HomeEnginesCummins/Onan 6BT5.9 G1

Cummins/Onan 6BT5.9 G1 Engine

The Cummins/Onan 6BT5.9 G1 is a 5.9 L 6-cylinder turbocharged engine rated at 1500 rpm, producing up to 83 kW. It powers generator sets from Cummins/Onan, including the 76 DGDA, C100 D5, C80 D5 and C90 D5. It holds 17.3 L (4.6 gal) of oil and 25 L (6.6 gal) of coolant.

Also known as: Cummins 6BT5.9 G1

Part of the Cummins/Onan 6BT5.9 engine family — 5 variants share parts & fitment.

5.9 L
Displacement
6
Cylinders
1500 rpm
Rated speed
83 kW
Gross power

Engine specifications

Oil capacity17.3 L
Coolant capacity25.0 L
Displacement5.9 L
Cylinders6
AspirationTurbocharged
Rated speed1500 rpm
Gross power83 kW

Common problems

15
  • The starter will disengage after a specified period of time and the control will indicate an overcrank fault
    Fix: Place the Run-Stop-Remote switch in the STOP position and momentarily depress the Reset switch. Wait two minutes for the Starter motor to cool and then repeat the starting procedure
  • The fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run. FAULT 1 or FAULT 2
  • SWITCH OFF lamp flashes.
    Fix: Indicates Run-Stop-Remote switch is in the Stop position which will prevent automatic Starting. Moving the Run-Stop-Remote switch to the Remote position will stop the lamp flashing and enable automatic starting.
  • PRELO OIL PRES lamp lights. Engine continues to operate.
    Fix: Indicates engine oil pressure has dropped to 20 psi (138 kPa). If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure. If engine can be stopped, follow procedure in step 5.
  • PREHI ENGINE TEMP lamp lights. Engine continues to operate.
    Fix: Indicates engine has begun to overheat and engine temperature has risen to approximately 220° F (105° C). If generator is powering non-critical and critical loads, and cannot be shut down, use the following: a. Reduce load if possible by turning off non-Critical loads. b. Check air inlets and outlets and remove any obstructions to airflow. c. Open doors or windows in generator area to increase ventilation. If engine can be stopped, follow procedure in step 3.
  • OVERCRANK lamp lights and engine stops cranking.
    Fix: Indicates possible fuel system problem. a. Check for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required. Engine runs, shuts down, and LO OIL PRES lamp lights. b. Check for dirty fuel filter and replace if necessary (see MAINTENANCE section). c. Check for dirty or plugged air filter and replace if necessary (see MAINTENANCE section). d. Refer to step 5. e. Reset the control and restart after correcting the problem. Contact your distributor for service if none of the above applies.
  • No AC output voltage.
    Fix: Voltage regulator is inoperative. Refer to Initial Start and Checks, and Adjustments sections of your Installation Manual for voltage check and adjustment procedures. Contact your distributor if voltage build-up is still a problem.
  • LOOIL PRES lamp lights. Engine shuts down.
    Fix: Indicates engine oil pressure has dropped to 14 psi (97 kPa). Check oil level, replenish as necessary. Check oil lines and filters for leaks, repair as required. Reset control and restart. Contact your distributor if oil pressure is not in the range of 35 to 55 psi (241 to 379 kPa).
  • LOFUEL lamp lights. Engine continues to run.
    Fix: Indicates diesel fuel supply is running low. Check fuel supply and replenish as required.
  • LOENG TEMP lamp lights. Set is in standby mode but is not operating.
    Fix: Lamp lights when engine coolant temperature is 70° F (21° C) or lower. Since the lamp goes out after the engine warms up, there should be no cause for alarm if it remains lighted during initial generator Set operation. Or is not circulating coolant. Check for the following conditions: a. Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required. b. Check for low coolant level and replenish. if required. Look for possible coolant leakage points and repair as required. c. Contact your distributor if none of the above applies.
  • LO FUEL lamp lights. Engine shuts down and LO OIL PRES lamp lights.
    Fix: Indicates engine has run out of fuel. Check fuel level and replenish as required.
  • HI ENG TEMP lamp lights. Engine shuts down.
    Fix: Indicates engine has overheated (engine temperature has risen above 230° F/110° C) or coolant level is low (sets with coolant level sensor). Allow engine to cool down completely before proceeding with the following checks: a. Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check for a slipping fan belt, tighten if loose. d. Reset control and restart after locating and correcting problem. Contact your distributor if none of the above applies.
  • Green RUN lamp lights following engine Start-up.
    Fix: Indicates all engine systems are normal. No corrective action required.
  • Green RUN lamp does not light following engine start-up.
    Fix: Indicates possible Start/Disconnect relay failure. Contact your distributor for assistance.
  • Fault lamp lights but no fault exists. Engine gauges show oil pressure, engine temperature, and frequency (speed) are within normal limits.
    Cause: The monitor board or a sensor may be at fault.
    Fix: Contact your distributor for service.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan 6BT5.9 G1.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter0140-3550 Amazon eBay
Fuel filterFS3345 Amazon eBay
Oil filterLF1251 Amazon eBay
Battery
Belt
Coolant34.0 L
Oil16.0 L
Spark plug

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Parts cataloged across the Cummins/Onan 6BT5.9 family

23
Part #DescriptionCategory
982-0200Air Filterair_filter
3824469fuel pump gear pullerfuel_pump
DM-3801372Gasket Set - 6BT 5.9gasket
FP-6B59PREM6B/6BT5.9 In-Frame Kit w/upper gasket set & oil pan gasketgasket
FP-6B59PREML6B/6BT5.9 In-Frame Kit w/upper gasket set & oil pan gasket (late)gasket
FP-IFK6B59PREM6B/6BT5.9 In-Frame Kit w/upper gasket set & oil pan gasketgasket
FP-IFK6B59PREML6B/6BT5.9 In-Frame Kit w/upper gasket set & oil pan gasket (late)gasket
3822509injector pullerinjector
3823276injector bore brushinjector
DM-3029551Fuel Injector - 6BT 5.9injector
LF3349Lube, Full-Flow Spin-Onoil_filter
3377259bosch timing tool (ve)other_service
960-0627Cother_service
965-0520Cooling Fanother_service
DM-3802010Main Bearing Set Standard - 4BT 3.9, 6BT 5.9, 6CT 8.3other_service
FP-33569706B/6BT5.9 In-Frame Kit (contains FP-3802160 Piston Kit)other_service
FP-33569716B/6BT5.9 In-Frame Kit (contains FP-3802248 Piston Kit)other_service
TB1-7B+ OUTPUTother_service
DM-3805401Oil Pump - 6BT 5.9pump
DM-3805403Water Pump - 4BT 3.9, 6BT 5.9pump
S103Selector switchswitch
TB1-6Control box terminal (TB1-6)terminal
DM-3015282Thermostat 180F - 4BT 3.9, 6BT 5.9thermostat

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan 6BT5.9 G1?

The Cummins/Onan 6BT5.9 G1 engine has an oil capacity of 17.3 liters.

What is the displacement of the Cummins/Onan 6BT5.9 G1?

The Cummins/Onan 6BT5.9 G1 has a displacement of 5.9 liters with 6 cylinders.

Which generators use the Cummins/Onan 6BT5.9 G1 engine?

The Cummins/Onan 6BT5.9 G1 powers 6 generator set(s), including Cummins/Onan 76 DGDA, Cummins/Onan C100 D5, Cummins/Onan C80 D5, Cummins/Onan C90 D5, Cummins/Onan DTDA.

What is a common problem with the Cummins/Onan 6BT5.9 G1 engine?

A commonly reported issue on generators using the Cummins/Onan 6BT5.9 G1 is: The starter will disengage after a specified period of time and the control will indicate an overcrank fault. Fix: Place the Run-Stop-Remote switch in the STOP position and momentarily depress the Reset switch. Wait two minutes for the Starter motor to cool and then repeat the starting procedure.