| 101 | IDLE MODE | Indicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. | Warning | Remove ground from engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Local or remote Emergency Stop activated | Shutdown | Turn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required. |
| 1122 | Rated/Idle Trans | | Info | |
| 1123 | Shutdown After Battle Short | Shutdown fault occurred while Battle Short was enabled and then disabled. | Shutdown | Review Fault History and perform corrective action. |
| 1124 | Delayed Shutdown | Shutdown fault became active while Delayed Shutdown feature was enabled. | Warning | Review Fault History and perform corrective action. |
| 1131 | Battle Sh Active | Control is in Battle Short mode. | Warning | Bypasses several critical fault shutdowns for emergency operation. |
| 121 | Speed Signal Lost | Mag pickup speed indication is not being sensed. | Shutdown | Restart and check RPM on the digital display. |
| 1311 | Customer Input #1 | | | Optional customer selection (e.g. Low Fuel Day Tank, Water In Fuel, Ground Fault). Programmable via service tool: enable/disable, status/warning/shutdown, active open/closed, display name. |
| 1311, 1312, 1317, 1318 | CUSTOMER INPUT #1 - #4 | Optional customer-selected fault input is active. | Warning | Check external wiring and active input (closed/open) selection. |
| 1312 | Customer Input #2 | | | See code 1311. |
| 1313-1316 | Network Fault 1 thru 4 | | | |
| 1317 | Customer Input #3 | | | See code 1311. |
| 1318 | Customer Input #4 | | | See code 1311. |
| 1334 | Crit Scaler Out Of Range | Incorrect feature or calibration entered into control. | Shutdown | Reload correct calibration. |
| 1335 | Noncrit Scaler Out Of Range | Incorrect feature or calibration entered into control. | Warning | Reload correct calibration. |
| 1337 | No Message | | Info | |
| 135 | Oil Pressure Sensor H | Engine oil pressure sender signal is shorted high. | Warning | Check sender/connectors/wires. |
| 141 | Oil Pressure Sensor L | Engine oil pressure sender signal is shorted low. | Warning | Check sender/connectors/wires. |
| 1416 | Fail To Shutdown | Genset continues to run after shutdown command. | Warning | Check Battle Short feature enabled condition. |
| 1417 | Powr Down Error | Controller cannot power down. | Warning | Controller cannot power down; possible drain on battery. Contact an authorized service center. |
| 143 | Pre-Low Oil Pres | Engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure. |
| 1433 | Emergency Stop | Local Emergency Stop. | Shutdown | Pull button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto. |
| 1434 | Remote E-Stop | Remote Emergency Stop. | Shutdown | See code 1433 to reset. |
| 1435 | Low Coolant Temp | Warning LED illuminates when engine jacket water coolant temperature falls below 70°F (21°C); per NFPA 110 requirement, indicates engine may not accept load within 10 seconds | Warning | Set is not operating; occurs when coolant temperature is 70°F (21°C) or lower. Check coolant heater power/fuse/cord, check coolant level and leaks. |
| 1438 | Fail To Crank | Engine failed to crank after PCC received a start signal. | Shutdown | Possible fault with control, speed sensing, or starting system. See code 441 for corrective action. |
| 144 | Coolant Sensor High | Engine coolant temperature signal is shorted high. | Warning | Check sender/connectors/wires. |
| 1442 | Weak Battery | Battery voltage at or below weak battery warning trip point during cranking. | Warning | See code 441 for corrective action. |
| 1443 | Battery Failed | Dead battery - engine will not start. | Shutdown | See code 441 for corrective action. |
| 1444 | KW Overload | Generator output power exceeded 105% of genset rating. | Warning | Check load and load lead connections; check CTs. |
| 1445 | Short Circuit | Generator output current has exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 1446 | High AC Voltage | One or more phase voltages exceeded 130% of nominal. | Shutdown | Check fault simulation, load removal, threshold settings, Base board/generator. |
| 1447 | Low AC Voltage | Phase voltages dropped below 85% of nominal for 10 seconds. | Shutdown | Check overload, output terminal connections, PMG/field wiring, rectifier diodes. |
| 1448 | Under Frequency | Engine speed dropped below 90% of nominal for 10 seconds. | Shutdown | Check fuel supply, intake air supply and load. |
| 1449 | Over Frequency | Frequency is 10% above base frequency for 20 seconds. | Warning | Check fuel or air delivery; check connections. |
| 145 | Coolant Sensor Low | Engine coolant temperature signal is shorted low. | Warning | Check sender/connectors/wires. |
| 1452 | Gen CB Not Close | Genset circuit breaker (S2) failed to close when PTC is enabled. | Warning | Refer to Section 5 troubleshooting charts. |
| 1453 | Gen CB Not Open | Genset circuit breaker (S2) failed to open when PTC is enabled. | Warning | Refer to Section 5 troubleshooting charts. |
| 1459 | Reverse Power | Improper CT phasing. | Shutdown | Check wiring to voltage sense circuit; refer to CT Installation in Section 6. |
| 146 | Pre-High Coolant Temp | Engine has begun to overheat. | Warning | Reduce load; check air inlets/outlets; follow code 151 if engine can be stopped. |
| 1461 | Loss Of Field | Loss of field (electric) due to reverse kVAR. | Shutdown | Check excitation circuit. |
| 1466 | Modem Failure | Control cannot communicate with the modem. | Warning | Check for open, short to ground and loose connections to the modem. |
| 1468 | Network Error | Momentary loss of communication from the LonWorks Network. | Warning | Refer to LonWorks Network publications. |
| 1469 | Speed/Hz Match | Measured speed and measured AC output frequency do not agree. | Shutdown | Check calibration file. |
| 1471 | Over Current | Generator output current exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 1472 | Over Current | Output current exceeded 110% of rated and time/current calculation initiated shutdown. | Shutdown | Check load and load lead connections. |
| 151 | High Coolant Temp | Engine has overheated above the shutdown trip point. | Shutdown | Allow engine to cool completely. Check coolant level and replenish if low, look for leaks and repair. Check for obstructions to cooling airflow. Check fan belt. Check blower fan/circulation pumps on remote radiator installations. Reset control and restart. |
| 197 | Low Coolant Level | Engine coolant level has fallen below the warning trip point. | Warning | Optional. If generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure. If engine can be stopped, follow code 235 procedure. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, replenish if low, reset control and restart; contact authorized service center. |
| 204 | OIL PRES SENDER | Indicates that the control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70°F (21°C) or lower. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary. | Warning | Review 212 correction list; increase in load or higher ambient may cause shutdown. |
| 212 | Oil Temp Sensor H | Indicates engine has overheated (coolant temperature above 215° F (102° C) − standby or 207° F (97° C) − primary). | Warning | Cool engine; check coolant level, airflow obstructions and fan belt; reset and restart. |
| 213 | Oil Temp Sensor L | Resistance of the coolant temperature sender is out of range. | Warning | Contact authorized service center. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Cool engine; check coolant level and leaks; reset control and restart. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Shutdown | Cool engine; check coolant level and leaks; reset control and restart. Shutdown will not occur in Idle mode. |
| 220 | MAG PICKUP | Mag pickup speed indication not sensed or does not match output frequency | Shutdown | Restart and check RPM; check PCC model setting; inspect and test MPU. |
| 221 | FAIL TO CRANK | Possible fault with control or starting system. | Shutdown | Clean and tighten battery cables; recharge or replace battery; contact service center. |
| 222 | OVERCRANK | Possible fuel system problem. | Shutdown | Check fuel tank, leaks, plugged lines, fuel filter and air filter; reset control and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed. (115% ±1% of nominal). | Shutdown | Contact authorized service center. |
| 224 | FAIL TO SYNCHRONIZE | Generator set has not synchronized to the system bus within the allowable time frame. | Warning | Check governor system stability; adjust governing and synchronizer parameters; check fuel system. |
| 226 | FAIL TO CLOSE | Paralleling breaker has been given a signal to close, but has not closed properly. | Shutdown | Verify breaker charging mechanism; check close signal; verify auxiliary contact signals. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Lower battery charger float level if applicable; check engine DC alternator. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | See warning message 230 LOW DC VOLTAGE. |
| 2323-2326 | Network Fault 5 thru 8 | | | |
| 2327 | PTC Fault | PTC module or communication link is not working properly. | Warning | Check PTC module power, ground shield, cycle control power. |
| 2329 | Low S1 Frequency | Low utility (S1) frequency. | Warning | Check S1 AC inputs and wiring to PTC at TB5; check sensor set points. |
| 2331 | Low S1 Voltage | Low utility (S1) voltage. | Warning | Check S1 AC inputs and wiring to PTC at TB5; check pickup/dropout set points. |
| 2335 | Excitation Fault | Loss of all three voltage sense leads or failure in excitation circuit. | Shutdown | Check field wiring (X1 and X2) for shorts or opens. |
| 2336 | Memory Error | Control memory error; data corruption of critical operating parameters. | Shutdown | Try reloading calibration file. |
| 2337 | Pwr Tran Disabled | PTC module available but PTC feature not enabled. | Warning | Enable PTC feature with InPower; cycle control power. |
| 2338 | Pwr Tran Failure | Control could not communicate with the PTC module. | Warning | Check PTC module power and cable ground shield; cycle control power. |
| 2339 | Pwr Down Enabled | Power Down (sleep) enabled but PTC module or network board is active. | Warning | None required. |
| 234 | Overspeed | Engine has exceeded normal operating speed. | Shutdown | Check for large block load removal, flammable vapors or leaking turbocharger seals. |
| 2341 | High Control Temp | Control temperature above 158 F (70 C) for longer than set time. | Warning | Check genset room air flow. |
| 2342 | Too Long In Idle (10 min.) | Genset has been in Idle mode too long. | Warning | Exit idle mode. |
| 235 | Low Coolant Level | Engine coolant level has fallen below the shutdown trip point. | Shutdown | Optional. Allow engine to cool completely. Check coolant level and replenish if low, look for leaks and repair. Reset control and restart. |
| 2358 | High S1 Voltage | Utility (S1) voltage increased above the over-voltage threshold. | Warning | Measure S1 AC inputs at PTC module; check sensor set points. |
| 2396 | S1 CB Not Close | Utility contact (S1) failed to close with PTC enabled. | Warning | Refer to Section 5 troubleshooting charts. |