| 101 | IDLE MODE | Indicates that the engine is operating in idle mode. Grounding the engine idle input inhibits generator build-up and governs the engine at 800 RPM; control lowers oil pressure warning and shutdown trip points accordingly. | Warning | None required; removing ground returns the genset to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Pull the button out (turn clockwise to allow it to pop out); move Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Reset only at the PCC front panel. |
| 121 | SPEED SIGNAL LOST | Mag pickup speed indication is not being sensed. | Shutdown | Restart and check RPM on digital display; inspect MPU wires/connector pins; check for 3.5 to 15 VAC at MPU while cranking. |
| 135 | OIL PRESSURE SENSOR H | Engine oil pressure sender signal is shorted high. | Warning | Check sender/connectors/wires; verify fault simulation not enabled; check 0.5 to 4.5 VDC at P7-13 (OP OUT) and P7-17 (OP COM). |
| 141 | OIL PRESSURE SENSOR L | Engine oil pressure sender signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts/open circuits at P7-13, 17, 21. |
| 143 | PRE-LOW OIL PRES | Engine oil pressure dropped to an unacceptable level. | Warning | Check oil level, lines and filters; replenish if low; if powering critical loads wait until next shutdown period and follow code 415. |
| 144 | COOL SENSOR HIGH | Engine coolant temperature signal is shorted high. | Warning | Check sender/connectors/wires; check resistance between P7-30 (IH20) and P7-34 (IH20 COM). |
| 145 | COOL SENSOR LOW | Engine coolant temperature signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts at P7-30 and P7-34. |
| 146 | PRE-HIGH COOL TMP | Engine has begun to overheat (coolant temperature risen to an unacceptable level). | Warning | Reduce load; check air inlets/outlets and remove obstructions to airflow; if engine can be stopped follow code 151. |
| 151 | HIGH COOLANT TEMP | Engine has overheated (coolant temperature above the shutdown trip point). | Shutdown | Allow engine to cool; check coolant level; check airflow obstructions; check fan belt; check blower fan/remote radiator pumps; reset control and restart. |
| 197 | LOW COOLANT LEVEL | Engine coolant level has fallen below the warning trip point. | Warning | Allow engine to cool; check coolant level and replenish; look for leaks; reset control and restart. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If powering critical loads and cannot be shut down, wait until next shutdown period then follow the 201-SHUTDOWN procedure. Check oil pressure via the Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; if oil system is OK but oil level is low, replenish; reset control and restart. Oil pressure limits are listed in Table 4-3. |
| 204 | OIL PRES SENDER | Indicates that the control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70 deg F (21 deg C) or lower while set is not operating. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant; check coolant heater power supply/fuse, low coolant level, and open heater element. |
| 211 | HIGH COOLANT TEMP | Indicates engine coolant temperature is getting close to the recommended maximum (215 deg F/102 deg C standby or 207 deg F/97 deg C prime). | Warning | Reduce load if possible; check air inlets and outlets and remove obstructions to airflow; if engine can be stopped follow the 212-SHUTDOWN procedure. |
| 212 | HIGH COOLANT TEMP | Indicates engine has overheated (coolant above 223 deg F/106 deg C standby or 215 deg F/102 deg C prime). | Shutdown | Allow engine to cool; check for obstructions to cooling airflow, check fan belt, check coolant mixture, check blower fan and circulation pumps; reset control and restart after correcting problem. |
| 213 | COOLANT SENDER | Indicates that the resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender (should be 500 to 2k ohms). |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Allow engine to cool; check coolant level in radiator and recovery bottle and replenish if low; check for possible coolant leakage points. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the shutdown trip point. | Shutdown | Check coolant level in radiator and recovery bottle and replenish if low; check defective coolant bottle hose or radiator cap; reset control and restart after correcting problem. Will not occur in Idle mode. |
| 220 | MAG PICKUP | Indicates mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM on the digital display; isolate per troubleshooting table 4-18. |
| 221 | FAIL TO CRANK | Indicates possible fault with control or starting system. | Shutdown | Check fuse F3 on the Engine Interface board; clean battery cable connections; recharge or replace battery. |
| 222 | OVERCRANK | Indicates possible fuel system problem. | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines; check for dirty fuel filter and replace; check for dirty or plugged air filter and replace; reset control and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed (115% +/-1% of nominal). | Shutdown | Inspect mechanical fuel linkage; check EFC for binding/damage; monitor PCC duty cycle and replace A32 or A38 as indicated. |
| 224 | FAIL TO SYNCHRONIZE | The generator set has not synchronized to the system bus within the allowable time frame. | | Check governor system stability and adjust governing/synchronizer parameters; check for fuel system problems causing engine instability; widen synchronizing window and reduce acceptance time delay. |
| 226 | FAIL TO CLOSE | Indicates that the paralleling breaker has been given a signal to close, but has not closed properly. | | Verify charging mechanism of paralleling breaker; check the close signal to the breaker; verify auxiliary contact signals from the breaker to the control are operational. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Check battery charger fuse and recharge or replace battery; clean and tighten battery cable connections; check engine DC alternator; check battery charge voltage float level. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Check voltage float level on battery charger (lower float level); check engine DC alternator and replace if normal charging voltage is not obtained. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds during starting. | Warning | Discharged or defective battery; see warning message 230, LOW DC VOLTAGE. |
| 234 | OVERSPEED | Engine has exceeded normal operating speed. | Shutdown | Clear fault and restart genset; check fault threshold; monitor RPM; check electronic governor actuator. |
| 235 | LOW COOLANT LEVEL | Engine coolant level has fallen below the shutdown trip point. | Shutdown | Check coolant level and replenish; look for leaks; reset control and restart. |
| 240 | LOW FUEL-DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 241 | LOW FUEL | Indicates fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 250 | EEPROM ERROR | Indicates PCC memory error - data corruption of critical operating parameters. | Shutdown | Perform initial start setup; turn Run/Off/Auto to Off and reset; if the same EEPROM ERROR message occurs, replace the digital board (A32). |
| 251 | EEPROM ERROR | Indicates PCC memory error - data corruption of noncritical operating parameters. | Warning | Perform adjustment procedures and save; if the same EEPROM ERROR message occurs, replace the digital board (A32). |
| 252 | EEPROM ERROR | Indicates PCC memory error - data corruption of noncritical operating parameters. | Warning | Verify values/choices selected and repeat the save operation; if the same EEPROM ERROR message occurs, replace the digital board (A32). |
| 260 | CUSTOMER FAULT 1 | Customer defined input closed to ground; message is editable. | | Isolate the source of the false signal; check A34 LED corresponding to the fault input. |
| 261 | GROUND FAULT | Customer defined input closed to ground (default message); message is editable. | | Isolate the source of the false signal; check A34 LED corresponding to the fault input. |
| 262 | RUPTURE BASIN (DAY TANK) | Customer defined input closed to ground; message is editable. | | Isolate the source of the false signal; check A34 LED corresponding to the fault input. |
| 263 | HIGH GEN TEMP | Customer defined input closed to ground (default message); message is editable. | | Isolate the source of the false signal; check A34 LED corresponding to the fault input. |
| 270 | PHASE ROTATION | The phase relationship between the generator set and the system bus is not matched. | Shutdown | Using a phase rotation checker, verify that the generator set phase rotation matches the system bus; verify control wiring to the bus PT module is properly connected. |
| 272 | FIRST START | The PowerCommand control is not receiving a proper signal from the system master first start sensor. | Warning | Control reverts to fallback mode; verify the Master First Start Sensor is functioning and that the voltage pulse is present at the PowerCommand control (terminal TB1-50); check interconnection wiring. |
| 301 | HIGH AC VOLTAGE | Indicates that one or more phase voltages has exceeded 130% of nominal, or exceeded 110% of nominal for 10 seconds. | Shutdown | Isolate the regulator module (A37), engine interface board (A31), digital board (A32), PMG/field wiring or PT/CT sensing path per troubleshooting table 4-29. |
| 303 | LOW AC VOLTAGE | Indicates that one or more phase voltages has dropped below 85% of nominal for 10 seconds. | Shutdown | Check PMG or field wiring, rotating rectifier diodes, overload, loose connectors, and voltage sensing circuitry per troubleshooting table 4-30. |
| 313 | UNDER FREQUENCY | Indicates that engine speed has dropped below 90% of nominal for 10 seconds. (Five seconds before shutdown, a Load Dump signal is initiated.) | Shutdown | Check fuel supply, intake air supply and load; check Initial Setup (set size). |
| 320 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 321 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated, and a PCC time/current calculation has initiated an overcurrent shutdown. | Shutdown | Check load and load lead connections. |
| 322 | SHORT CIRCUIT | Indicates that generator output current has exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 330 | OVERLOAD | Indicates that three-phase power output exceeds 105% of standby (or 115% of prime) rating. | Warning | Check load and load lead connections. |
| 335 | REVERSE POWER | Indicates that power is flowing into the generator set rather than out from the unit. | Shutdown | Verify connection of generator set CT's; verify proper connection of load sharing lines; verify correct frequency and voltage on all sets. |
| 337 | LOSS OF EXCITATION | Indicates that the alternator excitation system is improperly adjusted or has failed. | Shutdown | Check output voltage with calibrated meter and adjust; check load sharing lines; see Section 6 Servicing the Generator. |
| 359 | FAIL TO START | Engine cranks but fails to start (possible fuel system problem). | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines; replace dirty fuel filter; replace dirty air filter; reset control and restart. |
| 415 | LOW OIL PRESSURE | Engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset control and restart. |
| 421 | OIL TEMP | Engine has begun to overheat (oil temperature above unacceptable level) (Optional). | Warning | Reduce load; check air inlets/outlets; if engine can be stopped follow code 151 and check engine oil level. |
| 441 | LOW BAT VOLTAGE | Battery voltage supply to the control approaching a low level. | Warning | Check battery charger fuse; recharge or replace battery; clean and tighten cable connections; check engine DC alternator. |
| 442 | HIGH BAT VOLTAGE | Battery voltage supply approaching a high level at which control damage can occur. | Warning | Check float level on battery charger; check battery wiring/calibration. |
| 1122 | Rated/Idle Trans | | Info | |
| 1123 | SHUTDOWN AFTER BS | A shutdown fault occurred while Battle Short was enabled and transitioned from enabled to disabled. | Shutdown | Review Fault History and perform corrective action. |
| 1124 | DELAYED SHUTDOWN | A shutdown fault became active while the Delayed Shutdown feature was enabled. | Warning | Review Fault History and perform corrective action. |
| 1131 | BATTLE SHORT ACTIVE | Control is in Battle Short mode (bypasses several critical fault shutdowns). | Warning | None; used for genset operation during emergencies. |
| 1311 | Customer Input #1 | Configurable customer input 1 fault. | Warning | Check TB1-12; check external wiring; verify fault function settings. |
| 1311, 1312, 1317, 1318 | CUSTOMER INPUT #1 - #4 | Optional customer-selected fault input is active. | | Disconnect signal lead from TB1 and reset the control; check external wiring/active input selection. |
| 1312 | Customer Input #2 | Configurable customer input 2 fault. | Warning | Check TB1-14; check external wiring; verify fault function settings. |
| 1317 | Low Coolant Level | Optional coolant level sensor indicates low coolant level. | Warning | Add coolant; check coolant level sensor connections and operation; verify calibration. |
| 1318 | Low Fuel | Optional low fuel level switch indicates low fuel. | Warning | Add fuel; verify switch operation; check wiring; verify settings. |
| 1334 | CRIT SCALER OR | Incorrect feature or calibration was entered into control. | Shutdown | Reload correct feature/calibration file. |
| 1335 | NONCRIT SCALER OR | Incorrect feature or calibration was entered into control. | Warning | Reload correct feature/calibration file. |
| 1337 | No Message | | Info | |
| 1416 | FAIL TO SHUTDOWN | Genset continues to run after receiving shutdown command (Battle Short feature enabled). | Warning | Check Battle Short feature setting. |
| 1417 | POWER DOWN ERROR | Controller cannot power down because of an unknown condition. | Warning | Check for possible battery drain. |
| 1433 | EMERGENCY STOP | Local Emergency Stop. | Shutdown | Pull the button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto. |
| 1434 | REMOTE E-STOP | Remote Emergency Stop. | Shutdown | See code 1433 to reset. |
| 1435 | LOW COOLANT TEMP | Engine coolant heater is not operating or not circulating coolant (coolant <=70 F [21 C]). | Warning | Check coolant heater power/fuse/cord; check coolant level; check heater element (10 to 60 ohms); check sensor. |
| 1438 | FAIL TO CRANK | Engine failed to crank after the PCC received a start signal. | Shutdown | Test for B+ at the starter; check fuse F3 (2 Amps); check K4 start pilot relay and starter circuitry; refer to code 121. |
| 1442 | WEAK BATTERY | During cranking battery voltage at or below weak battery trip point. | Warning | Recharge or replace battery; check electrolyte level and connections; check harness. |
| 1443 | BATTERY FAILED | Dead battery - engine will not start. | Shutdown | See code 1438 instructions. |
| 1444 | KW OVERLOAD | Generator output power exceeded 105% of genset rating (3 sec at 110% of rated). | Warning | Check load and load lead connections; check CTs and CT connections. |
| 1445 | SHORT CIRCUIT | Generator output current exceeded 175% of rated. | Shutdown | Check load and load lead connections (fault may not reset for several minutes). |
| 1446 | HIGH AC VOLTAGE | Phase voltage exceeded 130% of nominal, or 110% of nominal for 10 seconds. | Shutdown | Check fault simulation; clear fault and restart; refer to Generator/Base Board Isolation Procedure. |
| 1447 | LOW AC VOLTAGE | Phase voltage dropped below 85% of nominal for 10 seconds. | Shutdown | Check load; reconnect per reconnection diagram; check PMG/field wiring; check P8-21/P8-22 shunt connections. |