PowerCommand 3100 Controller

The PowerCommand 3100 is a generator-set controller. It is used on generator sets from Cummins/Onan, including the 1000DFHD, 620DFHA, 700DFHB and 750DFHA.

36
Generator sets
Cummins/Onan
Brand
230–1000 kW
Power range
Diesel
Fuel

Troubleshooting

60

Fault codes

CodeMeaningCauseRemedy
1Green RUN lamp lights following engine startup.Indicates all engine systems are normal.No corrective action required.
10LO FUEL LAMP lights. Engine shuts down and LO OIL PRES lamp lights.Indicates engine has run out of fuel.Check fuel level and replenish as required.
101IDLE MODE
101IDLE MODE — Engine continues to operate at reduced RPMIndicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.When ground is removed from this input, the set returns to normal speed and voltage. When the engine idle function is enabled, the control automatically sets lower oil pressure warning and shutdown trip points to reflect the lower operating speed. When the engine idle function is removed and the set reverts to normal operating speed, the control automatically resets oil pressure warning and shutdown trip points to the normal settings.
101IDLE MODE — Engine continues to operate at reduced RPM.Indicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.When ground is removed from this input, the set returns to normal speed and voltage. When the engine idle function is enabled, the control automatically sets lower oil pressure warning and shutdown trip points to reflect the lower operating speed. When the engine idle function is removed and the set reverts to normal operating speed, the control automatically resets oil pressure warning and shutdown trip points to the normal settings.
101IDLE MODE — WARNING; Engine continues to operate at reduced RPM.Indicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.When ground is removed from this input, the set returns to normal speed and voltage. When the engine idle function is enabled, the control automatically sets lower oil pressure warning and shutdown trip points to reflect the lower operating speed. When the engine idle function is removed and the set reverts to normal operating speed, the control automatically resets oil pressure warning and shutdown trip points to the normal settings.
101IDLE MODE — Warning lamp lights
102EMERGENCY STOPTo reset the local/remote Emergency Stop button: Pull the button out. Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
102EMERGENCY STOP — Engine shuts down and will not crankIndicates local or remote Emergency Stop.To reset the local Emergency Stop button: Pull the button out; Move the Run/Off/Auto switch to Off; Press the Reset switch; Select Run or Auto, as required.
102EMERGENCY STOP — Engine shuts down and will not crank.Indicates local or remote Emergency Stop.To reset the local Emergency Stop button: Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out. Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
102EMERGENCY STOP — SHUTDOWN; Engine shuts down and will not crank.Indicates local or remote Emergency Stop.To reset the local Emergency Stop button: Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out; Move the Run/Off/Auto switch to Off; Press the Reset switch; Select Run or Auto, as required.
102EMERGENCY STOP — Shutdown lamp lights
11LO ENG TEMP lamp lights. Set is in standby mode but is not operating. (Lamp lights when engine coolant temperature is 70° F (21° C) or lower. Since the lamp goes out after the engine warms up, there should be no cause for alarm even during initial generator set operation.)Indicates engine coolant heater is not operating, not circulating coolant or ambient temperature too cold for heater to keep up with demand.Check for the following conditions: a. Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required. b. Check for low coolant level and replenish if required. Look for possible coolant leakage points and repair as required. c. Contact an authorized service center if none of the above.
1123Shutdown After Battle Short
1124Delayed Shutdown
1131Battle Short Active
12The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run.The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay.
121Speed Signal Lost
1244Engine Normal Shutdown
13Fault lamp lights but no fault exists. Engine gauges show oil pressure, engine temperature, and frequency (speed) are within normal limits.The monitor board or a sensor may be at fault.Contact an authorized service center for service.
1311Customer Inputs #1
1312Customer Inputs #2
1317Customer Inputs #3
1318Customer Inputs #4
1334Crit Scaler OR
1335Non-Crit Scaler OR
135Oil Pressure Sensor High
14The BASIN (optional) fault lamp lights. Engine continues to run or is in standby mode. (Engine can be programmed to shut down.)Indicates fuel is leaking from inner tank to outer basin or the sensor may be defective.Contact an authorized service center for service.
141Oil Pressure Sensor Low
1416Fail to Shutdown
1417Power Down Error — WarningThe controller can not power down because of some unknown condition. Possible drain on battery.Contact an authorized service center for service.
1417Power Down Failure
143Pre-Low Oil Pres — WarningEngine oil pressure has dropped to an unacceptable level.If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure.
143Pre-Low Oil Pressure Sensor
1433Emergency Stop
1433Emergency Stop — ShutdownLocal Emergency Stop.To reset the local/remote Emergency Stop button: pull the button out; move the O/Manual/Auto switch to O; press the front panel Fault Acknowledge/Reset button; select Manual or Auto, as required.
1434Remote E-Stop — ShutdownRemote Emergency Stop.See code 1433 to reset.
1434Remote Emergency Stop
1435Low Coolant Temp — WarningEngine coolant heater is not operating or is not circulating coolant. Warning occurs when engine coolant temperature is 70° F (21° C) or lower. NOTE: In applications where the ambient temperature falls below 40 F (4 C), Low Coolant Temp may be indicated even though the coolant heaters are operating.Check for the following conditions: coolant heater not connected to power supply — check for blown fuse or disconnected heater cord and correct as required; check for low coolant level and replenish if required, look for possible coolant leakage points and repair as required.
1435Low Coolant Temperature
1438Fail To Crank — ShutdownPossible fault with control, speed sensing or starting system.See code 441 for corrective action.
1438Fail to Crank
144Coolant Temperature Sensor High
1442Weak Battery
1442Weak Battery — WarningDuring cranking, the battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time.See code 441 for corrective action.
1443Battery Failed
1443Battery Failed — ShutdownDead battery − engine will not start.See code 441 for corrective action.
1444KW Overload
1445Short Circuit
1446High AC Voltage
1447Low AC Voltage
1448Under Frequency
1449Over Frequency
145Coolant Temperature Sensor Low
146Pre-High Cool Temp
146Pre-High Cool Tmp — WarningEngine has begun to overheat (coolant temperature has risen to an unacceptable level).If generator is powering non-critical and critical loads and cannot be shut down: reduce load if possible by turning off non-critical loads; check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow code 151 procedure.
1461Loss of Field
1466Modem Failure
1468Network Error
1469Speed/Hz Match

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.