| 101 | IDLE MODE | Indicates that the engine is operating in idle mode. Grounding the engine idle input inhibits generator build-up and governs the engine at 800 RPM. | Warning | Grounding the engine idle input inhibits generator build-up and governs at 800 RPM; removing ground returns the genset to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Pull the button out; move the Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Can only be reset at the PCC front panel. |
| 121 | SPEED SIGNAL LOST | Mag pickup speed indication is not being sensed. | Shutdown | Restart and check RPM on digital display; inspect MPU wires/connector pins; check for 3.5 to 15 VAC at MPU while cranking. |
| 135 | OIL PRESSURE SENSOR H | Engine oil pressure sender signal is shorted high. | Warning | Check sender/connectors/wires; verify fault simulation not enabled; check 0.5 to 4.5 VDC at P7-13 (OP OUT) and P7-17 (OP COM). |
| 141 | OIL PRESSURE SENSOR L | Engine oil pressure sender signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts/open circuits at P7-13, 17, 21. |
| 143 | PRE-LOW OIL PRES | Engine oil pressure dropped to an unacceptable level. | Warning | Check oil level, lines and filters; replenish if low; if powering critical loads wait until next shutdown period and follow code 415. |
| 144 | COOL SENSOR HIGH | Engine coolant temperature signal is shorted high. | Warning | Check sender/connectors/wires; check resistance between P7-30 (IH20) and P7-34 (IH20 COM). |
| 145 | COOL SENSOR LOW | Engine coolant temperature signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts at P7-30 and P7-34. |
| 146 | PRE-HIGH COOL TMP | Engine has begun to overheat (coolant temperature risen to an unacceptable level). | Warning | Reduce load; check air inlets/outlets and remove obstructions to airflow; if engine can be stopped follow code 151. |
| 151 | HIGH COOLANT TEMP | Engine has overheated (coolant temperature above the shutdown trip point). | Shutdown | Allow engine to cool; check coolant level; check airflow obstructions; check fan belt; check blower fan/remote radiator pumps; reset control and restart. |
| 197 | LOW COOLANT LEVEL | Engine coolant level has fallen below the warning trip point. | Warning | Allow engine to cool; check coolant level and replenish; look for leaks; reset control and restart. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow the 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. Oil pressure limits are listed in Table 4-3. |
| 204 | OIL PRESS SENDER | Indicates that the control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70°F (21°C) or lower, indicating the engine coolant heater is not operating or is not circulating coolant. | Warning | Check coolant heater power supply, fuse or disconnected heater cord; check for low coolant level and replenish; check for an open heater element by checking current draw of heater. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215°F (102°C) standby or 207°F (97°C) prime. | Warning | Reduce load if possible; check air inlets and outlets and remove any obstructions to airflow; if engine can be stopped, follow the 212-SHUTDOWN procedure. |
| 212 | OIL TEMP SENSOR H | Engine oil temperature signal is shorted high. | Warning | Check sender/connectors/wires; check resistance between P7-22 (OIL TEMP) and P7-26 (OIL TEMP COM). |
| 213 | OIL TEMP SENSOR L | Engine oil temperature signal is shorted low. | Warning | Check sender/connectors/wires; check shorts and resistance between P7-22 and P7-26. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Allow engine to cool; check coolant level in both radiator and coolant recovery bottle and replenish; look for coolant leakage points; reset control and restart. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. LOW COOLANT LVL Shutdown will not occur if genset is in Idle mode (low coolant warning only). | Shutdown | Allow engine to cool; check coolant level in both radiator and coolant recovery bottle and replenish; if radiator level is low and bottle level correct, check coolant bottle hose or radiator cap; reset control and restart. |
| 220 | MAG PICKUP | Indicates mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM on the digital display. Check MPU sender, wiring and adjustment. |
| 221 | FAIL TO CRANK | Indicates possible fault with control or starting system. | Shutdown | Check fuse F3 on the Engine Interface board; check for poor battery cable connections; recharge or replace a discharged or defective battery. |
| 222 | OVERCRANK | Indicates possible fuel system problem. | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines; check for dirty fuel filter and replace if necessary; check for dirty or plugged air filter and replace if necessary; reset the control and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed (115% ±1% of nominal). | Shutdown | Inspect the mechanical fuel linkage and repair or replace; check the EFC for binding or damage; monitor the PCC duty cycle display and replace A32 or A38 as indicated. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Check for discharged or defective battery; check the battery charger fuse; recharge or replace the battery; clean and tighten battery cable connections; check engine DC alternator; check battery charge voltage float level. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Check voltage float level on battery charger if applicable (lower float level); check engine DC alternator and replace if normal battery charging voltage is not obtained. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | Discharged or defective battery. See Warning message 230, LOW DC VOLTAGE. |
| 234 | OVERSPEED | Engine has exceeded normal operating speed. | Shutdown | Clear fault and restart genset; check fault threshold; monitor RPM; check electronic governor actuator. |
| 235 | LOW COOLANT LEVEL | Engine coolant level has fallen below the shutdown trip point. | Shutdown | Check coolant level and replenish; look for leaks; reset control and restart. |
| 240 | LOW FUEL-DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 241 | LOW FUEL | Indicates fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 250 | EEPROM ERROR | Indicates PCC memory error. Data corruption of critical operating parameters. | Shutdown | Perform the Initial Start Setup procedure and save; if the same EEPROM ERROR occurs, replace the digital board (A32). |
| 251 | EEPROM ERROR | Indicates PCC memory error. Data corruption of noncritical operating parameters. | Warning | Perform the adjustment procedures and save; if the same EEPROM ERROR occurs, perform the calibration procedures; if it still occurs, replace the digital board (A32). |
| 252 | EEPROM ERROR | Indicates PCC memory error. Data corruption of noncritical operating parameters. | Warning | Verify the values or choices selected and repeat the save operation; if the same EEPROM ERROR occurs, replace the digital board (A32). |
| 260 | CUSTOMER FAULT 1 | Customer defined input closed to ground; the nature of the fault is an optional customer selection which can be programmed to initiate a shutdown or a warning. Default message is editable. | Warning | Isolate the source of the false signal; disconnect the signal lead near the control and reset; if the message drops out there is a short to ground in the external wiring; if it remains replace A34. Customer fault messages are editable. |
| 261 | GROUND FAULT | Customer defined input closed to ground; the nature of the fault is an optional customer selection. Default message is editable. | Warning | Isolate the source of the false signal; check the corresponding customer interface board LED; disconnect the signal lead and reset the control; replace A34 or A32 as indicated. |
| 262 | RUPTURE BASIN / DAY TANK | Customer defined input closed to ground; the nature of the fault is an optional customer selection. Default message is editable. | Warning | Isolate the source of the false signal; check the corresponding customer interface board LED; disconnect the signal lead and reset the control; replace A34 or A32 as indicated. |
| 263 | HIGH GEN TEMP | Customer defined input closed to ground; the nature of the fault is an optional customer selection. Default message is editable. | Warning | Isolate the source of the false signal; check the corresponding customer interface board LED; disconnect the signal lead and reset the control; replace A34 or A32 as indicated. |
| 301 | HIGH AC VOLTAGE | Indicates that one or more of the phase voltages has exceeded 130% of nominal, or has exceeded 110% of nominal for 10 seconds. | Shutdown | Set the display to GEN VOLTS L-N and observe; determine if the output voltage the control sees is low or high; isolate to the PCC, alternator, PT/CT module (A36), customer interface board (A34), analog board (A33) or digital board (A32). |
| 303 | LOW AC VOLTAGE | Indicates that one or more of the phase voltages has dropped below 85% of nominal for 10 seconds. | Shutdown | Check and repair the PMG or field wiring; check rotating rectifier diodes; check the load and correct any overload; check connectors J8 and J9 on A36, J3 and J5 on A34, and J7 on A37; isolate to A33, A32, A37 or A31. |
| 313 | UNDER FREQUENCY | Indicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown, a Load Dump signal is initiated. | Shutdown | Check Initial Setup (set size); check load and correct any overload; check fuel supply, intake air supply and load; refer to the fault-finding table. |
| 320 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 321 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated, and that a PCC time/current calculation has initiated an overcurrent shutdown. | Shutdown | Check load and load lead connections. |
| 322 | SHORT CIRCUIT | Indicates that generator output current has exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 330 | OVERLOAD | Indicates that three-phase power output exceeds 105% of standby (or 115% of prime) rating. After five seconds, the Load Dump output is activated. After 60 seconds, the OVERLOAD warning is activated. | Warning | Check load and load lead connections. |
| 335 | REVERSE POWER | Indicates improper CT or PT phasing (non-parallel units only). | Shutdown | Check CT / PT wiring. Refer to CT Installation in Section 5. |
| 359 | FAIL TO START | Engine cranks but fails to start (possible fuel system problem). | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines; replace dirty fuel filter; replace dirty air filter; reset control and restart. |
| 415 | LOW OIL PRESSURE | Engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset control and restart. |
| 421 | OIL TEMP | Engine has begun to overheat (oil temperature above unacceptable level) (Optional). | Warning | Reduce load; check air inlets/outlets; if engine can be stopped follow code 151 and check engine oil level. |
| 441 | LOW BAT VOLTAGE | Battery voltage supply to the control approaching a low level. | Warning | Check battery charger fuse; recharge or replace battery; clean and tighten cable connections; check engine DC alternator. |
| 442 | HIGH BAT VOLTAGE | Battery voltage supply approaching a high level at which control damage can occur. | Warning | Check float level on battery charger; check battery wiring/calibration. |
| 1122 | Rated/Idle Trans | Rated/Idle transition | Info | |
| 1123 | SHUTDOWN AFTER BS | A shutdown fault occurred while Battle Short was enabled and transitioned from enabled to disabled. | Shutdown | Review Fault History and perform corrective action. |
| 1124 | DELAYED SHUTDOWN | A shutdown fault became active while the Delayed Shutdown feature was enabled. | Warning | Review Fault History and perform corrective action. |
| 1131 | BATTLE SHORT ACTIVE | Control is in Battle Short mode (bypasses several critical fault shutdowns). | Warning | None; used for genset operation during emergencies. |
| 1311 | Customer Input #1 | Customer input #1 (optional customer selection) | | Programmable (service tool): enable/disable input (default enable); status, warning or shutdown (default #1 = None); active closed or open (default closed [ground]); change display name up to 19 characters. |
| 1311, 1312, 1317, 1318 | CUSTOMER INPUT #1 - #4 | Optional customer-selected fault input is active. | | Disconnect signal lead from TB1 and reset the control; check external wiring/active input selection. |
| 1312 | Customer Input #2 | Customer input #2 (optional customer selection) | | Programmable (service tool): enable/disable input (default enable); status, warning or shutdown (default #2 = Warning); active closed or open (default closed [ground]); change display name. |
| 1313−1316 | Network Fault 1 thru 4 | Network fault 1 through 4 | | |
| 1317 | Customer Input #3 | Customer input #3 (optional customer selection) | | Programmable (service tool): enable/disable input; status, warning or shutdown; active closed or open; change display name. |
| 1318 | Customer Input #4 | Customer input #4 (optional customer selection) | | Programmable (service tool): enable/disable input; status, warning or shutdown; active closed or open; change display name. |
| 1334 | CRIT SCALER OR | Incorrect feature or calibration was entered into control. | Shutdown | Reload correct feature/calibration file. |
| 1335 | NONCRIT SCALER OR | Incorrect feature or calibration was entered into control. | Warning | Reload correct feature/calibration file. |
| 1337 | No Message | No message | Info | |
| 1416 | FAIL TO SHUTDOWN | Genset continues to run after receiving shutdown command (Battle Short feature enabled). | Warning | Check Battle Short feature setting. |
| 1417 | POWER DOWN ERROR | Controller cannot power down because of an unknown condition. | Warning | Check for possible battery drain. |
| 1433 | EMERGENCY STOP | Local Emergency Stop. | Shutdown | Pull the button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto. |
| 1434 | REMOTE E-STOP | Remote Emergency Stop. | Shutdown | See code 1433 to reset. |
| 1435 | LOW COOLANT TEMP | Engine coolant heater is not operating or not circulating coolant (coolant <=70 F [21 C]). | Warning | Check coolant heater power/fuse/cord; check coolant level; check heater element (10 to 60 ohms); check sensor. |
| 1438 | FAIL TO CRANK | Engine failed to crank after the PCC received a start signal. | Shutdown | Test for B+ at the starter; check fuse F3 (2 Amps); check K4 start pilot relay and starter circuitry; refer to code 121. |
| 1442 | WEAK BATTERY | During cranking battery voltage at or below weak battery trip point. | Warning | Recharge or replace battery; check electrolyte level and connections; check harness. |
| 1443 | BATTERY FAILED | Dead battery - engine will not start. | Shutdown | See code 1438 instructions. |
| 1444 | KW OVERLOAD | Generator output power exceeded 105% of genset rating (3 sec at 110% of rated). | Warning | Check load and load lead connections; check CTs and CT connections. |
| 1445 | SHORT CIRCUIT | Generator output current exceeded 175% of rated. | Shutdown | Check load and load lead connections (fault may not reset for several minutes). |
| 1446 | HIGH AC VOLTAGE | Phase voltage exceeded 130% of nominal, or 110% of nominal for 10 seconds. | Shutdown | Check fault simulation; clear fault and restart; refer to Generator/Base Board Isolation Procedure. |
| 1447 | LOW AC VOLTAGE | Phase voltage dropped below 85% of nominal for 10 seconds. | Shutdown | Check load; reconnect per reconnection diagram; check PMG/field wiring; check P8-21/P8-22 shunt connections. |
| 1448 | UNDER FREQUENCY | Engine speed dropped below 90% of nominal for 10 seconds. | Shutdown | Check fuel supply, intake air supply and load; check P8 connections. |
| 1449 | OVER FREQUENCY | Frequency is 10% above base frequency for 20 seconds. | Warning | Check fuel or air delivery problem; repair P7/P8 connections. |
| 1452 | GEN CB NOT CLOSE | Genset circuit breaker (S2) failed to close when PTC enabled. | Warning | Refer to Section 5. |
| 1453 | GEN CB NOT OPEN | Genset circuit breaker (S2) failed to open when PTC enabled. | Warning | Refer to Section 5. |