HomeEnginesCummins/Onan QSM11G4

Cummins/Onan QSM11G4 Engine

The Cummins/Onan QSM11G4 is a 10.8 L 6-cylinder turbocharged, egr and cac engine rated at 1800 rpm, producing up to 350 kW. It powers generator sets from Cummins/Onan and Terex, including the DQHAA, DQHAB, DQHAB-6515690 and DQHAB-7229336. It holds 36.72 L (9.7 gal) of oil and 33.7 L (8.9 gal) of coolant.

Also known as: CUMMINS QSM11G4

Part of the Cummins/Onan QSM11G4 engine family — 2 variants share parts & fitment.

10.8 L
Displacement
6
Cylinders
1800 rpm
Rated speed
350 kW
Gross power

Engine specifications

Oil capacity36.72 L
Coolant capacity33.7 L
Displacement10.8 L
Cylinders6
AspirationTurbocharged, EGR and CAC
Rated speed1800 rpm
Gross power350 kW

Generator sets powered by this engine

5

Shared across brands: Cummins/Onan, Terex

Cummins/Onan DQHAACummins/Onan DQHABCummins/Onan DQHAB-6515690Cummins/Onan DQHAB-7229336Terex T360 Super Quiet Generator

How to read your Cummins/Onan engine serial & model number →

Common problems

15
  • Over Current 1471
  • Low Coolant Level 197
  • Weak Battery 1442
  • Under Frequency 1448
  • Too Long in Idle 2342
  • Speed/Hz Match 1469
  • Speed Signal Lost 121
  • Shutdown After Battle Short 1123
  • Short Circuit 1445
  • Remote Emergency Stop 1434
  • Pre-Low Oil Pressure Sensor 143
  • Pre-High Cool Temp 146
  • Power Down Failure 1417
  • Overspeed 234
  • Over Frequency 1449

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan QSM11G4.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterClean/replace engine air cleaner element; Inspect/clean engine ground1000 hr
Fuel filterDrain fuel system primary filter/water separator500 hr
Oil filterInspect, adjust or replace alternator or fan belt; Change cooling system coolant (ELC); Replace water separator element; Replace fuel system secondary filter; Inspect/adjust engine valve lash; Inspect aftercooler core; Inspect alternator; Inspect engine mounts; Inspect starting motor; Inspect turbocharger; Inspect water pump2000 hr
BatteryCheck battery electrolyte level500 hr
BeltInspect, adjust or replace alternator or fan belt; Inspect/adjust engine valve lash; Inspect aftercooler core; Inspect alternator; Inspect engine mounts; Inspect starting motor; Inspect turbocharger; Inspect water pump2000 hr
CoolantCheck cooling system coolant level; Check driven equipment; Inspect engine air cleaner service indicator; Check engine oil level; Drain tank water and sediment; Check battery electrolyte level; Clean/test aftercooler core; Add cooling system coolant extender (ELC); Change cooling system coolant (ELC)50 hr
Coolant filter
OilChange engine oil and filter12000 hr
Spark plugInspect, adjust or replace alternator or fan belt; Inspect/adjust engine valve lash; Inspect aftercooler core; Inspect alternator; Inspect engine mounts; Inspect starting motor; Inspect turbocharger; Inspect water pump2000 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

1
ItemActionHoursMonthsNotes
Engine oil filterReplace440 hrLast changed 8-12-24 at 440.8 Hrs

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

6
TypeItemValueUnitCondition
PressureOil pressure37 / 35 / 34 / 34 / 34 / 35during load bank test at 300 kW (unit not stated in document)
SpeedFrequency60Hzduring load bank test
TemperatureAmbient temperature70 to 72°Ftest room ambient
TemperatureCoolant freeze protection-35°Fcoolant level check
TemperatureCoolant temperature180°Fduring load bank test (178°F during cool down)
VoltageDC voltage28Vduring load bank test

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

1
Generator Check list maintenance
  1. Check coolant level and record freeze protection: -35F.
  2. Visually inspect radiator: Good.
  3. Visually inspect radiator hoses: Good.
  4. Check condition of coolant hoses: Good.
  5. Check condition of fuel hoses: Good.
  6. Check condition of engine belts: Good.
  7. Batteries and QTY: None.
  8. Battery install date if applicable: 8/17.
  9. Genset has battery charger: Yes.
  10. Genset has coolant heater: E204747, 240/480V, 4990W 1PH.
  11. Check engine oil level.
  12. Engine oil filters last changed date and HRS: 8-12-24, 440.8 Hrs.
  13. Inspect exhaust system for cracks / leaks: OPEN SKID UNIT.
  14. Check rain cap for proper operation: OPEN SKID UNIT.
  15. Generator end is 12 lead reconnectable; has PMG permanent magnet generator; electronic engine.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan QSM11G4 family

12
Part #DescriptionCategory
ES100027Distribution Panel Wiring for T360 Series Single Phase Controldistribution_panel_wiring
ES100030Standard Generator Wiring for T360 Seriesgenerator_wiring
A035N852Hose, Drain - Bulk (Order by the Foot - 1 Feet Required)hose
ES100039Idle-Run Wiring (Cummins)idle_run_wiring
134890T360 Super Quiet Generatorother_service
961-0514InPower Service Tool Kitother_service
961-0619Generator Set Supportother_service
A045Z906Isolator, Vibrationother_service
A045Z908Bracket, Switchother_service
E204747Coolant heater 240/480V 6420W 1PHother_service
ES100006Overcurrent Relay Wiringovercurrent_relay_wiring
ES100026Three Position Stack Switch Wiringstack_switch_wiring

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan QSM11G4?

The Cummins/Onan QSM11G4 engine has an oil capacity of 36.72 liters.

What is the displacement of the Cummins/Onan QSM11G4?

The Cummins/Onan QSM11G4 has a displacement of 10.8 liters with 6 cylinders.

Which generators use the Cummins/Onan QSM11G4 engine?

The Cummins/Onan QSM11G4 powers 5 generator set(s), including Cummins/Onan DQHAA, Cummins/Onan DQHAB, Cummins/Onan DQHAB-6515690, Cummins/Onan DQHAB-7229336, Terex T360 Super Quiet Generator.

How often should you change the oil in the Cummins/Onan QSM11G4?

The Cummins/Onan QSM11G4 oil change interval is every 12000 hours.

What is a common problem with the Cummins/Onan QSM11G4 engine?

A commonly reported issue on generators using the Cummins/Onan QSM11G4 is: Over Current.