | Over frequency shutdown/warning | Genset is operating at a potentially damaging frequency level. | Warning | Adjustable 2-10 Hz above nominal governor set point, 1-20 second delay; default 6 Hz, 20 seconds, disabled. |
| 81u | Under frequency shutdown | Genset output frequency cannot be maintained. | Shutdown | Adjustable 2-10 Hz below reference governor set point, 5-20 second delay; default 6 Hz, 10 seconds. |
| 111 | Engine Control Module Critical Internal Failure | Engine Control Module Critical Internal Failure - Bad Intelligent Device or Component | Shutdown | |
| 115 | Engine Speed/Position Sensor Circuit | Engine Speed/Position Sensor Circuit - lost both of two signals from the magnetic pickup sensor - Data Erratic | Shutdown | |
| 122 | Intake Manifold Pressure Sensor Circuit | Intake Manifold Pressure Sensor Circuit - Voltage Above Normal, or Shorted to High Source | Warning | |
| 123 | Intake Manifold Pressure Sensor Circuit | Intake Manifold Pressure Sensor Circuit - Voltage Below Normal, or Shorted to Low Source | Warning | |
| 135 | Oil Pressure Sensor Circuit | Oil Pressure Sensor Circuit - Voltage Above Normal, or Shorted to High Source | Warning | |
| 141 | Oil Pressure Sensor Circuit | Oil Pressure Sensor Circuit - Voltage Below Normal, or Shorted to Low Source | Warning | |
| 143 | Oil Pressure Low | Oil Pressure Low - Data Valid But Below Normal Operational Range - Moderately Severe Level | Warning | |
| 144 | Coolant Temperature Sensor Circuit | Coolant Temperature Sensor Circuit - Voltage Above Normal or Shorted to High Source | Warning | |
| 145 | Coolant Temperature Sensor Circuit | Coolant Temperature Sensor Circuit - Voltage Below Normal or Shorted to Low Source | Warning | |
| 146 | Coolant Temperature High | Coolant Temperature High - Data Valid But Above Normal Operational Range - Moderately Severe Level | Warning | |
| 151 | Coolant Temperature Low | Coolant Temperature Low - Data Valid But Above Normal Operational Range - Most Severe Level | Shutdown | |
| 221 | Barometric Pressure Sensor Circuit | Barometric Pressure Sensor Circuit - Voltage Above Normal, or Shorted to High Source | Warning | |
| 234 | Engine Speed High | Engine Speed High - Data Valid But Above Normal Operational Range - Most Severe Level | Shutdown | |
| 235 | Coolant Level Low | Coolant Level Low - Data Valid But Below Normal Operational Range - Most Severe Level | Shutdown | |
| 415 | Oil Pressure Low | Oil Pressure Low - Data Valid But Below Normal Operational Range - Most Severe Level | Shutdown | |
| 418 | Water in Fuel Indicator High | Water in Fuel Indicator High - Data Valid But Above Normal Operational Range - Least Severe Level | Warning | |
| 441 | Auxiliary Temperature Sensor Input #1 | Auxiliary Temperature Sensor Input #1 - Special Instructions | Shutdown | |
| 442 | Auxiliary Pressure Sensor Input #1 | Auxiliary Pressure Sensor Input #1 - Special Instructions | Shutdown | |
| 451 | Injector Solenoid Cylinder #1 Circuit | Injector Solenoid Cylinder #1 Circuit - Current Below Normal, or Open Circuit | Warning | |
| 452 | Injector Solenoid Cylinder #5 Circuit | Injector Solenoid Cylinder #5 Circuit - Current Below Normal, or Open Circuit | Warning | |
| 453 | Injector Solenoid Cylinder #3 Circuit | Injector Solenoid Cylinder #3 Circuit - Current Below Normal, or Open Circuit | Warning | |
| 561 | Injector Solenoid Cylinder #5 | Injector Cylinder #5 - Mechanical System Not Responding Properly or Out Of Adjustment | Warning | |
| 689 | ECM Program Memory (RAM) Corruption | ECM Program Memory (RAM) Corruption - Condition Exists | Warning | |
| 731 | Starter Relay Circuit | Starter Relay Circuit - Voltage Above Normal, or Shorted to High Source | Warning | |
| 755 | ECM Data Lost | Electronic Control Module data lost - Condition Exists | Warning | |
| 1117 | Power Lost With Ignition On | Power Lost With Ignition On - Data Erratic, Intermittent, or Incorrect | | |