HomeEnginesCummins/Onan NTA 855-G6 / NTA 855-G5

Cummins/Onan NTA 855-G6 / NTA 855-G5 Engine

The Cummins/Onan NTA 855-G6 / NTA 855-G5 is an engine. It powers generator sets from Cummins/Onan, including the DFCE.

Also known as: Cummins NTA 855-G6 / NTA 855-G5

Part of the Cummins/Onan NTA 855 engine family — 5 variants share parts & fitment.

Engine specifications

Common problems

15
  • UNDER FREQUENCY 313
    Fix: Shutdown
  • SHORT CIRCUIT 322
    Fix: Shutdown
  • Over Current 1471
  • LOW OIL PRESSURE 200
    Fix: Shutdown
  • Low Coolant Level 197
  • LOW AC VOLTAGE 303
    Fix: Shutdown
  • High Coolant Temp 211
    Fix: Indicates engine has begun to overheat and coolant temperature has risen to an unacceptable level: (215° F − standby / 207° F − primary).
  • HIGH AC VOLTAGE 301
    Fix: Shutdown
  • Weak Battery 1442
  • Warning, Shutdown, and Non-Automatic lamps are not lit. Digital display shows main menu or selected menu.
    Cause: Indicates all engine systems are normal. No corrective action required
  • Warning lamp lights. MESSAGE: WEAK BATTERY 232 - WARNING 232
    Fix: Indicates battery voltage drops below 60% of nominal for two seconds, during starting. a. Discharged or defective battery. See Warning message 230, LOW DC VOLTAGE.
  • Warning lamp lights. MESSAGE: RUPTURE BASIN 262
  • Warning lamp lights. MESSAGE: OVERLOAD 330
    Fix: Indicates that three-phase power output exceeds 105% of standby (or 115% of prime) rating. After five seconds, the Load Dump output is activated. After 60 seconds, the OVERLOAD warning is activated. Contact an authorized service center.
  • Warning lamp lights. MESSAGE: OVERCURRENT 320
    Fix: Indicates that generator output current has exceeded 110% of rated for 60 seconds. Contact an authorized service center.
  • Warning lamp lights. MESSAGE: LOW FUEL DAY 240 - WARNING 240
    Fix: Indicates day tank fuel supply is running low. Check fuel supply and replenish as required.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan NTA 855-G6 / NTA 855-G5.

Service intervals

22
ItemActionHoursMonthsNotes
GensetInspect8 hrInspect for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually with set running (footnote X1).
Air CleanerCheck50 hrClean if required. Perform more often in dusty conditions (footnote X2).
Battery Charging SystemCheck50 hr
Charge Air PipingCheck50 hr
Coolant HeaterCheck50 hrColumn alignment in source table is ambiguous; interval as printed in schedule columns.
Coolant LevelCheck50 hr
Fuel LevelCheck50 hr
Oil LevelCheck50 hr
Anti-freeze and DCA ConcentrationCheck100 hrRefer to engine operation and maintenance manual for procedure (footnote X5).
Drive Belt TensionCheck100 hrVisually check belt for evidence of wear or slippage; replace if hard or brittle (footnote X3). Refer to engine operation and maintenance manual (footnote X5).
Exhaust Condensate TrapDrain100 hr
Fuel Filter(s)Drain100 hrDrain 1 cup or more of fuel to remove water and sediment (footnote X4); refer to engine operation and maintenance manual (footnote X5).
Water and Sediment from Fuel TankDrain100 hrDrain 1 cup or more of fuel to remove water and sediment (footnote X4).
Air Cleaner ElementChange250 hrPerform more often in dusty conditions (footnote X2).
Coolant FilterChange250 hrRefer to engine operation and maintenance manual for procedure (footnote X5).
Crankcase BreatherClean250 hrRefer to engine operation and maintenance manual for procedure (footnote X5).
Crankcase oil and filterChange250 hr12 moTable 7-1. If genset used for prime power, change every 6 months or 250 hours. If standby, change every 12 months or 250 hours, whichever comes first.
Starting BatteriesCheck250 hr
Cooling SystemClean500 hrRefer to engine operation and maintenance manual for procedure (footnote X5).
Fuel FiltersChange500 hrRefer to engine operation and maintenance manual for procedure (footnote X5).
Radiator Hoses for Wear & CracksCheck500 hr12 mo
Rupture basin leak detect switchTest12 moSome areas may require weekly inspections by safety code.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceFloat switch assembly float lift clearance below C-clip stop1/8inch (3 mm)use a feeler gauge
ClearanceGenerator-to-engine angular alignment (T.I.R.).001 in. per inch of radius (center of shaft to indicator axis), maximumin750 kW gensets and larger
ClearanceMPU sensor to gear tooth adjustmentback out one quarter turnturnafter contacting gear tooth
ClearanceVibration isolator base elevation difference0.25inch (6 mm)all isolator bases within this elevation of each other
ClearanceVibration isolator clearance between top plate and base0.25inch (6 mm)nominal or greater
ClearanceVibration isolator top plate to base clearance0.25inch (6 mm)nominal, or greater
GapAir cleaner cleaning nozzle distance1inch (25 mm)at least
GapAngular alignment total indicator reading (T.I.R.)0.001inch per inch of radiusmaximum
GapFloat switch lift to test open1/8inchbelow C-clip stop
OtherAir cleaner cleaning compressed air30psi (207 kPa)blow from clean side, nozzle at least 1 inch (25 mm) away
OtherAngular alignment maximum T.I.R..001inch per inch of radiuscenter of shaft to indicator axis
OtherBattery electrolyte specific gravity, charge if below1.215
OtherBattery electrolyte specific gravity, fully charged (corrected)1.260corrected; add 0.004 per 10°F above 80°F (27°C)
OtherCool-down at idle timer range0 to 30minutes
OtherGOV GAIN default value for paralleling applications70%
OtherREG VHZ (underfrequency roll-off) adjustable range1 through 50; normal range 7 through 21
OtherRated To Idle delay range0 to 10secondsdefault = 0; Beginning Version 2.303
OtherStart Delay setting range0 to 300secondsdefault = 0
OtherStart delay adjustment range0 to 300seconds
OtherStop Delay setting range0 to 600secondsdefault = 0
OtherStop delay adjustment range0 to 600seconds
OtherWarm-up at idle time delay range0-300seconds
PressureEngine oil pressure - K19 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - K38 normal45-65psi (310-448 kPa)run mode
PressureEngine oil pressure - K50 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - L10/M11 normal30-50psi (207-345 kPa)run mode
PressureEngine oil pressure - NTA 855 normal35-50psi (241-345 kPa)run mode
PressureEngine oil pressure - V28 normal50-90psi (345-620 kPa)run mode
PressureEngine oil pressure shutdown limit - L10/M1120psi (138 kPa)run mode value
PressureEngine oil pressure shutdown limit - L10/M118psi (55 kPa)idle mode value
PressureEngine oil pressure warning limit - L10/M1112psi (83 kPa)idle mode value
PressureEngine oil pressure warning limit - L10/M1125psi (172 kPa)run mode value
PressureIdle oil pressure shutdown limit12psi (83 kPa)
PressureIdle oil pressure shutdown limit (PCC)12psi (83 kPa)idle
PressureIdle oil pressure warning limit15psi (104 kPa)
PressureIdle oil pressure warning limit (PCC)15psi (104 kPa)idle
PressureK19 engine idle oil pressure20psi (138 kPa)idle
PressureK19 engine normal oil pressure50-70psi (345-482 kPa)normal run
PressureK19 oil pressure shutdown/warning limitsshutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idlepsi (kPa)
PressureK38 engine idle oil pressure20psi (138 kPa)idle
PressureK38 engine normal oil pressure45-65psi (310-448 kPa)normal run
PressureK38 oil pressure shutdown/warning limitsshutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idlepsi (kPa)
PressureK50 engine idle oil pressure20psi (138 kPa)idle
PressureK50 engine normal oil pressure50-70psi (345-482 kPa)normal run
PressureK50 oil pressure shutdown/warning limitsshutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idlepsi (kPa)
PressureL10/M11 engine idle oil pressure15psi (103 kPa)idle
PressureL10/M11 engine normal oil pressure30-50psi (207-345 kPa)normal run
PressureL10/M11 oil pressure shutdown limit20psi (138 kPa)run mode value
PressureL10/M11 oil pressure shutdown limit8psi (55 kPa)idle mode value
PressureL10/M11 oil pressure warning limit12psi (83 kPa)idle mode value
PressureL10/M11 oil pressure warning limit25psi (172 kPa)run mode value
PressureLow oil pressure shutdown (Detector)14psi (97 kPA)
PressureNTA 855 engine normal oil pressure35-50psi (241-345 kPa)normal run
PressureNTA 855 oil pressure shutdown limit25psi (172 kPa)run mode value
PressureNTA 855 oil pressure shutdown limit8psi (55 kPa)idle mode value
PressureNTA 855 oil pressure warning limit12psi (83 kPa)idle mode value
PressureNTA 855 oil pressure warning limit30psi (207 kPa)run mode value
PressureNormal engine oil pressure (PCC)35-50psi (242-345 kPa)
PressureNormal oil pressure35-50psi (242-345 kPa)
PressureOil pressure shutdown limit25psi (172 kPa)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolantsoft water / E.G. / DCA mixtureCooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist).
CoolantNFPA 110above 4°CNFPA 110 recommends engine jacket water coolant heaters where minimum ambient is above 40°F (4°C); coolant maintained at minimum 90°F (32°C). Cooling system capacity with standard radiator: DFAB/DFAC 13 Gal (49 L); DFBF 13.5 Gal (51 L); DFCC 13.5 Gal (51 L); DFCE 15 Gal (57 L).
Engine oilRefer to Cummins engine Operation and Maintenance ManualGensets are shipped with oil added. Check oil level before initial start. Keep oil level near high mark on dipstick without overfilling.
FuelDiesel fuelDo not use zinc coated or copper fuel lines with diesel fuel. Fuel connection at the engine should be made with an approved flexible line.
FuelASTM No. 2 dieselCummins engine Operation and Maintenance Manual alternate diesel fuelsCummins engines normally use ASTM No. 2 diesel fuel. Never use galvanized or copper fuel lines, fittings or fuel tanks.
FuelASTM No. 2 diesel fuelASTM No. 2Cummins engines normally use ASTM No. 2 diesel fuel; they will operate on alternate diesel fuels within the specifications shown in the Cummins engine Operation and Maintenance Manual. Never use galvanized or copper fuel lines, fittings or fuel tanks.
FuelDieselDay tank fuel transfer pump maintains reservoir of diesel fuel in the day tank.
FuelNo. 2 Diesel Fuel; Bio-Diesel B5-B20 approved with recommendationsASTM D975 (post-storage purge fuel)Bio-diesel not recommended for Emergency Standby RV use (low annual hours, critical start nature).
GreaseLithium based-30°C to 120°C81.0 mlMobilux No. 2 or Shell Alvania R3; generator end bearing; temperature range -22 F to +248 F (-30 C to +120 C); grease divided between bearing, bearing cap cavity and cartridge cavity.
GreaseLithium based grease, Mobilux No. 2 or Shell Alvania R3-30°C to 120°C2.74 oz (81 ml)End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
101IDLE MODEIndicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.WarningRemove ground from engine idle input to return to normal speed and voltage.
102EMERGENCY STOPLocal or remote Emergency Stop.ShutdownTurn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
1122Rated/Idle Trans
1123Shutdown After BSShutdown fault occurred while Battle Short was enabled and then disabled.ShutdownReview Fault History and perform corrective action.
1124Delayed ShutdownShutdown fault became active while Delayed Shutdown feature was enabled.WarningReview Fault History and perform corrective action.
1131Battle Sh ActiveControl is in Battle Short mode.WarningBypasses several critical fault shutdowns for emergency operation.
121Speed Signal LostMag pickup speed indication is not being sensed.ShutdownRestart and check RPM on the digital display.
1311Customer Input #1The nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Enable/disable input (Default: enable); Status, Warning or Shutdown (Default: #1-None, #2 thru #4-Warning); Active closed or open (Default: closed [ground]); change display name up to 19 characters (Default: #1-Customer Fault 1).
1311, 1312, 1317, 1318CUSTOMER INPUT #1 - #4Optional customer-selected fault input is active.WarningCheck external wiring and active input (closed/open) selection.
1312Customer Input #2Default display name: Ground Fault.Configurable input; defaults #2 thru #4 = Warning.
1317Customer Input #3Default display name: Low Fuel.Configurable input; defaults #2 thru #4 = Warning.
1318Customer Input #4Default display name: Rupture Basin Fault.Configurable input; defaults #2 thru #4 = Warning.
1334Crit Scaler ORIncorrect feature or calibration entered into control.ShutdownReload correct calibration.
1335Noncrit Scaler ORIncorrect feature or calibration entered into control.WarningReload correct calibration.
1337No Message
135Oil Pressure Sensor HEngine oil pressure sender signal is shorted high.WarningCheck sender/connectors/wires.
141Oil Pressure Sensor LEngine oil pressure sender signal is shorted low.WarningCheck sender/connectors/wires.
1416Fail To ShutdownGenset continues to run after shutdown command.WarningCheck Battle Short feature enabled condition.
1417Powr Down ErrorIndicates that the controller can not power down because of some unknown condition. Possible drain on battery.WarningContact an authorized service center for service.
143Pre-Low Oil PresIndicates engine oil pressure has dropped to an unacceptable level. If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure.WarningIf powering critical loads and cannot be shut down, wait until next shutdown period and follow code 415 procedure.
1433Emergency StopLocal Emergency Stop.ShutdownTo reset: pull the button out; move the O/Manual/Auto switch to O; press the front panel Fault Acknowledge/Reset button; select Manual or Auto as required.
1434Remote E-StopRemote Emergency Stop.ShutdownSee code 1433 to reset.
1435Low Coolant TempWarning occurs when engine coolant temperature is 70°F (21°C) or lower. In applications where the ambient temperature falls below 40°F (4°C), Low Coolant Temp may be indicated even though the coolant heaters are operating.WarningIndicates engine coolant heater is not operating or is not circulating coolant. Check that coolant heater is connected to power supply (check for blown fuse or disconnected heater cord). Check for low coolant level and replenish if required; look for possible coolant leakage points and repair as required.
1438Fail To CrankIndicates possible fault with control, speed sensing or starting system.ShutdownSee code 441 for corrective action.
144Coolant Sensor HighEngine coolant temperature signal is shorted high.WarningCheck sender/connectors/wires.
1442Weak BatteryIndicates that during cranking, the battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time.WarningSee code 441 for corrective action.
1443Battery FailedDead battery - engine will not start.ShutdownSee code 441 for corrective action.
1444KW OverloadGenerator output power exceeded 105% of genset rating.WarningCheck load and load lead connections; check CTs.
1445Short CircuitGenerator output current has exceeded 175% of rated.ShutdownCheck load and load lead connections.
1446High AC VoltageOne or more phase voltages exceeded 130% of nominal.ShutdownCheck fault simulation, load removal, threshold settings, Base board/generator.
1447Low AC VoltagePhase voltages dropped below 85% of nominal for 10 seconds.ShutdownCheck overload, output terminal connections, PMG/field wiring, rectifier diodes.
1448Under FrequencyEngine speed dropped below 90% of nominal for 10 seconds.ShutdownCheck fuel supply, intake air supply and load.
1449Over FrequencyFrequency is 10% above base frequency for 20 seconds.WarningCheck fuel or air delivery; check connections.
145Coolant Sensor LowEngine coolant temperature signal is shorted low.WarningCheck sender/connectors/wires.
1452Gen CB Not CloseGenset circuit breaker (S2) failed to close when PTC is enabled.WarningRefer to Section 5 troubleshooting charts.
1453Gen CB Not OpenGenset circuit breaker (S2) failed to open when PTC is enabled.WarningRefer to Section 5 troubleshooting charts.
1459Reverse PowerImproper CT phasing.ShutdownCheck wiring to voltage sense circuit; refer to CT Installation in Section 6.
146Pre-High Coolant TempIndicates engine has begun to overheat (coolant temperature has risen to an unacceptable level).WarningReduce load; check air inlets/outlets; follow code 151 if engine can be stopped.
1461Loss Of FieldLoss of field (electric) due to reverse kVAR.ShutdownCheck excitation circuit.
1466Modem FailureControl cannot communicate with the modem.WarningCheck for open, short to ground and loose connections to the modem.
1468Network ErrorMomentary loss of communication from the LonWorks Network.WarningRefer to LonWorks Network publications.
1469Speed/Hz MatchMeasured speed and measured AC output frequency do not agree.ShutdownCheck calibration file.
1471Over CurrentGenerator output current exceeded 110% of rated for 60 seconds.WarningCheck load and load lead connections.
1472Over CurrentOutput current exceeded 110% of rated and time/current calculation initiated shutdown.ShutdownCheck load and load lead connections.
151High Coolant TempIndicates engine has overheated (coolant temperature has risen above the shutdown trip point). Allow engine to cool down completely before proceeding.ShutdownCheck coolant level and replenish if low; look for coolant leakage points and repair. Check for obstructions to cooling airflow. Check fan belt and repair or tighten if necessary. Check blower fan and circulation pumps on remote radiator installations. Reset control and restart after correcting problem.
197Low Coolant LevelIndicates engine coolant level has fallen below the warning trip point (optional).WarningIf powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure. If engine can be stopped, follow code 235 procedure.
200LOW OIL PRESSUREIndicates engine oil pressure has dropped to an unacceptable level.WarningIf powering critical loads, wait until next shutdown period then follow 201 procedure.
201LOW OIL PRESSUREIndicates engine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters; replenish if low; reset control and restart; contact service center.
204OIL PRES SENDERIndicates that the control has sensed that the engine oil pressure sender is out of its working range.WarningCheck that the engine oil pressure sender is properly connected. Contact service center.
210LOW COOLANT TEMPWarning occurs when engine coolant temperature is 70°F (21°C) or lower.WarningWarning LED illuminates. Check the coolant heaters for proper operation; if operating properly, other precautions may be necessary to warm the engine before applying a load.
211HIGH COOLANT TEMPIndicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary.WarningReduce load; check air inlets/outlets and remove obstructions.
212Oil Temp Sensor HIndicates engine has overheated (coolant temperature above 215° F (102° C) − standby or 207° F (97° C) − primary).WarningCheck sender/connectors/wires.
213Oil Temp Sensor LResistance of the coolant temperature sender is out of range.WarningContact an authorized service center.
214LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.WarningCheck coolant level in radiator and coolant recovery bottle; replenish if low; look for leaks.
215LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.ShutdownAllow engine to cool; check coolant level and replenish; look for leaks and repair; reset and restart. Shutdown will not occur in Idle mode.
220MAG PICKUPMag pickup speed indication not sensed or does not match generator set output frequency.ShutdownRestart and check RPM; check PCC model setting; inspect and test MPU.
221FAIL TO CRANKPossible fault with control or starting system.ShutdownCheck fuse F3 on the Engine Interface board. Check for poor battery cable connections; clean battery cable terminals and tighten. Recharge or replace a discharged or defective battery.
222OVERCRANKPossible fuel system problem.ShutdownCheck for empty fuel tank, leaks, plugged fuel lines; replace dirty fuel or air filter; reset and restart.
223OVERSPEEDIndicates engine has exceeded normal operating speed. (115% ±1% of nominal).ShutdownContact an authorized service center.
224FAIL TO SYNCHRONIZEGenerator set has not synchronized to the system bus within the allowable time frame.WarningCheck governor system stability; adjust governing and synchronizer parameters; check fuel system.
226FAIL TO CLOSEParalleling breaker has been given a signal to close, but has not closed properly.ShutdownVerify breaker charging mechanism; check close signal; verify auxiliary contact signals.
230LOW DC VOLTAGEIndicates battery voltage is below 10 VDC.WarningRecharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable.
231HIGH DC VOLTAGEIndicates battery voltage exceeds 32 VDC.WarningLower battery charger float level if applicable; check engine DC alternator.
232WEAK BATTERYIndicates battery voltage drops below 60% of nominal for two seconds, during starting.WarningSee Warning message 230, LOW DC VOLTAGE.
2327PTC FaultPTC module or communication link is not working properly.WarningCheck PTC module power, ground shield, cycle control power.
2329Low S1 FrequencyLow utility (S1) frequency.WarningCheck S1 AC inputs and wiring to PTC at TB5; check sensor set points.
2331Low S1 VoltageLow utility (S1) voltage.WarningCheck S1 AC inputs and wiring to PTC at TB5; check pickup/dropout set points.
2335Excitation FaultLoss of all three voltage sense leads or failure in excitation circuit.ShutdownCheck field wiring (X1 and X2) for shorts or opens.
2336Memory ErrorControl memory error; data corruption of critical operating parameters.ShutdownTry reloading calibration file.
2337Pwr Tran DisabledPTC module available but PTC feature not enabled.WarningEnable PTC feature with InPower; cycle control power.
2338Pwr Tran FailureControl could not communicate with the PTC module.WarningCheck PTC module power and cable ground shield; cycle control power.
2339Pwr Down EnabledPower Down (sleep) enabled but PTC module or network board is active.WarningNone required.
234OverspeedEngine has exceeded normal operating speed.ShutdownCheck for large block load removal, flammable vapors or leaking turbocharger seals.
2341High Control TempControl temperature above 158 F (70 C) for longer than set time.WarningCheck genset room air flow.
2342Too Long In Idle (10 min.)Indicates genset has been in Idle mode too long (10 minutes maximum).WarningExit idle mode.
235Low Coolant LevelIndicates engine coolant level has fallen below the shutdown trip point (optional). Allow engine to cool down completely before proceeding.ShutdownCheck coolant level and replenish if low; reset control.
2358High S1 VoltageUtility (S1) voltage increased above the over-voltage threshold.WarningMeasure S1 AC inputs at PTC module; check sensor set points.
2396S1 CB Not CloseUtility contact (S1) failed to close with PTC enabled.WarningRefer to Section 5 troubleshooting charts.
2397S1 CB Not OpenUtility contact (S1) failed to open with PTC enabled.WarningRefer to Section 5 troubleshooting charts.
240LOW FUEL−DAYIndicates day tank fuel supply is running low.WarningCheck fuel supply and replenish as required.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjust Start/Stop Delays (PCC Adjust Menu) adjustment

⚠ Electrostatic discharge will damage circuit boards. Always wear a grounding wrist strap when working inside control box.

  1. Press the button next to ADJUST in the Main Menu; the VOLTAGE submenu appears.
  2. Press the button next to >> to move through VOLTAGE and FREQUENCY to the START DELAY submenu.
  3. Use the buttons next to the up and down symbols to set the start delay.
  4. Press >> to move to the STOP DELAY submenu and set the stop delay.
  5. Press >> to move to the IDLE SPEED submenu and set idle speed (only in idle mode).
  6. Press >> to move to SAVE/EXIT; select SAVE then EXIT to return to Main menu.
Adjusting Values/Parameters (PCC Adjust Menu) adjustment
  1. Press the button next to the arrow symbol in the display until the + and - symbols are displayed.
  2. If necessary, press the button next to the arrows to move to the numeric character to change.
  3. Press + to increase the value or select the parameter; press - to decrease the value or select the parameter.
  4. Press the save symbol to save changes; changes are not saved if Home or Previous Main Menu is pressed first.
Aligning Generator with Engine (Angular Alignment) adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.

Tools: Dial indicator, Shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with the sensing point on the capscrew head or flat surface of the drive disc at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
  4. Determine the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one revolution.
  5. Measure the distance from the center of the generator shaft to the indicator measuring point.
  6. Measure the distance from the generator side of the flex discs to the center of the generator mounting bolt.
  7. Compare the distances; multiply this ratio times one half the T.I.R. to approximate the amount of shims to remove or add.
Angular Alignment Procedure (750 kW Gensets and Larger) adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) before beginning.

⚠ Do not bar engine over by prying on fan blade.

Tools: Dial indicator, Shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan, with the sensing point on the capscrew head or drive disc flat surface at bolt circle diameter.
  3. Bar the engine over clockwise as viewed from the engine flywheel; do not allow it to roll back on compression.
  4. Total indicator reading (T.I.R.) is the sum of the maximum positive and negative readings as the engine completes one revolution.
  5. To lower the generator, remove equal shims from under both generator mounting feet; approximate shim amount from the distance ratio.
Angular Alignment Procedure (Generator to Engine) adjustment

⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.

⚠ Do not bar engine over by prying on fan blade.

Tools: dial indicator

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with sensing point resting on the drive disc capscrew head/flat surface at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from the engine flywheel; do not allow it to roll back on compression at the end of travel of each reading.
  4. Record the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one engine revolution.
  5. Compare the measured T.I.R. to the maximum allowed (.001 in. per inch of radius from center of shaft to indicator axis); add or remove shims under the generator mounting feet to correct.
Axial Alignment Procedure adjustment

Tools: Dial indicator, Magnetic base or clamp

  1. Check axial alignment only when an objectionable vibration is present after angular alignment.
  2. Fasten dial indicator holding device to skid base, engine block, or generator shell with a magnetic base or clamp; rest sensor on generator shaft hub.
  3. Bar the engine over clockwise through a couple of rotations; record indicator readings at eight equally spaced points around the shaft diameter.
  4. To correct out-of-tolerance T.I.R., remove the drive disc capscrews, mark discs and flywheel, rotate 180 degrees from original location, retorque, and recheck.
  5. If unchanged, rotate the discs to 30, 60 or 90 degrees from their original location.
Axial Alignment Procedure (Generator to Engine) adjustment

Tools: dial indicator

  1. Fasten a dial indicator holding device to the skid base, engine block, or generator shell with the sensor point resting on the generator shaft hub.
  2. Bar the engine over in a clockwise rotation through a couple of rotations, recording indicator readings at eight equally spaced points around the shaft diameter to obtain axial T.I.R.
  3. Reduce the measured T.I.R. runout by one half if excessive vibration remains after angular alignment.
Voltage Adjustment adjustment

⚠ Do not adjust the factory-sealed V/HZ break point pot.

⚠ Hazardous voltage inside output box.

  1. Remove the protective cover for access to the voltage adjusting pot and 50/60 Hz selector switch.
  2. Check the position of the 50/60 Hz selector switch and change if necessary.
  3. Adjust no-load voltage as required.
  4. Replace the cover.
Cooling System Test (LAT calculation) diagnostic

Tools: Load bank, Thermocouples (No. 24 AWG or lighter)

  1. Complete a representative installation.
  2. Load the genset to rated full-load using a load bank.
  3. Conduct the test at ambient >= 21 C (70 F).
  4. Measure engine coolant outlet temperature and shielded ambient air temperature with thermocouples.
  5. Expel air from the coolant system before testing; add coolant as necessary.
  6. Run at full-load and record temperatures at 15-minute intervals until stable.
  7. Calculate LAT = T(max) 107C - T(test) + T(amb); goal LAT >= 40 C (104 F).
Generator/Base Board Isolation Procedure diagnostic

⚠ This test involves unregulated excitation of the generator.

⚠ Hazardous voltage; use insulated tools and stand on dry platform.

Tools: Voltmeter, Jumper leads, 12V battery

  1. Throw line circuit breaker OFF and shut down the set.
  2. Disconnect exciter stator leads X and XX from AC harness.
  3. Prepare to measure output voltage across generator terminals.
  4. Bring 12V battery jumpers to X (Field +) and XX (Field -).
  5. Verify polarity is correct before connecting.
  6. Start set; connect battery negative to XX lead.
  7. If rated voltage and balanced phases, generator is OK.
  8. If unbalanced troubleshoot main stator; if low troubleshoot exciter circuits.
Generator/PCC Control Isolation Procedure diagnostic

⚠ HIGH VOLTAGE. Touching uninsulated high voltage parts inside the control box can result in severe personal injury or death.

Tools: Voltmeter, Jumpers, 12 volt battery

  1. Throw the line circuit breaker OFF and shut down the set.
  2. Remove accessory box cover; remove plug P10 from A37 J10.
  3. Prepare to measure output voltage across generator terminals.
  4. Connect 12V battery jumpers to X (P10-6 red) and XX (P10-3 brown).
  5. Check polarity; incorrect polarity makes the test inconclusive.
  6. Start set and connect battery negative to the XX lead.
  7. Rated or higher balanced voltage means generator circuitry is OK.
  8. Unbalanced voltage: troubleshoot main stator; low voltage: exciter/field.
Ground Fault Relay Test diagnostic
  1. Verify that the N-G Fault Indicator on the GFR is not lit; if lit, the neutral-to-ground bonding jumper circuit is open.
  2. Move the control switch to the Run position.
  3. Press the TEST switch on the ground fault relay.
  4. Verify that the control panel warning message is displayed and the Fault Indicator (>I) on the GFR is lit.
  5. Reset the control panel fault, which also resets the ground fault relay.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
12 lead generator setsLoad wires are routed through the CTsReconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage).
6 lead generator setsGenerator output leads are routed through the CTsNon-reconnectable gensets (6 leads) have single secondary CTs (2 pins).
Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F)Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100).
Current transformers CT21-U load leads (A phase), CT22-V load leads (B phase), CT23-W load leads (C phase)CT secondary wire marked 1 to pin 1; wire marked 2/3 to pin 2 for high voltage gensets or pin 3 for low voltage gensetsCT dot must face toward the generator; CTs have dual secondaries (3 pins).
Generator load terminals stamped U, V, W and N (U=L1, V=L2, W=L3, N=L0)Stranded load wires bolted to generator reconnection terminal block or circuit breaker lugsAvailable generator output voltages and maximum current ratings are specified on the generator set nameplate; line-to-neutral is the lower voltage, line-to-line the higher. Reconnection diagram is located on the upper side cover of the control housing.
A (U)CT21U load leads (A phase)CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground.
B (V)CT22V load leads (B phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
C (W)CT23W load leads (C phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
110 V - 120 V L-N1Single phase, 2-wirePTC module jumper locations
190 V - 240 V L-L3Three phaseUse PTC module 0300-5382-01; 50/60 Hz
200 V - 240 V L-L1Single phase, 3-wirePTC module jumper locations
380 V - 600 V L-L3Three phaseUse PTC module 0300-5382-02; 50/60 Hz

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

Which generators use the Cummins/Onan NTA 855-G6 / NTA 855-G5 engine?

The Cummins/Onan NTA 855-G6 / NTA 855-G5 powers 1 generator set(s), including Cummins/Onan DFCE.

What is a common problem with the Cummins/Onan NTA 855-G6 / NTA 855-G5 engine?

A commonly reported issue on generators using the Cummins/Onan NTA 855-G6 / NTA 855-G5 is: UNDER FREQUENCY. Fix: Shutdown.