Home›Engines›Cummins/Onan 4B3.9-G2

Cummins/Onan 4B3.9-G2 Engine

The Cummins/Onan 4B3.9-G2 is a 3.9 L 4-cylinder naturally aspirated engine rated at 1800 rpm, producing up to 50.7 kW. It powers generator sets from Cummins/Onan, including the C40 D6, C45D5 and DGBB. It holds 10.9 L (2.9 gal) of oil and 16.9 L (4.5 gal) of coolant.

Also known as: Cummins 4B3.9-G2

Part of the Cummins/Onan 4B3.9 engine family — 5 variants share parts & fitment.

3.9 L
Displacement
4
Cylinders
1800 rpm
Rated speed
50 kW
Gross power

Engine specifications

Oil capacity10.9 L
Coolant capacity16.9 L
Displacement3.9 L
Cylinders4
AspirationNaturally aspirated
Rated speed1800 rpm
Gross power50 kW

Common problems

15
  • Engine cranks but will not start
    Cause: Empty fuel tank, fuel leaks, or plugged fuel lines
    Fix: Correct as required
  • Low Battery Voltage — Battery voltage is low 441
    Cause: Damaged battery cable connections
    Fix: Inspect the battery cable connections for loose connections and/or corrosion, and repair as necessary
  • Excitation Fault (Loss of AC Sense) — The control has lost voltage sensing or has lost zero cross sensing 2335
    Cause: Incorrect configuration
    Fix: Make sure that values for the Low of AC Voltage Threshold (85%) and Low of AC Voltage Time Delay (10 seconds) are correct in calibration
  • Engine Oil Pressure Low (Shutdown) — Engine oil pressure is below the low oil pressure shutdown threshold (35 psig) 415
    Cause: Lubricating oil level is low
    Fix: Check the oil level. Add or drain oil, if necessary
  • Over Current 1471
  • Low Coolant Level 197
    Cause: Engine coolant level has fallen below the warning trip point
    Fix: If generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure; if engine can be stopped, follow code 235 procedure.
  • Engine Is Difficult to Start or Does Not Start
    Cause: Battery voltage is low, interrupted, or open
    Fix: Check the battery connections, unswitched battery supply circuit, and fuses
  • Low Coolant Level (Warning or Shutdown) — This fault is used when an optional coolant level sensor is installed. The nature of the fault is an optional customer selection 1317
    Cause: Low coolant
    Fix: Stop the engine and allow the engine to cool down; Visually inspect and verify that the engine coolant is at the appropriate level; If the coolant level is too low, add coolant per specifications
  • Engine Noise Is Excessive
    Cause: Lubrication issue(s)
    Fix: Check the oil level and fill the system to the specified level if lubricating oil level is below specification; check the oil pressure if lubricating oil pressure is below specification; analyze the oil if lubricating oil is thin or diluted
  • Engine Experiences Low Power, Poor Acceleration, or Poor Response
    Cause: Excessive load
    Fix: Ensure that the load on the generator set does not exceed the generator set kW rating; revisit the generator set sizing process to ensure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system
  • Unstable Voltage (With Load)
    Cause: Engine governing unstable
    Fix: Refer to the engine service manual (if applicable) or E-Controls service manual
  • Poor Voltage Regulation (With Load)
    Cause: Unbalanced load
    Fix: Check voltage and load current on all phases; if unbalanced, redistribute the load more evenly across the phases
  • Poor Engine Transient Response
    Cause: Excessive loads
    Fix: Make sure that the load on the generator set does not exceed the generator set KW rating; re-visit the generator set sizing process to make sure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system
  • Low Voltage (With Load)
    Cause: Under frequency roll-off protection activated
    Fix: Under frequency roll-off protection is activated, indicating excessive load; check that under frequency roll-off set point and slope are correct; load on generator is in excess of rated, ensure that the load on the generator set does not exceed the generator kW rating; revisit the generator set sizing process to ensure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system
  • Low Fuel (Warning or Shutdown) — This fault is used when an optional low fuel level switch is installed. The nature of the fault is an optional customer selection 1318
    Cause: Low fuel level
    Fix: Add the manufacturer's prescribed fuel

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan 4B3.9-G2.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter—
Fuel filter—
Oil filterSingle spin-on canister, full flow—695 hr
BatterySet mounted starting battery.—
Belt—
Coolant17.3 liters—
Oil10.9 liters—
Spark plug—

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

40
ItemActionHoursMonthsNotes
Charge air pipingCheck50 hrDaily or after 8 hours
Coolant levelCheck8 hrDaily or after 8 hours
Exhaust systemInspect8 hrVisually and audibly inspect the exhaust system daily for leaks per the maintenance schedule; check for corrosion, obstruction, and leaks every time you start the generator set and every eight hours when you run it continuously
Fuel Filter(s)Drain8 hrDrain 1 cup or more of fuel to remove water and sediment. Refer to engine operation and maintenance manual for procedure.
Fuel Tanks (water and sediment)Drain8 hrDrain 1 cup or more of fuel to remove water and sediment.
Fuel levelCheck8 hrDaily or after 8 hours
General genset inspectionInspect8 hrDaily or after 8 hours. Check for oil, fuel, cooling and exhaust system leaks; check exhaust audibly and visually with set running.
Inspect GensetCheck8 hrCheck for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually with set running and repair any leaks immediately.
Oil LevelCheck8 hrKeep oil level near the dipstick high mark without overfilling.
Air cleaner restriction indicatorCheck24 hrIf service indicator shows red, replace air cleaner elements and reset indicator.
Coolant level of radiator(s)Check24 hrTop up with Cummins recommended coolant mix if low.
Engine oil levelCheck24 hrTop up with recommended oil if low.
Fuel level in fuel tankCheck24 hrRefill as required.
Fuel lines and hosesCheck24 hrCheck for leaks, worn or damaged hoses.
Generator set enclosureInspect24 hrWalk-around; ensure no inlets/outlets covered.
Operator panel operationCheck24 hrCheck display; replace component if not functioning.
Air CleanerClean50 hrClean if required. Perform more often in dusty conditions.
Air cleaner (clean if required)Clean50 hrWeekly or after 50 hours; perform more often in dusty conditions
Air intake system for leaksInspect50 hrVisually inspect; check audibly when running.
Battery charging systemCheck50 hrWeekly or after 50 hours
Battery connectionsCheck50 hrVerify connections are secure.
Charge alternatorCheck50 hrCheck visually and audibly when running.
Coolant heaterCheck50 hrWeekly or after 50 hours
Coolant lines and radiator hosesCheck50 hrCheck for leaks, wear, and cracks.
Cooling fan bladesInspect50 hrVisually inspect through guarding.
Crankcase OilDrain50 hrFirst service — Break-in: drain and replace the crankcase oil after the first 50 hours of operation on new generator sets.
Drive belt condition and tensionCheck50 hrCheck for wear or slippage.
Exhaust components and hardwareCheck50 hrVisually inspect; check audibly when running.
Exhaust condensate trapDrain50 hrWeekly or after 50 hours
Radiator air flowInspect50 hrCheck for blockage, debris, wear or damage.
Water and sediment from fuel tankDrain50 hrWeekly or after 50 hours; drain 1 cup or more of fuel to remove water and sediment
Radiator hoses for wear and cracksInspect100 hrMonthly or after 100 hours
Starting batteriesCheck100 hrMonthly or after 100 hours
Battery electrolyte levelCheck200 hrCheck at least every 200 hours of operation
Engine oil and filtersReplace200 hrFirst service — After the initial 50 hour interval and every 200 hours thereafter (footnote 3).
Anti-freeze and DCA ConcentrationCheck250 hr3 moRefer to engine operation and maintenance manual.
Crankcase oil and filterChange250 hr12 moRefer to Cummins Engine Operation and Maintenance Manual. Standby applications: change every 12 months or 250 hours, whichever comes first.
Drive Belt TensionCheck250 hr3 moVisually check belt for evidence of wear or slippage. Replace if hard or brittle. Refer to engine operation and maintenance manual.
Fuel FiltersChange250 hr3 moRefer to engine operation and maintenance manual.
Governor AdjustmentCheck250 hr3 mo

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceFloat switch lift below C-clip stop1/8inch (3 mm)
ClearanceOverspeed switch magnet-to-fly arm air gap (minimum)0.005inches (0.13 mm)
GapMPU sensor tip to ring gear teeth clearance0.5 - 0.6mm
GapMechanical overspeed switch air gap between magnet and fly arm (replace switch if less)0.005inches (0.13 mm)
OtherAFLEX-H (shake table test datum)<=3.200gAC156, tri-axial, 5% damping SRS
OtherAFLEX-V (shake table test datum)<=1.333gAC156, tri-axial, 5% damping SRS
OtherARIG-H (shake table test datum)<=2.400gAC156, tri-axial, 5% damping SRS
OtherARIG-V (shake table test datum)<=0.533gAC156, tri-axial, 5% damping SRS
OtherAVR DROOP preset at factoryfive percent droop at full load and zero power factor
OtherBattery electrolyte corrected specific gravity (fully charged)1.260electrolyte temperature corrected
OtherBattery electrolyte specific gravity, fully charged (corrected)1.260corrected to 80 °F (27 °C)
OtherBattery recharge threshold specific gravity1.215
OtherBattery specific gravity temperature correctionfour gravity points (0.004) for every ten degrees above 80 F (27 C)
OtherBattery specific gravity, fully chargedapproximately 1.260at 80°F (27°C)
OtherCycle crank crank and rest time7 to 20seconds
OtherCycle crank number of cycles3, 4, or 5
OtherECM fuse F1 (starter solenoid circuit)20amps
OtherECM fuse F2 (fuel solenoid circuit)20amps
OtherECM fuse F3 (continuous B+ to remote circuits)15amps
OtherECM fuse F4 (ECM circuits)5amps
OtherECM fuse F5 (engine gauge circuits)5amps
OtherFlywheel teeth (Teeth Pulses Per Revolution)110PCC setting
OtherFrequency adjustment range±5%%genset running
OtherFuse A31-F1 (control B+)5AmpEngine Interface board
OtherFuse A31-F3 (auxiliary B+)5AmpEngine Interface board; panel lights, run and start relays
OtherFuse A38-F1 (Network B+)10AmpGovernor Output Module
OtherFuse A38-F2 (Switched B+)10AmpGovernor Output Module
OtherFuse A38-F3 (Governor B+)10AmpGovernor Output Module
OtherFuse TB-Bat F1 (Customer B+)20AmpEngine Harness Assembly
OtherGOV RAMP adjustment range0 through 10seconds
OtherGlow plug preheat time5glow plug calibration
OtherGlow plug total glow plug time60glow plug calibration
OtherGovernor droop adjustment rangewithin 5percent of nominal frequency (3 Hz for 60Hz sets, 2.5 Hz for 50Hz sets)
OtherGround snow load limit30psfFor indoor (covered) and outdoor (exposed) installation
OtherHorizontal design seismic coefficient (z/h = 0.0)1.440gCertified seismic design level, IBC Importance IP <= 1.5, Soil Classes A-E, Risk Categories I-IV, Design Categories A-F, SDS <= 2.000 g
OtherLow oil pressure / high engine temperature fault time delayabout 10secondsfollowing starter disconnect and inhibited during cranking
OtherOvercrank limit (Sentinel)60seconds
OtherOvercrank option limit (Detector)75seconds
OtherOverspeed warning range 60 Hz sets2000 to 2200RPM
OtherREG VHZ adjustment range1 through 50 (normal range 7 through 21)
OtherResponse jumper setting - 90 to 550 kWB to C
OtherResponse jumper setting - over 550 kWA to B
OtherResponse jumper setting - under 90 kWA to C
OtherSDS (g) at z/h=1 for C10 D6 - C60 D62.0gCertified SDS, z/h = 1
OtherSDS (g) at z/h=1 for C50 D6C - C125 D6C2.5gCertified SDS, z/h = 1
OtherSetup/calibration menu access code574
OtherSpeed/frequency mismatch threshold2.0HzPCC setting
OtherSpeed/frequency mismatch threshold time1.5secondsPCC setting
OtherStandard cycle cranking (Detector)three 15-second cranking cycles with two 15-second rest periods
OtherStart delay adjustment range0 to 300secondsremote starting in Auto mode
OtherStop delay adjustment range0 to 600secondsremote stopping in Auto mode
OtherTrailer brake shoe adjustment back-off10clicks
OtherTrailer surge brake actuator stroke length (service brakes if exceeds)1inch (25 mm)
OtherUnder-frequency roll-off (UFRO) threshold, 50 Hz applications49Hz
OtherUnder-frequency roll-off (UFRO) threshold, 60 Hz applications59Hz
OtherVoltage adjustment range±5%%genset running
OtherZPA-H (shake table test datum)<=2.160gAC156, tri-axial, 5% damping SRS
OtherZPA-V (shake table test datum)<=0.480gAC156, tri-axial, 5% damping SRS
PressureEngine oil pressure (normal)30 to 65psi (207 to 449 kPa)at normal operating temperature
PressureEngine oil pressure range (low oil pressure troubleshooting)25 to 65psi (172 to 449 kPa)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolantsoft water/E.G./DCA mixtureInstallation review checklist item: cooling system must be filled with soft water/E.G./DCA mixture.
Coolant50/50 coolant solution (50% pure water and 50% ethylene glycol)
Coolant50/50 coolant solution (50% water / 50% ethylene glycol)
Coolant50/50 mix of water and antifreezeBalanced coolant mixture of water, antifreeze and coolant additivesDrain and replace the mixture every 6 months or after 500 hours of operation. Do not add cold coolant to a hot engine; allow engine to cool below 120 F (50 C) before adding coolant.
Engine oilRefer to Cummins engine Operation and Maintenance Manual for lubricating oil classificationGensets are shipped with oil added.
Engine oil15W407.9 L (8.35 qt)Refer to the Engine Operator Manual
FuelASTM number 2D fuelASTM 2D
FuelDieselDo not use zinc coated or copper fuel lines with diesel fuel.
FuelNumber 2 diesel
FueldieselDo not use zinc coated or copper fuel lines with diesel fuel.
GreaseDow Corning silicone heat sink compound type 340 or similarApply to base of replacement diode only
Hydraulic oilDOT-3Trailer master cylinder reservoir - keep at least half full

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
101IDLE MODEIndicates that the engine is operating in idle mode. Grounding the engine idle input inhibits generator build-up and governs the engine at 800 RPM; control lowers oil pressure warning and shutdown trip points accordingly.WarningNone required; removing ground returns the genset to normal speed and voltage.
102EMERGENCY STOPIndicates local or remote Emergency Stop.ShutdownPull the button out (turn clockwise to allow it to pop out); move Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Reset only at the PCC front panel.
121SPEED SIGNAL LOSTMag pickup speed indication is not being sensed.ShutdownRestart and check RPM on digital display; inspect MPU wires/connector pins; check for 3.5 to 15 VAC at MPU while cranking.
135OIL PRESSURE SENSOR HEngine oil pressure sender signal is shorted high.WarningCheck sender/connectors/wires; verify fault simulation not enabled; check 0.5 to 4.5 VDC at P7-13 (OP OUT) and P7-17 (OP COM).
141OIL PRESSURE SENSOR LEngine oil pressure sender signal is shorted low.WarningCheck sender/connectors/wires; check for shorts/open circuits at P7-13, 17, 21.
143PRE-LOW OIL PRESEngine oil pressure dropped to an unacceptable level.WarningCheck oil level, lines and filters; replenish if low; if powering critical loads wait until next shutdown period and follow code 415.
144COOL SENSOR HIGHEngine coolant temperature signal is shorted high.WarningCheck sender/connectors/wires; check resistance between P7-30 (IH20) and P7-34 (IH20 COM).
145COOL SENSOR LOWEngine coolant temperature signal is shorted low.WarningCheck sender/connectors/wires; check for shorts at P7-30 and P7-34.
146PRE-HIGH COOL TMPEngine has begun to overheat (coolant temperature risen to an unacceptable level).WarningReduce load; check air inlets/outlets and remove obstructions to airflow; if engine can be stopped follow code 151.
151HIGH COOLANT TEMPEngine has overheated (coolant temperature above the shutdown trip point).ShutdownAllow engine to cool; check coolant level; check airflow obstructions; check fan belt; check blower fan/remote radiator pumps; reset control and restart.
197LOW COOLANT LEVELEngine coolant level has fallen below the warning trip point.WarningAllow engine to cool; check coolant level and replenish; look for leaks; reset control and restart.
200LOW OIL PRESSUREIndicates engine oil pressure has dropped to an unacceptable level.WarningIf powering critical loads and cannot be shut down, wait until next shutdown period then follow the 201-SHUTDOWN procedure. Check oil pressure via the Oil Pressure menu prior to clearing the fault.
201LOW OIL PRESSUREIndicates engine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters; if oil system is OK but oil level is low, replenish; reset control and restart. Oil pressure limits are listed in Table 4-3.
204OIL PRES SENDERIndicates that the control has sensed that the engine oil pressure sender is out of its working range.WarningCheck that the engine oil pressure sender is properly connected.
210LOW COOLANT TEMPWarning occurs when engine coolant temperature is 70 deg F (21 deg C) or lower while set is not operating.WarningIndicates engine coolant heater is not operating or is not circulating coolant; check coolant heater power supply/fuse, low coolant level, and open heater element.
211HIGH COOLANT TEMPIndicates engine coolant temperature is getting close to the recommended maximum (215 deg F/102 deg C standby or 207 deg F/97 deg C prime).WarningReduce load if possible; check air inlets and outlets and remove obstructions to airflow; if engine can be stopped follow the 212-SHUTDOWN procedure.
212HIGH COOLANT TEMPIndicates engine has overheated (coolant above 223 deg F/106 deg C standby or 215 deg F/102 deg C prime).ShutdownAllow engine to cool; check for obstructions to cooling airflow, check fan belt, check coolant mixture, check blower fan and circulation pumps; reset control and restart after correcting problem.
213COOLANT SENDERIndicates that the resistance of the coolant temperature sender is out of range.WarningCheck the resistance of the sender (should be 500 to 2k ohms).
214LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.WarningAllow engine to cool; check coolant level in radiator and recovery bottle and replenish if low; check for possible coolant leakage points.
215LOW COOLANT LVLIndicates engine coolant level has fallen below the shutdown trip point.ShutdownCheck coolant level in radiator and recovery bottle and replenish if low; check defective coolant bottle hose or radiator cap; reset control and restart after correcting problem. Will not occur in Idle mode.
220MAG PICKUPIndicates mag pickup speed indication is not being sensed or does not match generator set output frequency.ShutdownRestart and check RPM on the digital display; isolate per troubleshooting table 4-18.
221FAIL TO CRANKIndicates possible fault with control or starting system.ShutdownCheck fuse F3 on the Engine Interface board; clean battery cable connections; recharge or replace battery.
222OVERCRANKIndicates possible fuel system problem.ShutdownCheck for empty fuel tank, fuel leaks, or plugged fuel lines; check for dirty fuel filter and replace; check for dirty or plugged air filter and replace; reset control and restart.
223OVERSPEEDIndicates engine has exceeded normal operating speed (115% +/-1% of nominal).ShutdownInspect mechanical fuel linkage; check EFC for binding/damage; monitor PCC duty cycle and replace A32 or A38 as indicated.
224FAIL TO SYNCHRONIZEThe generator set has not synchronized to the system bus within the allowable time frame.Check governor system stability and adjust governing/synchronizer parameters; check for fuel system problems causing engine instability; widen synchronizing window and reduce acceptance time delay.
226FAIL TO CLOSEIndicates that the paralleling breaker has been given a signal to close, but has not closed properly.Verify charging mechanism of paralleling breaker; check the close signal to the breaker; verify auxiliary contact signals from the breaker to the control are operational.
230LOW DC VOLTAGEIndicates battery voltage is below 10 VDC.WarningCheck battery charger fuse and recharge or replace battery; clean and tighten battery cable connections; check engine DC alternator; check battery charge voltage float level.
231HIGH DC VOLTAGEIndicates battery voltage exceeds 32 VDC.WarningCheck voltage float level on battery charger (lower float level); check engine DC alternator and replace if normal charging voltage is not obtained.
232WEAK BATTERYIndicates battery voltage drops below 60% of nominal for two seconds during starting.WarningDischarged or defective battery; see warning message 230, LOW DC VOLTAGE.
234OVERSPEEDEngine has exceeded normal operating speed.ShutdownClear fault and restart genset; check fault threshold; monitor RPM; check electronic governor actuator.
235LOW COOLANT LEVELEngine coolant level has fallen below the shutdown trip point.ShutdownCheck coolant level and replenish; look for leaks; reset control and restart.
240LOW FUEL-DAYIndicates day tank fuel supply is running low.WarningCheck fuel supply and replenish as required.
241LOW FUELIndicates fuel supply is running low.WarningCheck fuel supply and replenish as required.
250EEPROM ERRORIndicates PCC memory error - data corruption of critical operating parameters.ShutdownPerform initial start setup; turn Run/Off/Auto to Off and reset; if the same EEPROM ERROR message occurs, replace the digital board (A32).
251EEPROM ERRORIndicates PCC memory error - data corruption of noncritical operating parameters.WarningPerform adjustment procedures and save; if the same EEPROM ERROR message occurs, replace the digital board (A32).
252EEPROM ERRORIndicates PCC memory error - data corruption of noncritical operating parameters.WarningVerify values/choices selected and repeat the save operation; if the same EEPROM ERROR message occurs, replace the digital board (A32).
260CUSTOMER FAULT 1Customer defined input closed to ground; message is editable.Isolate the source of the false signal; check A34 LED corresponding to the fault input.
261GROUND FAULTCustomer defined input closed to ground (default message); message is editable.Isolate the source of the false signal; check A34 LED corresponding to the fault input.
262RUPTURE BASIN (DAY TANK)Customer defined input closed to ground; message is editable.Isolate the source of the false signal; check A34 LED corresponding to the fault input.
263HIGH GEN TEMPCustomer defined input closed to ground (default message); message is editable.Isolate the source of the false signal; check A34 LED corresponding to the fault input.
270PHASE ROTATIONThe phase relationship between the generator set and the system bus is not matched.ShutdownUsing a phase rotation checker, verify that the generator set phase rotation matches the system bus; verify control wiring to the bus PT module is properly connected.
272FIRST STARTThe PowerCommand control is not receiving a proper signal from the system master first start sensor.WarningControl reverts to fallback mode; verify the Master First Start Sensor is functioning and that the voltage pulse is present at the PowerCommand control (terminal TB1-50); check interconnection wiring.
301HIGH AC VOLTAGEIndicates that one or more phase voltages has exceeded 130% of nominal, or exceeded 110% of nominal for 10 seconds.ShutdownIsolate the regulator module (A37), engine interface board (A31), digital board (A32), PMG/field wiring or PT/CT sensing path per troubleshooting table 4-29.
303LOW AC VOLTAGEIndicates that one or more phase voltages has dropped below 85% of nominal for 10 seconds.ShutdownCheck PMG or field wiring, rotating rectifier diodes, overload, loose connectors, and voltage sensing circuitry per troubleshooting table 4-30.
313UNDER FREQUENCYIndicates that engine speed has dropped below 90% of nominal for 10 seconds. (Five seconds before shutdown, a Load Dump signal is initiated.)ShutdownCheck fuel supply, intake air supply and load; check Initial Setup (set size).
320OVERCURRENTIndicates that generator output current has exceeded 110% of rated for 60 seconds.WarningCheck load and load lead connections.
321OVERCURRENTIndicates that generator output current has exceeded 110% of rated, and a PCC time/current calculation has initiated an overcurrent shutdown.ShutdownCheck load and load lead connections.
322SHORT CIRCUITIndicates that generator output current has exceeded 175% of rated.ShutdownCheck load and load lead connections.
330OVERLOADIndicates that three-phase power output exceeds 105% of standby (or 115% of prime) rating.WarningCheck load and load lead connections.
335REVERSE POWERIndicates that power is flowing into the generator set rather than out from the unit.ShutdownVerify connection of generator set CT's; verify proper connection of load sharing lines; verify correct frequency and voltage on all sets.
337LOSS OF EXCITATIONIndicates that the alternator excitation system is improperly adjusted or has failed.ShutdownCheck output voltage with calibrated meter and adjust; check load sharing lines; see Section 6 Servicing the Generator.
359FAIL TO STARTEngine cranks but fails to start (possible fuel system problem).ShutdownCheck for empty fuel tank, fuel leaks, or plugged fuel lines; replace dirty fuel filter; replace dirty air filter; reset control and restart.
415LOW OIL PRESSUREEngine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters; replenish if low; reset control and restart.
421OIL TEMPEngine has begun to overheat (oil temperature above unacceptable level) (Optional).WarningReduce load; check air inlets/outlets; if engine can be stopped follow code 151 and check engine oil level.
441LOW BAT VOLTAGEBattery voltage supply to the control approaching a low level.WarningCheck battery charger fuse; recharge or replace battery; clean and tighten cable connections; check engine DC alternator.
442HIGH BAT VOLTAGEBattery voltage supply approaching a high level at which control damage can occur.WarningCheck float level on battery charger; check battery wiring/calibration.
1122Rated/Idle TransInfo
1123SHUTDOWN AFTER BSA shutdown fault occurred while Battle Short was enabled and transitioned from enabled to disabled.ShutdownReview Fault History and perform corrective action.
1124DELAYED SHUTDOWNA shutdown fault became active while the Delayed Shutdown feature was enabled.WarningReview Fault History and perform corrective action.
1131BATTLE SHORT ACTIVEControl is in Battle Short mode (bypasses several critical fault shutdowns).WarningNone; used for genset operation during emergencies.
1311Customer Input #1Configurable customer input 1 fault.WarningCheck TB1-12; check external wiring; verify fault function settings.
1311, 1312, 1317, 1318CUSTOMER INPUT #1 - #4Optional customer-selected fault input is active.Disconnect signal lead from TB1 and reset the control; check external wiring/active input selection.
1312Customer Input #2Configurable customer input 2 fault.WarningCheck TB1-14; check external wiring; verify fault function settings.
1317Low Coolant LevelOptional coolant level sensor indicates low coolant level.WarningAdd coolant; check coolant level sensor connections and operation; verify calibration.
1318Low FuelOptional low fuel level switch indicates low fuel.WarningAdd fuel; verify switch operation; check wiring; verify settings.
1334CRIT SCALER ORIncorrect feature or calibration was entered into control.ShutdownReload correct feature/calibration file.
1335NONCRIT SCALER ORIncorrect feature or calibration was entered into control.WarningReload correct feature/calibration file.
1337No MessageInfo
1416FAIL TO SHUTDOWNGenset continues to run after receiving shutdown command (Battle Short feature enabled).WarningCheck Battle Short feature setting.
1417POWER DOWN ERRORController cannot power down because of an unknown condition.WarningCheck for possible battery drain.
1433EMERGENCY STOPLocal Emergency Stop.ShutdownPull the button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto.
1434REMOTE E-STOPRemote Emergency Stop.ShutdownSee code 1433 to reset.
1435LOW COOLANT TEMPEngine coolant heater is not operating or not circulating coolant (coolant <=70 F [21 C]).WarningCheck coolant heater power/fuse/cord; check coolant level; check heater element (10 to 60 ohms); check sensor.
1438FAIL TO CRANKEngine failed to crank after the PCC received a start signal.ShutdownTest for B+ at the starter; check fuse F3 (2 Amps); check K4 start pilot relay and starter circuitry; refer to code 121.
1442WEAK BATTERYDuring cranking battery voltage at or below weak battery trip point.WarningRecharge or replace battery; check electrolyte level and connections; check harness.
1443BATTERY FAILEDDead battery - engine will not start.ShutdownSee code 1438 instructions.
1444KW OVERLOADGenerator output power exceeded 105% of genset rating (3 sec at 110% of rated).WarningCheck load and load lead connections; check CTs and CT connections.
1445SHORT CIRCUITGenerator output current exceeded 175% of rated.ShutdownCheck load and load lead connections (fault may not reset for several minutes).
1446HIGH AC VOLTAGEPhase voltage exceeded 130% of nominal, or 110% of nominal for 10 seconds.ShutdownCheck fault simulation; clear fault and restart; refer to Generator/Base Board Isolation Procedure.
1447LOW AC VOLTAGEPhase voltage dropped below 85% of nominal for 10 seconds.ShutdownCheck load; reconnect per reconnection diagram; check PMG/field wiring; check P8-21/P8-22 shunt connections.

Showing the first 80 of 145 codes.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjusting Values/Parameters adjustment

⚠ If Home button or Previous Main Menu button is pressed before pressing save symbol, changes are not saved.

  1. Press button next to symbol in display until + and − symbols are displayed.
  2. Press button next to arrow symbols to move to numeric character to change.
  3. Press button next to + symbol to increase value or select parameter.
  4. Press button next to − symbol to decrease value or select parameter.
  5. After adjusting values/selecting parameters, press symbol to save changes.
Convert Day Tank Controller 240 VAC to 120 VAC adjustment
  1. Remove the two jumpers between terminals TB1-6 and TB1-7.
  2. Connect one jumper between TB1-5 and TB1-6 and the other between TB1-7 and TB1-8.
  3. Move selector switch S103 on the control PCB to the up position for 120V.
  4. If equipped with a transformer, remove jumpers between H2 and H3 and connect one between H1 and H3 and the other between H2 and H4.
Day Tank Controller Conversion 240 VAC to 120 VAC adjustment
  1. Remove the two jumpers between terminals TB1-6 and TB1-7 and connect one between TB1-5 and TB1-6 and the other between TB1-7 and TB1-8.
  2. Move selector switch S103 on the control PCB to the up position for 120V.
  3. On the control transformer, remove the two jumpers between terminals H2 and H3 and connect one between H1 and H3 and the other between H2 and H4.
Dip Adjustment adjustment
  1. Turn the DIP pot clockwise to increase the voltage vs frequency slope for frequencies below the UFRO threshold.
  2. Greater slope gives greater voltage roll off as frequency drops, easing large load pickup but increasing voltage dip.
  3. Turn the pot fully counterclockwise to make the slope the same above and below the threshold frequency.
Disabling the AMF Feature adjustment

⚠ Must be performed by a qualified technician.

Tools: InPower service tool

  1. Connect to the PCC 1.1 or PCC 2.3 via InPower.
  2. Navigate to Adjustments->Features->Automatic Transfer Switch folder.
  3. Select the Auto Mains Failure Enable parameter.
  4. Double-click on Enabled in the Value field.
  5. Select Disabled from the pop-up choices.
  6. Select Device->Save Adjustments from the top menu bar.
  7. Click Save on the confirmation pop-up.
  8. Disconnect InPower from the PCC1302 after confirmation.
Dwell Adjustment adjustment
  1. Turn the DWELL pot clockwise to increase dwell time (voltage recovery time when frequency dips below threshold).
  2. Turn the DWELL pot fully counterclockwise to eliminate dwell.
  3. With no dwell, voltage recovery follows engine speed recovery.
Fuel Injection Pump Speed Lever Adjustment adjustment
  1. Make sure the generator set is off and the battery is disconnected.
  2. If replacing pump or engine, discard speed adjust screw and tamper proof wire and seal.
  3. Replace the low idle screw; reuse throttle screw nut and acorn nut.
  4. Pull throttle lever back and screw new low idle screw until it contacts boss.
  5. Continue tightening until throttle lever is locked in place.
  6. Tighten the throttle lock nut.
  7. Install tamper proof wire and seal.
  8. Set the throttle lever as shown and lock it using seal wire.
Fuel Pump Control: Convert 120 VAC to 240 VAC adjustment
  1. Remove jumpers between TB1-5/TB1-6 and TB1-7/TB1-8; connect two jumpers between TB1-6 and TB1-7.
  2. Move selector switch S103 on control PCB to down position for 240 VAC.
  3. If equipped with a transformer, remove jumpers between H1/H3 and H2/H4 and connect two jumpers between H2 and H3.
  4. Attach a tag to the control box indicating the supply voltage.
Fuel Pump Control: Convert 240 VAC to 120 VAC adjustment
  1. Remove jumpers between TB1-6/TB1-7; connect one jumper TB1-5 to TB1-6 and one TB1-7 to TB1-8.
  2. Move selector switch S103 on control PCB to up position for 120V.
  3. If equipped with a transformer, remove jumpers between H2/H3 and connect one between H1-H3 and one between H2-H4.
Governor Adjustments (Type A Electric Governor) adjustment
  1. Set selector switch S1 to OFF, S2 to appropriate model position.
  2. Set pots initially: Gain 20%, I 20%, D 30%, Droop 0%.
  3. Start set, adjust Speed pot for required frequency (60Hz=1800RPM or 50Hz=1500RPM) at operating temperature.
  4. Disconnect load, turn Gain pot to 100% or until unstable, then back off until stable.
  5. Adjust D and I pots similarly; readjust Speed if necessary.
  6. Push throttle to minimum speed, release and observe overshoot (2-5 Hz acceptable); adjust I pot to reduce overshoot or hunting.
Initial Start Setup adjustment

⚠ Selecting this menu resets all operating parameters to default values; perform only by technically qualified personnel.

  1. Press RESET, MENU and PHASE SELECT simultaneously to invoke the Initial Start Setup menu.
  2. Toggle the Standby/Prime option.
  3. Select the correct generator set model, frequency and kW rating.
  4. Select the correct nominal line-to-line output voltage.
  5. Select DELTA or WYE.
  6. Select SAVE to save changes; MAIN MENU is then displayed.
Operating PowerCommand in Droop Mode adjustment
  1. Set the no load speed and voltage at the desired level (bus must be de-energized or disconnect Bus PT module).
  2. Apply 100% load and adjust KW load sharing gain for desired full load frequency; adjust KVAR load sharing gain for desired full load voltage.
  3. Repeat the process for other generator sets in the system.
  4. Test the system with all available load and verify approximately equal load sharing at no load and maximum load.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
AVR response jumperA to CFor generator output 90 kW or less (SX440 and MX321)
Auxiliary terminal board TB21K1, K2, P2, P3, P4, S2, S1, A2, A1A1 and A2 connect a VAR/power factor controller when paralleling with a utility; S1 and S2 connect a droop compensating CT when paralleling with a generator set or utility
CT1 - U load leads (A phase); CT2 - V load leads (B phase); CT3 - W load leads (C phase)6 lead gensets: generator output leads routed through CTs; 12 lead gensets: load wires routed through CTs12-lead sets have dual secondary CTs (3 pins); 6-lead sets have single secondary CTs (2 pins)
Day tank LO SHUTDOWN engine shutdown connectionTB1-14 to engine block ground; TB1-15 to TB2-16 on the ECM
Fault relay K8/K9 (Dry Contact Module)K8=Over Crank, Low Oil Pressure, High Engine Temperature, Low Coolant Level, Low Fuel Level; K9=Low Fuel Level, Rupture BasinContact ratings: 40A max carry/break N.O. 12V coil, 30A N.C. 12V coil, 20A N.O./10A N.C. 24V coil
MX321 PMG-excited jumper positions2-3, 4-5 and 6-7These jumpers must be in these positions
MX321 voltage regulator frequency jumper3-2 for 50 Hz; 3-1 for 60 Hz
SX440 voltage regulator frequency jumperC-50 for 50 Hz; C-60 for 60 Hz
TB3 (ECM alternative RUN/STOP/REMOTE connection)TB3-1=REMOTE, TB3-2=RUN, TB3-3=STOPProvides alternative direct connection to ECM for troubleshooting or customer connection
Voltage trimmer R21voltage regulator terminals 1 and 2There must be a jumper between terminals 1 and 2 when voltage trimmer R21 is not used
single phaseQSG-Series power distribution panel voltage selector switch S1 positionmain output terminalsRotary switch under lockable cover selects 120/240 VAC single phase
single phaseVoltage regulator terminal 6jumpered to terminal 8When the generator is connected for single-phase output, terminal 6 is not connected to the isolation transformer
three phaseQSG-Series power distribution panel voltage selector switch S1 positionmain output terminalsRotary switch selects 120/208 VAC three phase
110V - 120V L-NSingle phase, 2-wireJumper locations for single phase, 2-wirePTC Module AC wiring (0300-5382-01, -02)
120single phaseDay tank fuel pump control power reconnectionmove jumpers from TB1-6/TB1-7 to TB1-5/TB1-6 and TB1-7/TB1-8Move selector switch S103 on the control PCB to the up position for 120 V (factory set for 240 V, S103 down)
190, 200, 208, 220, 230, 240, 380, 416, 440, 460, 600 (L-L)3 (three phase)3 or 4 wiresVoltage Configuration submenu; default = 3Ph 208V 4W
190V - 240V L-LThree phaseJumper locations for three phase, 190V-240V L-LUse 0300-5382-01 for 190V-240V L-L, 50/60 Hz
200, 220, 230, 240 (L-L)1 (single phase)3 wiresVoltage Configuration submenu (Governor/Regulator Setup)
200V - 240V L-LSingle phase, 3-wireJumper locations for single phase, 3-wirePTC Module AC wiring
24Day tank fuel pump control logic power (two lead harness, no transformer)TB1-19 to positive (+) 24 V starter motor solenoid; TB-20 to negative (-)Provides 24 VDC for the control circuit
240single phaseDay tank fuel pump control default factory connectionjumpers between terminals TB1-6 and TB1-7Selector switch S103 on the control PCB in the down position for 240 V
380V - 600V L-LThree phaseJumper locations for three phase, 380V-600V L-LUse 0300-5382-02 for 380V-600V L-L, 50/60 Hz

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan 4B3.9 family

49
Part #DescriptionCategory
140-2641Tube, Air CleanerAir filter
140-3218Cleaner Assembly, Air (IncludesAir filter
982-0200Air FilterAir filter
300-3606Voltage Regulator Installation (PMG-Excited Generators), Rev. PAvr
300-3607Voltage Regulator Installation (Self-Excited Generators), Rev. GAvr
191-1965Tensioner, BeltBelt
191-2149-02Tensioner, BeltBelt
505-0055Element, FuelFuel filter
140-3255*Hose, BreatherHose
502-0827Fitting, Hose – Barbed (1/2” ID Pipe to 3/4” ID Hose)Hose
502-1317Fitting, Hose BarbedHose
503-1707*Hose, Intake (2–1/2” ID)Hose
102-1490-00Kit, Oil Sampler (IncludesOil filter
102-1490-01Valve, Oil SamplerOil filter
154-3078Manifold, Oil PressureOil filter
501-0575Hose Assembly, Oil (3/4–16Oil filter
501-0685Line, OilOil filter
504-0176Valve, Oil DrainOil filter
140-1260Fitting, Safety FilterService part / kit
201-3434-01Diode, Positive (Forward) Includes LeadService part / kit
201-3434-02Diode, Negative (Reverse) Includes LeadService part / kit
220-4289-31Main stator assembly (broad range generators)Service part / kit
220-4289-32Main stator assembly (broad range generators)Service part / kit
220-4289-33Main stator assembly (broad range generators)Service part / kit
220-4289-34Main stator assembly (broad range generators)Service part / kit
220-4289-35Main stator assembly (broad range generators)Service part / kit
220-4298-31Main stator assemblyService part / kit
220-4298-32Main stator assemblyService part / kit
220-4298-33Main stator assemblyService part / kit
220-4298-34Main stator assemblyService part / kit
220-4298-35Main stator assemblyService part / kit
220-4298-36Main stator assemblyService part / kit
300-4111Auxiliary Relay Board (ARB), Rev. EService part / kit
319-0969QS-Series Power Distribution Panel Wiring, Rev. GService part / kit
3905125Solenoid, Fuel Shutoff – MCGGA, 24 Volt, Negative Ground Electrical System (Cummins part number)Service part / kit
3921930Solenoid, Fuel Shutoff – 12 Volt (Cummins part number)Service part / kit
3921976Solenoid, Fuel Shutoff – 24 Volt (Cummins part number)Service part / kit
502-0153Plug, Hex HeadService part / kit
612-64877-Light DC Control Wiring Diagram, Sh 1 and 2 of 2, Rev. VService part / kit
612-648812-Light DC Control Wiring Diagram, Sh 1 and 2 of 2, Rev. WService part / kit
612-6489AC Control Wiring Diagram (Without Meters), Rev. S, modified 6/2001Service part / kit
612-6490AC Control Wiring Diagram (With Meters), Rev. ZB, modified 1/2002Service part / kit
625-2164Generator Reconnection Diagrams, Sh 1 and 2 of 2, Rev. KService part / kit
625-2256QS-Series Generator Connections When The Voltage Selector Switch Is Provided, Rev. BService part / kit
965-0520Cooling FanService part / kit
625-2141Day Tank Pump Control Wiring, Rev. PPump
509-0266-01Ring, OSeal
150-2201Sensor, Speed – MagneticSensor
517-0291Plug, TaperSpark plug

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan 4B3.9-G2?

The Cummins/Onan 4B3.9-G2 engine has an oil capacity of 10.9 liters.

What is the displacement of the Cummins/Onan 4B3.9-G2?

The Cummins/Onan 4B3.9-G2 has a displacement of 3.9 liters with 4 cylinders.

Which generators use the Cummins/Onan 4B3.9-G2 engine?

The Cummins/Onan 4B3.9-G2 powers 3 generator set(s), including Cummins/Onan C40 D6, Cummins/Onan C45D5, Cummins/Onan DGBB.

What is a common problem with the Cummins/Onan 4B3.9-G2 engine?

A commonly reported issue on generators using the Cummins/Onan 4B3.9-G2 is: Engine cranks but will not start. Cause: Empty fuel tank, fuel leaks, or plugged fuel lines. Fix: Correct as required.