Service parts for the DQFAC
Grouped by system, with how many of each the parts manual calls for.
Air intake
1 requiredFuel system
1 requiredOil system
1 requiredBelts
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
| Fuel | diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 900 kW |
| Standby kVA | 1125 |
| Prime power | 818 kW |
| Emissions | Tier 2 |
| Controller | PowerCommand, PowerCommand 3.3 |
| Oil capacity | 154.0 L |
| Alternator | Stamford/AvK HC6K (frame S6L1D-F4) (4-pole, Class Class H on low and medium voltage, Class F on high voltage insulation) |
| Voltage options | 120/208 V, 139/240 V, 220/380 V, 230/400 V, 240/416 V, 277/480 V, 347/600 V |
| Phase | 3 |
| Power factor | 0.8 |
| Battery cranking | 1800 CCA |
| Battery voltage | 24 V |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 4287×1990×2355 mm |
| Dry weight | 7335 kg |
| Wet weight | 7598 kg |
| Sound level | 120.3 dBA @ 1 m |
Engine
| Oil capacity | 154.0 L |
|---|---|
| Coolant capacity | 202.5 L |
| Displacement | 30.5 L |
| Aspiration | Turbocharged and low temperature after-cooled |
| Rated speed | 1800 rpm |
Same engine, other brands
1 brandThe Cummins/Onan QST30-G5 in this set also powers 5 generator sets sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| Katolight | D1000FJZ4, D1000FNZ4, D1000FPZ4, D1000FRZ4, D1000FSZ4 |
Maintenance & consumables
for the Cummins/Onan QST30-G5| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Dry replaceable element | D041-2 | eBay | ||
| Fuel filter | 30 micron Racor ® fuel filter system | — | 2000 hr | ||
| Fuel filter | Water/Fuel Filter Wrench | 3376807 | Amazon eBay | ||
| Oil filter | (4) Cummins Filtration LF9001 | 3825142 | 2000 hr | Amazon eBay | |
| Battery | 24 VDC | — | 2000 hr | ||
| Belt | Belt | ST669 | 500 hr | Amazon eBay $204.59 | |
| Coolant | 167.0 L | — | 6000 hr | ||
| Coolant filter | Not specified | — | 1500 hr | ||
| Oil | 154.0 L | — | 2000 hr | ||
| Spark plug | Not specified | — | 1000 hr |
Service intervals
40| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Air cleaner restriction indicator | Check | 8 hr | Where fitted; if indicator shows red replace elements and reset indicator | |
| Battery connections | Check | 8 hr | Connections secure; battery area free from tools and other items | |
| Bedframe/enclosure fluid containment | Drain | 8 hr | Where fitted | |
| Control panel operation | Test | 8 hr | System performs a control panel test on initial activation | |
| Engine oil level | Check | 8 hr | Check with engine stationary; top up to engine specifications | |
| Exhaust components, hardware and condensation trap | Check | 8 hr | Drain condensation into a suitable container | |
| Fuel level in tank | Check | 8 hr | Add fuel if low; full tank reduces condensation | |
| Fuel lines and hoses | Check | 8 hr | Check before starting and again with generator set running | |
| Fuel system primary filter/water separator | Drain | 8 hr | Drain one cup or more to remove water and sediment | |
| Generator set enclosure | Check | 8 hr | Walk-around inspection; no inlets/outlets covered | |
| Radiator coolant level (water jacket & LTA) | Check | 8 hr | Top up with Cummins recommended coolant mix | |
| Charge alternator | Check | 50 hr | Check visually and audibly with generator set running | |
| Coolant lines and radiator hoses | Check | 50 hr | 6 mo | Visually check for leaks, worn or damaged hoses |
| Cooling fan blades | Inspect | 50 hr | Visually through guarding for wear or damage | |
| Crankcase breather tube/collector | Drain | 50 hr | Check for condensed oil | |
| Drive belt condition and tension | Check | 50 hr | Visually check for evidence of wear or slippage | |
| Engine coolant heater | Check | 50 hr | Check heater has power and is running | |
| Battery | Check | 100 hr | 1 mo | Check electrolyte level at least every month or 100 hours, whichever occurs first |
| Air cleaner housing | Clean | 250 hr | 6 mo | |
| Air intake system leaks | Inspect | 250 hr | 6 mo | Visually and audibly inspect for signs of wear or damage |
| All hardware (fittings, clamps, fasteners) | Check | 250 hr | 6 mo | |
| Anti-freeze and DCA concentration | Check | 250 hr | 6 mo | |
| Battery electrolyte level | Check | 250 hr | 6 mo | |
| Electrical connections (battery, starter motor and alternator) | Check | 250 hr | 6 mo | |
| Emergency Stop Button operation | Test | 250 hr | 6 mo | With generator set running press the Emergency Stop button; check all systems before resetting |
| Engine ground | Check | 250 hr | 6 mo | Clean as necessary |
| Engine mounts | Check | 250 hr | 6 mo | |
| Engine oil heater | Check | 250 hr | 6 mo | |
| Engine steam clean | Clean | 250 hr | 6 mo | |
| Fuel system secondary filter | Replace | 250 hr | 6 mo | |
| Lubricating oil and filters | Replace | 250 hr | 6 mo | |
| Radiator air flow | Check | 250 hr | 6 mo | Inspect radiator through guarding for blockage and debris |
| Starting motor | Check | 250 hr | 6 mo | |
| Turbochargers | Check | 250 hr | 6 mo | |
| Water separator element | Replace | 250 hr | 6 mo | |
| Aftercooler core | Check | 1500 hr | 12 mo | |
| Bearings (fan/idler) | Lubricate | 1500 hr | 12 mo | Re-grease bearings |
| Coolant filter | Change | 1500 hr | 12 mo | |
| Coolant heater | Check | 1500 hr | 12 mo | |
| Fan drive idler arm and fan belt tensioner | Check | 1500 hr | 12 mo |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
38| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | Battery electrolyte specific gravity (fully charged, corrected) | 1.260 | SG | at 25 °C (77 °F) |
| Other | Battery electrolyte specific gravity - charge battery if reading is below | 1.215 | SG | at 25 °C (77 °F) |
| Other | Compression ratio | 14.7:1 | ||
| Other | Frequency regulation | Isochronous | ||
| Other | Generator set operating incline limit | +/- 2.5 | degrees | |
| Other | Governor regulation class | ISO 8528 Part 1 Class G3 | ||
| Other | Specific gravity at end of charge (ambient frequently above 32 °C / 90 °F) | 1.240 - 1.260 | SG | |
| Other | Specific gravity at end of charge (ambient normally below 32 °C / 90 °F) | 1.270 - 1.290 | SG | |
| Other | Specific gravity correction | 0.007 | SG points | subtract for every 10 °C (18 °F) above 25 °C (77 °F); add for every 10 °C below |
| Other | Specific gravity for filling new cells (ambient frequently above 32 °C / 90 °F) | 1.240 | SG | |
| Other | Specific gravity for filling new cells (ambient normally below 32 °C / 90 °F) | 1.270 | SG | |
| Other | Water quality - Calcium, Magnesium (Hardness) maximum level | 170 | ppm (as CaCO3) | |
| Other | Water quality - Chloride maximum level | 40 | ppm (as Cl) | |
| Other | Water quality - Sulfate maximum level | 100 | ppm (as SO4) | |
| Pressure | Fuel transfer pump maximum inlet restriction capability | 16 | inch Hg | |
| Pressure | Maximum air cleaner restriction | 6.2 | kPa | |
| Pressure | Maximum cooling air flow static restriction | 0.12 | kPa | |
| Pressure | Maximum exhaust back pressure | 6.8 | kPa | |
| Pressure | Maximum fuel inlet restriction | 27 | kPa | |
| Pressure | Maximum fuel return line restriction | 67.5 | kPa | |
| Speed | Overspeed limit | 2100 ±50 | rpm | |
| Speed | Rated speed | 1800 | rpm | |
| Temperature | Battery temperature fault (fault code 2263) threshold | 55 | °C (131 °F) | |
| Temperature | Coolant temperature before adding coolant to engine | 50 | °C (122 °F) | cool to below this value |
| Temperature | Electrolyte temperature limit for boost charge | 43 | °C (109 °F) | |
| Temperature | Electrolyte temperature limit for boost charge (tropical climates) | 49 | °C (120 °F) | |
| Temperature | Maximum fuel inlet temperature | 66 | °C | |
| Temperature | Maximum jacket water outlet temp (remote radiator cooling) | 104 | °C | |
| Temperature | Maximum jacket water outlet temp (remote radiator) | 104 | °C | |
| Temperature | Maximum permissible electrolyte temperature during charge | 45 | °C (113 °F) | |
| Temperature | Minimum engine water jacket coolant temperature maintained by coolant heaters (standby life safety) | 32 | °C (90 °F) | |
| Temperature | Temperature below which engine cold sensing logic initiates a warning (Low Coolant Temp) | 21 | °C (70 °F) | |
| Torque | AC distribution panel 100 A main breaker lugs (#4 to 2/0 conductors, AL or CU) | 5.6 | Nm (50 in-lbs) | |
| Torque | AC distribution panel ground bar (#1 to 2/0 conductors, AL or CU) | 23 | Nm (17 ft-lbs) | |
| Torque | AC distribution panel neutral bus (#5 to 300KCMIL conductors, AL or CU) | 28.4 | Nm (21 ft-lbs) | |
| Voltage | Battery volts limit for boost charge (12 V battery) | 15 | V | |
| Voltage | Exposure to energized power circuits - significant risk threshold | 50 VAC or 75 VDC | V | |
| Voltage | Voltage regulation, no load to full load | ± 0.5 | % |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | 50/50 mixture of fully formulated coolant and DCA4 (or equivalent); premixed fully formulated coolant or 50/50 mix of high-quality distilled/deionized water and fully formulated concentrated antifreeze | Cummins Engineering Standard 14603; Fleetguard coolants containing DCA4 recommended | Either ethylene glycol or propylene glycol; fill to bottom of filler neck | ||
| Engine oil | High-quality multi-viscosity lubricating oil such as Cummins Premium Blue or equivalent | Consult authorized distributor for correct lubricating oil specifications for operating conditions | |||
| Fuel | ASTM No. 2D diesel fuel, minimum Cetane number 40 | ASTM No. 2D; BS 2869:2010+A1:2011 acceptable alternative | Cetane numbers higher than 40 often needed at high altitudes or extremely low ambient temperatures | ||
| Fuel | Number 2 diesel | Direct injection; automatic electric fuel shutoff; triple element 10 micron spin-on fuel filters with water separator | |||
| Fuel | Number 2 diesel fuel | Direct injection | |||
| Fuel | number 2 diesel fuel | Direct injection |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
72| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 111 | Internal ECM Failure | Internal ECM Failure | Shutdown | |
| 1131 | Battle Short Active | Control is in Battle Short mode (bypasses several fault shutdowns). | Warning | If possible, investigate any fault codes being bypassed. |
| 115 | Eng Crank Sensor Error | Eng Crank Sensor Error | Shutdown | |
| 121 | Engine Magnetic Crankshaft Speed or Position Lost One of Two Signals | Engine Magnetic Crankshaft Speed or Position Lost One of Two Signals | Warning | |
| 1312 | Configurable Input # 2 | Optional customer configurable input fault. | Info | Check the Input # requirements and correct if possible. |
| 1317 | Configurable Input # 13 | Optional customer configurable input fault. | Info | Check the Input # requirements and correct if possible. |
| 1318 | Configurable Input # 14 | Optional customer configurable input fault. | Info | Check the Input # requirements and correct if possible. |
| 141 | Low Oil Rifle 1 Pressure | Low Oil Rifle 1 Pressure | Warning | See code 415 procedure. |
| 1416 | Fail To Shutdown | Records a bypassed shutdown fault while the generator set was in Battle Short mode. | Warning | Troubleshoot the shutdown fault causing the bypassed shutdown. |
| 142 | Oil Overpressure | Oil Overpressure | Warning | |
| 143 | Low Oil Rifle Pressure | Engine oil pressure has dropped below the warning trip point. | Warning | If powering critical loads and cannot be shut down, wait until next shutdown period, then follow fault code 415 procedure. |
| 1433 | Local Emergency Stop | A local Emergency Stop has been activated. | Shutdown | De-activate the Emergency Stop button; press Stop; press Reset; select desired operating mode; check the Emergency Stop button works correctly. |
| 1434 | Remote Emergency Stop | A remote Emergency Stop has been activated. | Shutdown | De-activate the Emergency Stop button; press Stop; press Reset; select desired operating mode; check the Emergency Stop button works correctly. |
| 1435 | Low Coolant Temperature | Engine coolant heater is not operating or not circulating coolant; occurs when coolant temperature is 21 °C (70 °F) or lower. | Warning | Check coolant heater power supply, blown fuse or disconnected heater cable; look for coolant leaks; check coolant level and replenish. |
| 1438 | Fail To Crank | Possible fault with the control, speed sensing, or starting system. | Shutdown | See code 441 for corrective action; ensure the Emergency Stop button is disengaged. |
| 1439 | Low Day Tank Fuel Switch | Day tank fuel supply is running low. | Warning | Look for possible fuel leaks and repair; check for low fuel level and replenish. |
| 144 | High Coolant 1 Temp | Engine has begun to overheat; coolant temperature has risen to an unacceptable level. | Warning | Review fault code 151 correction list for possible causes. |
| 1441 | Low Fuel Level | Fuel level has gone below the threshold setting for low fuel level against the time setting. | Warning | Look for possible fuel leaks and repair; check for low fuel level and replenish. |
| 1442 | Weak Battery | During cranking battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time. | Warning | See code 441. |
| 1443 | Dead Battery | During cranking battery voltage dropped below the operating voltage of the control, resetting the control; after three consecutive resets this code becomes active. | Shutdown | See code 441. |
| 1444 | Overload | Overload | Warning | |
| 1445 | Short Circuit | Short Circuit | Shutdown | |
| 1446 | High AC Voltage | High AC Voltage | Shutdown | |
| 1447 | Low AC Voltage | Low AC Voltage | Shutdown | |
| 1448 | Under Frequency | Generator set frequency has dropped below 90% of nominal for approximately ten seconds. | Shutdown | Check the fuel supply; check the air intake supply; check the load and correct any overload. |
| 1449 | Over Frequency | Generator set frequency has exceeded the Over Frequency threshold for the set time parameter. | Warning | Check the fuel supply; check the air intake supply; check the load and correct any overload. |
| 145 | Low Coolant 1 Temp | Engine coolant temperature is below the low coolant temperature warning threshold. | Warning | If powering critical loads and cannot be shut down, wait until next shutdown period, then follow fault code 1435 procedure. |
| 1452 | Genset Breaker Fail To Close | Genset Breaker Fail To Close | Warning | |
| 1453 | Genset Breaker Fail To Open | Genset Breaker Fail To Open | Warning | |
| 1455 | Utility Breaker Position Contact | Utility Breaker Position Contact | Warning | |
| 1456 | Bus Out Of Synchronizer Range | Bus Out Of Synchronizer Range | Warning | |
| 1457 | Fail To Synchronize | Fail To Synchronize | Warning | |
| 1459 | Reverse Power | Reverse Power | Shutdown | |
| 146 | Pre-High Engine Coolant Temperature | Engine operating near cooling system capacity. | Warning | Review fault code 151 correction list for possible causes. |
| 1461 | Loss of Field (Reverse kVAR) | Loss of Field (Reverse kVAR) | Shutdown | |
| 1463 | Not In Auto | Not In Auto | Info | |
| 1465 | Ready To Load | Ready To Load | Info | |
| 1469 | Speed/Hz Mismatch | Speed/Hz Mismatch | Shutdown | |
| 1471 | Over Current | Over Current | Warning | |
| 1472 | Over Current | Over Current | Shutdown | |
| 151 | High Coolant Temp | Engine has overheated (coolant temperature above shutdown trip point or coolant level is low). | Shutdown | Allow engine to cool completely. Check for coolant leaks and level; check for cooling airflow obstructions; check fan belt; check blower fan and circulation pumps; reset control and restart. |
| 155 | High Intake Manf 1 Temp | Engine has overheated (intake manifold temperature above shutdown trip point). | Shutdown | Review fault code 151 correction list for possible causes. |
| 1852 | Pre-High H2O In Fuel | Water in the fuel is above normal and has reached the warning trip point. | Warning | Check fuel in tank (local or remote); drain and re-fill if necessary. |
| 196 | Low Coolant 1 Level | Engine coolant level has fallen below the trip point. | Warning | Check for coolant leaks and level; replenish if low; reset the control and restart. |
| 197 | Low Coolant Level | Engine coolant level has fallen below the trip point. | Warning | Check for coolant leaks and level; replenish if low; reset the control and restart. |
| 1999 | Maximum Parallel Time | Maximum Parallel Time | Warning | |
| 228 | Low Coolant Pressure | Low Coolant Pressure | Shutdown | |
| 2335 | AC Voltage Sensing Lost (Excitation Fault) | Excitation Fault (Loss of Voltage Sense) | Shutdown | Critical shutdown fault - suspends Battle Short mode. |
| 234 | Crankshaft Speed High | Overspeed | Shutdown | Critical shutdown fault - suspends Battle Short mode. |
| 2342 | Too Long In Idle | Too Long In Idle | Warning | |
| 235 | Low Coolant Level | Low Coolant Level input is active and threshold response is set to Shutdown. | Shutdown | Allow engine to cool completely; check for coolant leaks and level; replenish if low; reset control and restart. |
| 236 | Both Engine Speed Signals Lost | Both Engine Speed Signals Lost | Shutdown | |
| 253 | Oil Level Low | Oil Level Low | Shutdown | |
| 27 | Low AC voltage shutdown | Voltage on any phase dropped below preset value; 50-95% of reference, 2-20 s delay, default 85% for 10 s | Shutdown | |
| 2977 | Low Coolant 2 Level | Engine coolant level in the second radiator has fallen below the trip point. | Warning | Look for possible coolant leakage points and repair; check coolant level and replenish if low; reset the control and restart. |
| 32 | Reverse power shutdown | Adjustment range 5-20% of Standby kW rating, delay 1-15 s; default 10%, 3 s | Shutdown | |
| 3416 | Start System Fault - Condition Exists | Start System Fault - Condition Exists | Warning | Refer to fault codes 359 and 1438. |
| 359 | Fail to Start | Possible fault with the control or starting system (engine cranks but fails to start). | Shutdown | Check fuel tank, leaks or blocked fuel lines; check/replace dirty fuel filter; check/replace dirty air filter; clean and tighten battery cable connections; recharge or replace battery; reset control and restart. |
| 415 | Low Oil Rifle Press | Engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset the control and restart. |
| 427 | CAN Data Link Degraded | Communication between the engine control (ECM) and the PCC is severed. | Warning | Ensure the E-Stop button is not active; reset the Local/Remote Emergency Stop. |
| 441 | Low Battery 1 Voltage | Battery voltage is below 24 VDC and approaching a low level at which unpredictable operation occurs. | Warning | Clean battery terminals and tighten connections; check electrolyte level, top up and recharge; recharge or replace discharged/defective battery. |
| 442 | High Battery 1 Voltage | Battery voltage to the control approaching a high level exceeding 32 VDC. | Warning | Clean battery terminals and tighten connections; check battery charge float level and lower if applicable. |
| 46 | Negative sequence overcurrent warning | Protects generator from damage due to excessive three-phase load imbalance | Warning | |
| 488 | High Intake Manf 1 Temp | Engine has overheated (intake manifold temperature above shutdown trip point). | Warning | Review fault code 151 correction list for possible causes. |
| 51 | Overcurrent warning/shutdown | Thermal damage curve with instantaneous trip level based on current transformer ratio and application power rating | Shutdown | |
| 51G | Ground fault overcurrent | Detects ground fault via external ground fault relay contact input or external CT measurement | Shutdown | |
| 59 | High AC voltage shutdown | Output voltage on any phase exceeds preset values; 105-125% of nominal, 0.1-10 s delay, default 110% for 10 s | Shutdown | |
| 611 | Engine Hot Shut Down | An engine hot shutdown has occurred (cooldown timers bypassed). | Warning | Generator set should run at 10% or less load for three minutes before engine shutdown; avoid hot shutdown. |
| 649 | Engine Oil Change Needed | Engine Oil Change Needed | Info | |
| 781 | CAN Data Link Failure | Communication between the engine control (ECM) and the PowerCommand 3.3 control has been severed. | Shutdown | Ensure the E-Stop button is not active; reset the Local/Remote Emergency Stop. |
| 81o | Over frequency shutdown/warning | Genset operating at a potentially damaging frequency; 2-10 Hz above nominal, 1-20 s delay, default 6 Hz 20 s disabled | Warning | |
| 81u | Under frequency shutdown | Genset output frequency cannot be maintained; 2-10 Hz below reference, 5-20 s delay, default 6 Hz 10 s | Shutdown |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Battery Charging (Bench / Boost) maintenance
⚠ Batteries should not be left on Boost Charge for extended periods.
- Do not put a filled battery into storage without first giving the battery a commissioning charge.
- Give batteries a further charge every six months at the normal initial charge rate until voltage ceases to rise.
- If the charger has a Boost Charge switch, select Boost at intervals detailed by the battery manufacturer (normally every 6 months).
- Reduce the charge rate to normal bench rate if electrolyte temperature exceeds 43 °C (109 °F) or battery volts reach 15 V (12 V battery).
- At the end of charging, check electrolyte levels and restore if necessary with electrolyte of correct SG.
- Replace vent caps.
Coolant Level - Check maintenance
⚠ Do not open the pressure cap while the engine is running; let the engine cool down and relieve pressure first.
⚠ Do not add cold coolant to a hot engine; allow engine to cool to below 50 °C (122 °F).
- Isolate the generator set to prevent accidental starting whilst filling the radiator.
- Slowly remove the radiator filler cap.
- Coolant level should be level with the bottom of the filler neck.
- Slowly fill with a 50/50 mixture of fully formulated coolant and DCA4 until level reaches bottom of filler neck.
- Replace the radiator cap securely - push down and twist clockwise until cap lip hits stop flange.
- Start the generator set and check for leaks.
Drive Belt - Inspection maintenance
- Visually inspect the belt through the guarding.
- Check for intersecting cracks (longitudinal cracks intersecting transverse cracks are NOT acceptable).
- Check for frays or pieces of material missing.
- Check for glazed or cracked side walls and uneven sidewall wear.
- Visually inspect sheaves through the guarding for damaged or worn grooves, broken flanges and missing material.
- Contact your authorized distributor to have worn belts or sheaves replaced.
Engine Oil Level Check maintenance
⚠ Do not check oil while the generator set is operating; crankcase pressure can blow out hot oil.
Tools: Lint free cloth, Funnel
- Remove the dipstick and wipe clean with a lint free cloth.
- Fully replace the dipstick.
- Remove the dipstick and check oil level against High and Low marks.
- Top up to the High mark if necessary with the correct grade of oil.
- Remove filler cap, place lint free cloth beneath filler neck, use a funnel to pour oil.
- Check oil level with dipstick; do not overfill.
- Replace dipstick and oil filler cap.
- Remove cloth, start engine, idle five minutes, switch off and wait five minutes.
- Check oil level; repeat if oil needs to be added.
Fuel Filter Element Removal maintenance
⚠ Diesel fuel is a fire and explosion hazard; do not permit any open flame or igniter near the fuel system.
Tools: Collar/vent cap wrench
- Shut down the engine.
- Close the fuel supply shutoff valve.
- Place a suitable container under the filter to be replaced.
- Use the collar/vent cap wrench to open the vent cap to break the air lock in the filter.
- Open the drain valve and allow fuel level to drain below the collar.
- Close the drain valve.
- Loosen the collar with the collar/vent cap wrench.
- Remove the clear cover, filter spring, fuel filter element, and o-ring.
- Remove the sealing grommet.
- Discard the o-ring and grommet.
Fuel/Water Separator - Drain (Spin on Type) maintenance
⚠ Diesel fuel is a fire and explosion hazard; do not permit any open flame or igniter near the fuel system.
- Shut off the engine.
- Wait 1 minute to remove any pressure in the fuel line.
- Place a suitable container under the fuel filter.
- Turn the valve clockwise four complete turns until the valve drops down one inch; drain until clear fuel is visible.
- When clear fuel flows, push the valve up and turn counterclockwise to close drain valve.
- Before starting the engine, remove the container and clean up any fuel spillage.
- Start the engine and check for leaks.
Heavy Duty Air Cleaner Element Installation maintenance
- Inspect all seals before installing new air cleaner elements.
- Install the Secondary inner air cleaner element first; secure using the inner wing nut with sealing washers.
- Install the Primary outer air cleaner element.
- Install the end cap and secure using the outer wing nut with sealing washers.
- Check for any leaks in the air intake system.
Heavy Duty Air Cleaner Element Removal maintenance
⚠ Cummins does not recommend cleaning paper-type air cleaner elements.
- Before disassembly, wipe dirt from the cover and upper portion of the air cleaner.
- Remove the outer wing nut and the end cap; sealing washers will need to be re-used.
- Remove the Primary outer air cleaner element.
- Remove the inner wing nut and remove the Secondary air cleaner element; sealing washers will need to be re-used.
Immobilizing for Safe Working maintenance
⚠ Accidental or remote starting can cause severe personal injury or death.
Tools: Insulated wrench
- Press the Off mode switch on the operator panel to shut down the generator set.
- Press the Emergency Stop button to prevent starting regardless of start signal source.
- Thoroughly ventilate the plant room before disconnecting any leads.
- Isolate and lock off the supply to the heater, where fitted.
- Isolate and lock off the supply to the battery charger, where fitted.
- Isolate the fuel supply to the engine.
- Using an insulated wrench, disconnect the negative (-) cable first on the starting and control batteries.
- Fit warning notices at each point to indicate Maintenance in Progress.
Normal Duty Air Cleaner Element Installation maintenance
- Secure the new air cleaner using the 2 air cleaner housing clamps.
- Install the coupler and secure the clamp to the intake tube.
- Check for any leaks in the air intake system.
Normal Duty Air Cleaner Element Removal maintenance
⚠ Holes, loose-end seals, dented sealing surfaces, corrosion of pipes and other damage require immediate element replacement.
- Before disassembly, wipe dirt from the cover and upper portion of the air cleaner.
- Note that normal duty air cleaners do not have serviceable filter elements; the entire cleaner is replaced.
- Remove the clamp securing the intake coupler to the air cleaner and slide the coupler off.
- Loosen or remove the 2 clamps securing the air cleaner.
- Remove the air cleaner from the generator set.
Oil Fill maintenance
⚠ Before carrying out any maintenance, isolate all supplies and disconnect the battery.
- Complete lock out procedure to ensure safe working environment.
- Refer to Engine Operation & Maintenance Manual for correct oil grade.
- Fill the engine to the correct level with clean engine oil.
- Check oil level on dipstick; level must be on the high (H) mark. Do not overfill.
- Return the generator set to the proper operating conditions.
- Operate the generator set at idle speed and check for leaks.
- Shut down the generator set.
- Wait approximately 5 minutes to allow oil to drain from upper parts of engine.
- Rectify any leaks; check the oil level; add oil as necessary to reach H mark.
- Dispose of waste material in accordance with local regulations.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 120/208 | 3 | Wye | 12/6 | Winding 311/312 |
| 120/208-139/240 | 3 | 12-lead | 12 | Temp rise 125/105 °C; ADS-312; feature B252 |
| 120/240 | 3 | Delta | 12/6 | Winding 311/312 |
| 127/220 | 3 | Wye | 12/6 | Winding 311/312 |
| 133/230 | 3 | Wye | 12/6 | Winding 311/312 |
| 139/240 | 3 | Wye | 12/6 | Winding 311/312 |
| 210/380-277/480 | 3 | Wye, 3-phase | 6 (12 optional) | ADS-331; feature B284 |
| 220/380-277/480 | 3 | Wye, 3-phase | 6 | ADS-330; feature B282/B283 |
| 240/416 | 3 | Wye | 12/6 | Winding 311/312 |
| 240/416-277/480 | 3 | 12-lead | 12 | Temp rise 125/105 °C; ADS-312; feature B252 |
| 254/440 | 3 | Wye | 12/6 | Winding 311/312 |
| 266/460 | 3 | Wye | 12/6 | Winding 311/312 |
| 277/480 | 3 | Wye, 3-phase | 6 (12 optional) | ADS-311; feature B276; max surge 3866 kVA / 1018 kW |
| 277/480 | 3 | Wye, 4 wire | 12/6 | Winding 311/312; feature code R002-2 |
| 347/600 | 3 | 3-phase | 6 | ADS-311 / ADS-312 / ADS-330; features B300/B301/B604 |
| 347/600 | 3 | Wye | 6 | Winding 07 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the Cummins/Onan DQFAC?
The Cummins/Onan DQFAC is rated 900 kW standby (1125.0 kVA).
What engine does the Cummins/Onan DQFAC use?
The Cummins/Onan DQFAC is powered by the Cummins/Onan QST30-G5 engine.
What kind of fuel does the Cummins/Onan DQFAC run on?
The Cummins/Onan DQFAC runs on diesel.
What is the oil capacity of the Cummins/Onan DQFAC?
The Cummins/Onan QST30-G5 engine in the Cummins/Onan DQFAC has an oil capacity of 154.0 liters.
What is the cooling system capacity of the Cummins/Onan DQFAC?
The Cummins/Onan DQFAC cooling system holds 202.5 liters (53.5 US gallons) for the engine, per the manufacturer specification sheet.
What is the continuous rating of the Cummins/Onan DQFAC?
The Cummins/Onan DQFAC is rated 818 kW prime (1023 kVA), against 900 kW standby.
What is the sound level of the Cummins/Onan DQFAC?
The Cummins/Onan DQFAC is rated at 120.3 dBA at 1 m, per the manufacturer specification sheet.
How much does the Cummins/Onan DQFAC weigh?
The Cummins/Onan DQFAC has a dry weight of 7335 kg (16170 lb).
What voltage does the Cummins/Onan DQFAC produce?
The Cummins/Onan DQFAC is offered in 120/208 V, 139/240 V, 220/380 V, 230/400 V, 240/416 V, 277/480 V, 3-phase.
What battery does the Cummins/Onan DQFAC use?
The Cummins/Onan DQFAC uses 24 V each, 1800 CCA, per the manufacturer specification sheet.
What alternator does the Cummins/Onan DQFAC use?
The Cummins/Onan DQFAC uses a Stamford/AvK HC6K (frame S6L1D-F4) alternator. It has 4 poles. Insulation class Class H on low and medium voltage, Class F on high voltage.
What oil filter fits the Cummins/Onan DQFAC?
The Cummins/Onan DQFAC uses oil filter part number 3825142.
What fuel filter does the Cummins/Onan DQFAC use?
The Cummins/Onan DQFAC uses fuel filter part number 3376807.
What air filter does the Cummins/Onan DQFAC use?
The Cummins/Onan DQFAC uses air filter part number D041-2.
Troubleshooting
6Symptoms & remedies
| Symptom | Remedy |
|---|---|
| Battle short mode | If enabled and the battle short switch is active, some shutdown faults will be bypassed. However, emergency stop shutdowns and other critical faults are not bypassed. |
| Derate | The derate function reduces output power of the genset in response to a fault condition. Commands will be issued to reduce load via contact closures or ModBus if on an isolated bus, and by lowering base load kW to target kW if in utility parallel mode. |
| Emergency stop | Annunciated whenever either emergency stop signal is received from an external switch. |
| Low and high battery voltage warning | Indicates status of the battery charging system (failure) by continuously monitoring battery voltage. |
| Weak battery warning | The control system will test the battery each time the genset is signaled to start and indicate a warning if the battery indicates impending failure. |
| Fail to start (overcrank) shutdown | The control system will indicate a fault if the genset fails to start by the completion of the engine crack sequence. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan DQFAC troubleshooting guide (36 entries) →
Parts
250Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 181.3 | 47.9 | |
| Prime | 25% | 64.0 | 16.9 |
| Prime | 50% | 122.8 | 32.4 |
| Prime | 75% | 181.5 | 48.0 |
| Prime | 100% | 240.3 | 63.5 |
| Standby | 199.5 | 52.7 | |
| Standby | 25% | 70.6 | 18.7 |
| Standby | 50% | 137.8 | 36.4 |
| Standby | 75% | 205.1 | 54.2 |
| Standby | 100% | 272.3 | 71.9 |
Available documents