Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Controller | Detector, PowerCommand 3100 |
| Oil capacity | 36.0 L |
| Voltage options | 120/240 V, 208/416 V |
| Phase | 3-phase |
| Rated current | 50 A |
| Power factor | 0.8 |
| Circuit breaker | 75 A |
| Battery group | 8D |
| Battery cranking | 1400 CCA |
| Battery voltage | 24 V |
| Battery quantity | 2 |
| Coolant capacity | 49 L |
| Fuel tank | 100.0 L |
| Tank runtime | 8.33 hr |
Filters for the Cummins/Onan LTA10
6Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Oil filter | P550777 | Lube Filter, Spin-On Bypass | CUMMINS 3021658, CUMMINS 33004232, NAPA 1749, BALDWIN B7577 | FridayParts $43.56 |
| Oil filter | P551670 | Lube Filter, Spin-On Full Flow | CUMMINS 298670, CUMMINS 299670, NAPA 1970, CARBOCOL 0026 | FridayParts $26.68 |
| Fuel filter | P550105 | Fuel Filter, Spin-On Primary | CUMMINS 154700, CUMMINS 154710, NAPA 3109, NAPA 3405 | buy |
| Fuel / water separator | P558000 | Fuel Filter, Water Separator Spin-On Twist&Drain | CUMMINS 3308638, CUMMINS 3308683, NAPA 3405, NAPA 3693 | KuduParts $24.00 FridayParts $25.66 |
| Fuel / water separator | P550106 | Fuel Filter, Water Separator Spin-On | CUMMINS 154789, CUMMINS 156164, NAPA 3405, BALDWIN BF957-D | FridayParts $285.60 |
| Coolant filter | P554071 | Coolant Filter, Spin-On | CUMMINS 209604, CUMMINS 209606, NAPA 4071, WALGAHN-MOTORENTECHN 00811412 | FridayParts $397.60 |
Same engine, other brands
1 brandThe Cummins/Onan LTA10 in this set also powers 2 generator sets sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| AKSA | AC250, AC275 |
Maintenance & consumables
for the Cummins/Onan LTA10| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | — | ||||
| Fuel filter | — | 4 hr | |||
| Oil filter | — | 250 hr | |||
| Battery | Two 12V Group 8D batteries | — | 5060 hr | ||
| Belt | — | 3 hr | |||
| Coolant | 49.0 L | — | |||
| Coolant filter | — | 5060 hr | |||
| Oil | 36.0 L | — | 250 hr | ||
| Spark plug | — |
Service intervals
1| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Rupture basin leak detect switch | Test | 12 mo | Check once a year; in some areas weekly inspections may be required by safety code regulations |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
60| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Angular alignment T.I.R. limit | not more than .001 | in per inch of radius | center of shaft to indicator axis |
| Clearance | Angular alignment maximum T.I.R. | 0.001 | inch per inch of radius (center of shaft to indicator axis) | measuring deflection to bolt heads |
| Clearance | Float switch assembly float lift clearance below C-clip stop | 1/8 | inch (3 mm) | use a feeler gauge |
| Clearance | Generator-to-engine angular alignment (T.I.R.) | .001 in. per inch of radius (center of shaft to indicator axis), maximum | in | 750 kW gensets and larger |
| Gap | MPU sensor to flywheel ring gear tooth | back it out one quarter turn | turn | sensor threaded in until it just touches gear tooth |
| Other | AVR Droop setting | 5 | % at full load, 0 PF | |
| Other | AVR voltage regulation (load regulation) | approximately ±0.5 | % RMS | |
| Other | Angular alignment maximum T.I.R. | .001 inches per inch of radius | in/in | center of shaft to indicator axis |
| Other | Battery specific gravity (high ambient, above 95F/35C) | 1.225 | recommended to reduce electrolyte loss | |
| Other | Battery specific gravity (recharge threshold) | below 1.260 | ||
| Other | Battery specific gravity, fully charged | approximately 1.260 | specific gravity | at 80 F (27 C) |
| Other | Fuel lift height limit | 6 | feet | (1.8 meters) between fuel lift pump and bottom of dip tube |
| Other | GOV GAIN default value for paralleling applications | 70 | % | |
| Other | Maximum cranking voltage drop | 2 | volts | difference between battery and starter terminals while cranking |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal | 55 | Hz | reset 53 Hz |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal | 65 | Hz | reset 63 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal | 45 | Hz | reset 47 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal | 55 | Hz | reset 57 Hz |
| Other | Over/Under Voltage Sensor Module time delay | typically 25 percent, approximately 2.5 | seconds | |
| Other | Overcrank cranking limit | 75 | seconds | three 15-second cranking cycles with two 15-second rest periods |
| Other | Overcurrent shutdown threshold | 110% of rated | % of rated | PCC time/current calculation |
| Other | Overcurrent warning threshold | 110% of rated for 60 seconds | % of rated | generator output current |
| Other | Overload warning threshold | 105% of standby or 115% of prime | % of rating | three-phase power output; load dump after five seconds, warning after 60 seconds |
| Other | REG VHZ (underfrequency roll-off) adjustable range | 1 through 50; normal range 7 through 21 | ||
| Other | Short circuit shutdown threshold | 175% of rated | % of rated | generator output current |
| Other | Start delay adjustment range | 0 to 300 | seconds | |
| Other | Stop delay adjustment range | 0 to 600 | seconds | |
| Other | Under Frequency Roll Off (UFRO) knee point, 50 Hz units | 48 to 49 | Hz | |
| Other | Under Frequency Roll Off (UFRO) knee point, 60 Hz units | 58 to 59 | Hz | |
| Other | Under-frequency roll-off threshold (UFRO) | typically 59 Hz for 60 Hz applications and 49 Hz for 50 Hz applications | Hz | AVR UFRO pot preset |
| Other | Weak battery warning threshold | below 60% of nominal for two seconds | % of nominal | during starting |
| Pressure | Engine oil pressure - K19 normal | 50-70 | psi (345-482 kPa) | run mode |
| Pressure | Engine oil pressure - K38 normal | 45-65 | psi (310-448 kPa) | run mode |
| Pressure | Engine oil pressure - K50 normal | 50-70 | psi (345-482 kPa) | run mode |
| Pressure | Engine oil pressure - L10/M11 normal | 30-50 | psi (207-345 kPa) | run mode |
| Pressure | Engine oil pressure - NTA 855 normal | 35-50 | psi (241-345 kPa) | run mode |
| Pressure | Engine oil pressure - V28 normal | 50-90 | psi (345-620 kPa) | run mode |
| Pressure | Engine oil pressure shutdown limit - L10/M11 | 20 | psi (138 kPa) | run mode value |
| Pressure | Engine oil pressure shutdown limit - L10/M11 | 8 | psi (55 kPa) | idle mode value |
| Pressure | Engine oil pressure warning limit - L10/M11 | 12 | psi (83 kPa) | idle mode value |
| Pressure | Engine oil pressure warning limit - L10/M11 | 25 | psi (172 kPa) | run mode value |
| Pressure | K19 engine idle oil pressure | 20 | psi (138 kPa) | idle |
| Pressure | K19 engine normal oil pressure | 50-70 | psi (345-482 kPa) | normal run |
| Pressure | K19 normal oil pressure (run/idle) | 50-70 / 20 | psi (345-482 / 138 kPa) | NORM run / IDLE |
| Pressure | K19 oil pressure shutdown limit | 10 | psi (69 kPa) | idle mode |
| Pressure | K19 oil pressure shutdown limit | 35 | psi (241 kPa) | run mode |
| Pressure | K19 oil pressure shutdown/warning limits | shutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idle | psi (kPa) | |
| Pressure | K19 oil pressure warning limit | 15 | psi (103 kPa) | idle mode |
| Pressure | K19 oil pressure warning limit | 40 | psi (276 kPa) | run mode |
| Pressure | K38 engine idle oil pressure | 20 | psi (138 kPa) | idle |
| Pressure | K38 engine normal oil pressure | 45-65 | psi (310-448 kPa) | normal run |
| Pressure | K38 normal oil pressure (run/idle) | 45-65 / 20 | psi (310-448 / 138 kPa) | NORM run / IDLE |
| Pressure | K38 oil pressure shutdown limit | 10 | psi (69 kPa) | idle mode |
| Pressure | K38 oil pressure shutdown limit | 35 | psi (241 kPa) | run mode |
| Pressure | K38 oil pressure shutdown/warning limits | shutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idle | psi (kPa) | |
| Pressure | K38 oil pressure warning limit | 15 | psi (103 kPa) | idle mode |
| Pressure | K38 oil pressure warning limit | 40 | psi (276 kPa) | run mode |
| Pressure | K50 engine idle oil pressure | 20 | psi (138 kPa) | idle |
| Pressure | K50 engine normal oil pressure | 50-70 | psi (345-482 kPa) | normal run |
| Pressure | K50 normal oil pressure (run/idle) | 50-70 / 20 | psi (345-482 / 138 kPa) | NORM run / IDLE |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | soft water / E.G. / DCA mixture | Cooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist). | |||
| Fuel | Diesel | Day tank fuel transfer pump maintains reservoir of diesel fuel in the day tank. | |||
| Grease | Lithium based grease | Mobilux No. 2 or Shell Alvania R3 | 2.74 oz (81 ml) | Generator end bearing. Temperature range -22F to +248F (-30C to +120C). Grease should be equally divided between the bearing, bearing cap cavity, and bearing cartridge cavity. | |
| Grease | Lithium based grease, Mobilux No. 2 or Shell Alvania R3 | -30°C to 120°C | 2.74 oz (81 ml) | End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
61| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 101 | IDLE MODE | Indicates that the engine is operating in idle mode (governed at 800 RPM, generator build-up inhibited). | Warning | Remove ground from engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Turn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. Oil pressure limits are listed in Table 4-3. |
| 204 | OIL PRES SENDER | Indicates that the control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Set is not operating. Warning occurs when engine coolant temperature is 70° F (21° C) or lower. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary. | Warning | Reduce load if possible by turning off non-critical loads. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow 212-SHUTDOWN procedure. |
| 212 | HIGH COOLANT TEMP | Indicates engine has overheated (coolant temperature above 215° F (102° C) − standby or 207° F (97° C) − primary). | Shutdown | Allow engine to cool down completely. Check for obstructions to cooling airflow; check fan belt; check coolant mixture; check blower fan and circulation pumps on remote radiator installations. Reset control and restart. |
| 213 | COOLANT SENDER | Indicates that the resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender. Resistance should be 500 to 2k ohms. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Allow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Look for coolant leakage points and repair if necessary. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Shutdown | Allow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Reset control and restart after correcting problem. Shutdown will not occur if genset is in Idle mode (low coolant warning only). |
| 220 | MAG PICKUP | Indicates mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM on the digital display. |
| 221 | FAIL TO CRANK | Indicates possible fault with control or starting system. | Shutdown | Check fuse F3 on the Engine Interface board. Check for poor battery cable connections; clean battery cable terminals and tighten. Recharge or replace a discharged or defective battery. |
| 222 | OVERCRANK | Indicates possible fuel system problem. | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines. Check for dirty fuel filter and replace if necessary. Check for dirty or plugged air filter and replace if necessary. Reset the control and restart after correcting the problem. |
| 223 | OVERSPEED | Engine has exceeded normal operating speed (115% ±1% of nominal). | Shutdown | Check mechanical fuel linkage and actuator; check governor output module (A38) and digital board (A32). |
| 224 | FAIL TO SYNCHRONIZE | Generator set has not synchronized to the system bus within the allowable time frame. | Warning | Check governor system stability; adjust governing and synchronizer parameters; check fuel system. |
| 226 | FAIL TO CLOSE | Paralleling breaker has been given a signal to close, but has not closed properly. | Shutdown | Verify breaker charging mechanism; check close signal; verify auxiliary contact signals. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Check float level on battery charger if applicable (lower float level). Check engine DC alternator; replace if normal battery charging voltage is not obtained. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | Discharged or defective battery. See Warning message 230, LOW DC VOLTAGE. |
| 240 | LOW FUEL−DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 241 | LOW FUEL | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 250 | EEPROM ERROR | PCC memory error; data corruption of critical operating parameters. | Shutdown | Perform initial start setup procedure; replace digital board (A32) if fault repeats. |
| 251 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Perform adjustment and calibration procedures; replace digital board (A32) if fault repeats. |
| 252 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Verify selected values; repeat save operation; replace digital board (A32) if fault repeats. |
| 260 | CUSTOMER FAULT 1 | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 261 | GROUND FAULT | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 262 | RUPTURE BASIN | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 263 | HIGH GEN TEMP | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 270 | PHASE ROTATION | The phase relationship between the generator set and the system bus is not matched. | Shutdown | Verify genset phase rotation matches bus; verify control wiring to bus PT module. |
| 272 | FIRST START | PowerCommand control is not receiving a proper signal from the system master first start sensor. | Warning | Verify Master First Start Sensor and interconnection wiring. |
| 301 | HIGH AC VOLTAGE | One or more phase voltages exceeded 130% of nominal, or exceeded 110% of nominal for 10 seconds. | Shutdown | Check PCC, alternator, excitation circuit, and PT/CT module wiring. |
| 303 | LOW AC VOLTAGE | One or more phase voltages dropped below 85% of nominal for 10 seconds. | Shutdown | Check PMG/field wiring, rotating rectifier, load and connectors. |
| 313 | UNDER FREQUENCY | Indicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown, a Load Dump signal is initiated. | Shutdown | Check fuel supply, intake air supply and load. |
| 320 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 321 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated, and that a PCC time/current calculation has initiated an overcurrent shutdown. | Shutdown | Check load and load lead connections. |
| 322 | SHORT CIRCUIT | Indicates that generator output current has exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 330 | OVERLOAD | Indicates that three-phase power output exceeds 105% of standby (or 115% of prime) rating. After five seconds, the Load Dump output is activated. After 60 seconds, the OVERLOAD warning is activated. | Warning | Check load and load lead connections. |
| 335 | REVERSE POWER | Indicates improper CT or PT phasing. (Non-parallel units only.) | Shutdown | Check CT / PT wiring. Refer to CT Installation in Section 5. |
| 337 | LOSS OF EXCITATION | Alternator excitation system is improperly adjusted or has failed. | Shutdown | Check output voltage calibration, load sharing lines, and leading power factor loads. |
| FAULT 1 | Fault 1 (Red) | Engine shut down because of a customer-connected system fault; part of a 10 second time delay shutdown circuit. | Shutdown | Service as required by the customer-supplied fault indicating switches. |
| FAULT 2 | Fault 2 (Red) | Engine shut down because of a customer-connected system fault; part of a non-time delay shutdown circuit. | Shutdown | Service as required by the customer-supplied fault indicating switches. |
| GF | Ground Fault Alarm (Optional) | Ground fault relay monitors neutral to ground connection and line to neutral, activating a fault alarm when the connection is broken or a ground fault is sensed. | Warning | Clear fault condition by pushing the Run/Stop (Reset)/Remote switch to Reset (auto reset link set at factory). |
| HET | High Engine Temperature (Red) | Engine shut down because of excessively high engine coolant temperature (greater than 230 deg F). | Shutdown | Check coolant level and leaks; service cooling system; reset engine control. |
| HI ENG TEMP | High Engine Temperature | Engine shut down due to critically high coolant temperature (above 215F/102C). | Shutdown | |
| LET | Low Engine Temperature (Yellow) | Engine temperature is less than 70 deg F and the engine might not start. | Warning | Plug in, repair or install engine coolant and oil heaters. |
| LO FUEL | Low Fuel | Fuel supply is marginally low, if equipped (Detector-12). | Warning | |
| LO OIL PRES | Low Oil Pressure | Engine shut down due to critically low oil pressure (below 14 psi/97 kPa). | Shutdown | |
| LOP | Low Oil Pressure (Red) | Engine shut down because of excessively low engine oil pressure (less than 14 psi). | Shutdown | Check oil level and oil leaks; service lubricating system; reset engine control. |
| LOW ENG TEMP | Low Engine Temperature | Engine water jacket temperature is 70F/21C or lower; indicates possible inoperative coolant heater (Detector-12). | Warning | |
| LOW FUEL | Low Fuel (Yellow) | Fuel level in the supply tank has dropped below the reserve necessary to run the set at full load for the prescribed number of hours. | Warning | Fill the main fuel supply tank with the appropriate grade of fuel. |
| OC | Overcrank (Red) | Engine shut down because it did not start during the timed cranking period (approximately 75 seconds, including two rest periods). | Shutdown | Service the set as necessary; reset engine control. |
| OS | Overspeed (Red) | Engine shut down because of overspeed. | Shutdown | Adjust the Electronic Overspeed Module; check governor for binding; reset engine control. |
| OVERCRANK | Overcrank | Starter locked out because of excessive cranking time (limited to 75 seconds). | Shutdown | |
| OVERSPEED | Overspeed | Engine shut down because of excessive speed. | Shutdown | |
| PRE HI ENG TEMP | Pre-High Engine Temperature | Coolant temperature is marginally high (205F/97C or higher). | Warning | Attend to when generator set is shut down. |
| PRE LO OIL PRES | Pre-Low Oil Pressure | Engine oil pressure is marginally low (20 psi/138 kPa or less). | Warning | Attend to when generator set is shut down. |
| PRE-HET | Pre High Engine Temperature (Yellow) | Engine coolant temperature is abnormally high (greater than 220 deg F). | Warning | Shut down if possible or disconnect non-critical loads; service cooling system. |
| PRE-LOP | Pre Low Oil Pressure (Yellow) | Engine oil pressure is abnormally low (less than 20 psi). | Warning | Shut down if possible or disconnect non-critical loads; service lubricating system. |
| RUN | Run | Green lamp comes on when both primary and secondary starter circuits open after unit starts. | Info | |
| SWITCH OFF | Switch-off (Flashing Red) | The Run/Stop/Remote switch is in the Stop position, preventing remote automatic operation. | Info | Push the Run-Stop-Remote switch to Remote. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Aligning Generator with Engine (Angular Alignment) adjustment
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.
Tools: Dial indicator, Shims
- Disconnect the negative (-) battery cable(s) before beginning.
- Fasten a dial indicator to the generator shaft or cooling fan with the sensing point on the capscrew head or flat surface of the drive disc at the bolt circle diameter.
- Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
- Determine the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one revolution.
- Measure the distance from the center of the generator shaft to the indicator measuring point.
- Measure the distance from the generator side of the flex discs to the center of the generator mounting bolt.
- Compare the distances; multiply this ratio times one half the T.I.R. to approximate the amount of shims to remove or add.
Angular Alignment Procedure adjustment
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) before beginning.
Tools: Dial indicator, Wooden shims
- Disconnect the negative (-) battery cable(s) before beginning.
- Fasten a dial indicator to the generator shaft or cooling fan with sensing point on capscrew head or flat surface of drive disc at bolt circle diameter.
- Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
- Record maximum positive and negative dial indicator readings as the engine completes one revolution.
- T.I.R. equals the sum of the maximum positive and negative readings.
- Maximum T.I.R. should not be more than .001 inch for each inch of radius.
- Remove equal shims from under both generator mounting feet to lower the generator.
Angular Alignment Procedure (Generator to Engine) adjustment
⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.
⚠ Do not bar engine over by prying on fan blade.
Tools: dial indicator
- Disconnect the negative (-) battery cable(s) before beginning.
- Fasten a dial indicator to the generator shaft or cooling fan with sensing point resting on the drive disc capscrew head/flat surface at the bolt circle diameter.
- Bar the engine over in a clockwise rotation as viewed from the engine flywheel; do not allow it to roll back on compression at the end of travel of each reading.
- Record the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one engine revolution.
- Compare the measured T.I.R. to the maximum allowed (.001 in. per inch of radius from center of shaft to indicator axis); add or remove shims under the generator mounting feet to correct.
Axial Alignment Procedure (Generator to Engine) adjustment
Tools: dial indicator
- Fasten a dial indicator holding device to the skid base, engine block, or generator shell with the sensor point resting on the generator shaft hub.
- Bar the engine over in a clockwise rotation through a couple of rotations, recording indicator readings at eight equally spaced points around the shaft diameter to obtain axial T.I.R.
- Reduce the measured T.I.R. runout by one half if excessive vibration remains after angular alignment.
Governor Calibration Checks adjustment
Tools: Frequency meter or tachometer, Jumper wire
- Start the generator set.
- Adjust engine no-load speed to the desired allowable speed droop using the Run Speed potentiometer.
- With no load, turn GAIN clockwise slowly until engine speed oscillates.
- Reduce GAIN slowly counterclockwise until engine speed is stable.
- Upset the governor by momentarily shorting terminals 7 and 10 on the governor control.
- Apply and remove loads to check generator set response.
HC4-7 Axial Alignment Procedure adjustment
Tools: Dial indicator with magnetic base or clamp
- Check only when an objectionable vibration is present.
- Fasten dial indicator holding device to skid base, engine block, or generator shell with magnetic base or clamp.
- Position sensor point on the generator shaft hub.
- Bar the engine over in a clockwise rotation as viewed from engine flywheel through a couple of rotations.
- Record indicator readings in eight equally spaced points around the shaft diameter.
- Remove the capscrews connecting drive discs and flywheel and mark discs and flywheel.
- Rotate engine or generator so drive disc holes are repositioned 180 degrees from original location.
- Put capscrews back in and retorque. Recheck shaft alignment.
- If runout unchanged, rotate discs to 30, 60 or 90 degrees from original location.
- If T.I.R. does not improve, inspect flywheel pilot and drive disc runouts.
P7 Axial Alignment Procedure adjustment
- Check only when an objectionable vibration is present.
- Remove the capscrews connecting drive discs and flywheel.
- Mark the drive discs and flywheel with respect to each other.
- Rotate engine or generator so drive discs holes are repositioned two bolt holes from original location.
- Put capscrews back in and retorque. Recheck/record vibration levels.
- Repeat this test until drive disc holes are repositioned 180 degrees from original location.
- Review vibration data and position drive disc in lowest recorded level location.
UFRO Adjustments adjustment
⚠ Use an insulated handle screw driver to prevent electrical shock.
Tools: Insulated handle screwdriver, Frequency meter or tachometer
- Make a note of the no-load frequency.
- Determine roll-off frequency by turning the governor speed pot until the LED lights; if okay go to step 5.
- Adjust the governor speed pot to the proper roll-off frequency.
- Turn the UFRO pot until LED goes off, then slowly turn it back until the LED just goes on.
- Adjust the governor speed pot back to the initial frequency setting.
Voltage and Voltage Stability Adjustments adjustment
⚠ Touching uninsulated high voltage parts inside the control and power output boxes can result in severe personal injury or death.
Tools: Insulated handle screwdriver, AC voltmeter
- Use the control panel mounted voltage trimmer, if provided, for small voltage adjustments.
- Measure generator output voltage while running without load at nominal frequency.
- If trimmer is insufficient, lock it at midpoint.
- Turn the VOLTS pot fully counterclockwise and the STABILITY pot to its midpoint.
- If the red LED lights, refer to Jumper Reconnections and UFRO Adjustments.
- Turn the VOLTS pot clockwise until rated voltage is obtained.
- If voltage becomes unstable with a large load, turn the STABILITY pot clockwise until stable.
- Check and readjust the VOLTS pot each time the STABILITY pot is readjusted.
Float Switch Assembly Testing diagnostic
Tools: Ohmmeter, Feeler gauge
- Remove fuel pump control cover, disconnect wiring jack, and unscrew assembly from top of day tank.
- Hold assembly vertical and use ohmmeter to check continuity between each pair of colored leads; all readings should be zero.
- Lift each float in turn to 1/8 inch (3 mm) below the C-clip stop above it and test continuity; all readings should be infinity.
- Replace assembly if any switch is open in step 2 or does not open in step 3.
- Use pipe thread sealant when replacing assembly.
Generator/PCC Control Isolation Procedure diagnostic
⚠ HIGH VOLTAGE. Touching uninsulated high voltage parts inside the control box can result in severe personal injury or death.
Tools: Voltmeter, Jumpers, 12 volt battery
- Throw the line circuit breaker OFF and shut down the set.
- Remove accessory box cover; remove plug P10 from A37 J10.
- Prepare to measure output voltage across generator terminals.
- Connect 12V battery jumpers to X (P10-6 red) and XX (P10-3 brown).
- Check polarity; incorrect polarity makes the test inconclusive.
- Start set and connect battery negative to the XX lead.
- Rated or higher balanced voltage means generator circuitry is OK.
- Unbalanced voltage: troubleshoot main stator; low voltage: exciter/field.
Insulation Resistance (Megger) & Polarization Index (PI) Testing diagnostic
⚠ The windings of medium-voltage (601 through 15,000 volts) generator sets must be dry before the generator is operated.
Tools: Megger or insulation resistance meter, Grounding cluster, High voltage gloves
- Perform the Generator Set Grounding Procedure.
- Disconnect plug J10 from A37 and AC control leads 4,5,6,7,8.
- If RTD option installed, ground all six RTD temperature leads (18 leads).
- Perform Insulation Resistance Test and PI Test for desired windings.
- Megger test: apply voltage for up to one minute.
- PI test: apply voltage for ten minutes; record 1-minute and 10-minute readings.
- PI ratio of 2 or greater is good for new and in-service sets.
- Investigate and correct low readings before returning set to service.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12 lead generator sets | Load wires are routed through the CTs | Reconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage). | ||
| 6 lead generator sets | Generator output leads are routed through the CTs | Non-reconnectable gensets (6 leads) have single secondary CTs (2 pins). | ||
| Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F) | Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100). | |||
| A | CT21 – U load leads | A phase | CT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground. | |
| A (U) | Bus PT module TB1 A | bus A phase | Bus PT module A39. | |
| A (U) | CT21 | U load leads (A phase) | CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground. | |
| B | CT22 – V load leads | B phase | CT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground. | |
| B (V) | Bus PT module TB1 B | bus B phase | Bus PT module A39. | |
| B (V) | CT22 | V load leads (B phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. | |
| C | CT23 – W load leads | C phase | CT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground. | |
| C (W) | Bus PT module TB1 C | bus C phase | Bus PT module A39. | |
| C (W) | CT23 | W load leads (C phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. | |
| N | Bus PT module TB1 N | bus neutral | Bus PT module A39. | |
| high voltage genset | 12-lead CT secondary wire marked 2/3 to pin 2 | 2/3 | For high voltage gensets. | |
| low voltage genset | 12-lead CT secondary wire marked 2/3 to pin 3 | 2/3 | For low voltage gensets. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What engine is in the Cummins/Onan DFAA?
The Cummins/Onan DFAA is powered by the Cummins/Onan LTA10 engine.
What fuel does the Cummins/Onan DFAA use?
The Cummins/Onan DFAA runs on Diesel.
What is the oil capacity of the Cummins/Onan DFAA?
The Cummins/Onan LTA10 engine in the Cummins/Onan DFAA has an oil capacity of 36.0 liters.
How much coolant does the Cummins/Onan DFAA hold?
The Cummins/Onan DFAA cooling system holds 49 liters (12.9 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What size fuel tank does the Cummins/Onan DFAA have?
The Cummins/Onan DFAA has a 100 liter (26 US gallon) fuel tank, giving about 8.33 hours of runtime.
What voltages is the Cummins/Onan DFAA available in?
The Cummins/Onan DFAA is offered in 120/240 V, 208/416 V, 3-phase-phase.
What battery does the Cummins/Onan DFAA use?
The Cummins/Onan DFAA uses 2 batteryies, 24 V each, 1400 CCA, group 8D, per the manufacturer specification sheet.
Troubleshooting
6Symptoms & remedies
| Symptom | Cause | Remedy |
|---|---|---|
| Green RUN lamp lights following engine startup | Indicates all engine systems are normal. No corrective action required. | |
| PREHI ENGINE TEMP lamp lights. Engine continues to operate | Engine has begun to overheat and engine temperature has risen to approximately 215°F (102°C) or coolant level is low on optionally wired sets | If generator is powering non-critical and critical loads and cannot be shut down, reduce load if possible by turning off non-critical loads; check air inlets and outlets and remove any obstructions to airflow; if engine can be stopped, follow procedure in step 3 |
| HI ENG TEMP lamp lights. Engine shuts down | Engine has overheated (engine temperature has risen above 222°F/106°C) or coolant level is low | Allow engine to cool down completely before proceeding with the following checks: check coolant level and replenish if low, look for possible coolant leakage points and repair if necessary; check for obstructions to cooling airflow and correct as necessary; check for a slipping fan belt and tighten if loose; reset control and restart after locating and correcting problem; contact an authorized service center if none of the above |
| PRELO OIL PRES lamp lights. Engine continues to operate | Engine oil pressure has dropped to 20 psi (138 kPa) | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure; if engine can be stopped, follow procedures in step 5 |
| LO OIL PRES lamp lights. Engine shuts down | Engine oil pressure has dropped to 14 psi (97 kPa) | Check oil level, lines and filters; if oil system is OK but oil level is low, replenish; reset control and restart; contact an authorized service center if oil pressure is not in the range of 25 to 40 psi (172 to 275 kPa) |
| OVERCRANK lamp lights and engine stops cranking | Possible fuel system problem | Check for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required; check for dirty fuel filter and replace if necessary (see Maintenance section); check for dirty or plugged air filter and replace if necessary (see Maintenance section); reset the control and restart after correcting the problem; contact an authorized service center for service if none of the above |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan DFAA troubleshooting guide (98 entries) →
Parts
20| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 0300-4623-05 | DFAA (600V) | 1 | Current transformer | Amazon eBay |
| 0300-4623-06 | DFAB (600V) | 1 | Current transformer | Amazon eBay $153.95 |
| 0300-4623-07 | DFAC (600V) | 1 | Current transformer | Amazon eBay |
| 0300-4623-17 | DFAA BR (0-480V) | 1 | Current transformer | Amazon eBay $165.95 |
| 0300-4623-19 | DFAB BR (0-480V) | 1 | Current transformer | Amazon eBay |
| 0300-4623-21 | DFAC BR (0-480V) | 1 | Current transformer | Amazon eBay |
| 960-0167 | Battery, Group Number: 8D, CCA (minimum): 1400, Cold Soak® -40°F (-40°C) | 2 | Battery | Amazon eBay |
| A40-TB1-2 | SWITCHED B+ | Belt | Amazon eBay | |
| A40-TB1-4 | GROUND | Belt | Amazon eBay | |
| A40-TB1-7 | COMMON ALARM | Belt | Amazon eBay | |
| A40-TB1-8 | JUMPER WIRE | Belt | Amazon eBay | |
| ES1855s | TIME DELAY START/STOP MODULE | Time delay start stop module | Amazon eBay | |
| LF3000 | Lube, Spin-On | 1 | Oil filter | Amazon eBay $76.00 NAPA $66.59 |
| P1-3 | Amperemeter | 1 | Ammeter | Amazon eBay |
| W1859s | CRANKING POTENTIOMETER | Cranking potentiometer | Amazon eBay | |
| 500-2782c1 | RUNNING TIME METER | Service part / kit | Amazon eBay | |
| TB1-2 | Battery charging alternator terminal TB1-2 | 2 | Service part / kit | Amazon Amazon eBay eBay FridayParts $34.80 |
| TB1-8 | Jump TB1-8 to 10 Harness Relay #1 COM Blue N/O White / Blue | 1 | Service part / kit | Amazon eBay FridayParts $87.88 |
| TB1-9 | B+ INPUT | 1 | Service part / kit | Amazon eBay |
| TB21 | TERMINAL BLOCK | 1 | Service part / kit | Amazon Amazon Amazon eBay eBay eBay NAPA $224.81 FridayParts $57.30 |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 100% | 52.7 | 13.9 |
Available documents