Decision-Maker 550 Controller

The Decision-Maker 550 is a generator-set controller. It is used on generator sets from Decision-Maker and Kohler, including the 1000 REOZM, 100ERESD, 100REOZJC and 100REOZJE.

218
Generator sets
2
Brands
26–2800 kW
Power range
4
Fuel types

Troubleshooting

39

Fault codes

CodeMeaningRemedy
32High Coolant Temperature
32AEmergency StopReset the emergency stop switch.
40Pre High Coolant Temp.
41Pre Low Oil PressureCheck and adjust oil level or replace oil pump.
48Emergency Stop
62Low Battery Volts
63Low FuelRefuel the generator set.

Symptoms & remedies

SymptomCauseRemedy
Battery charger and/or block heater not functioningDevices not connected to receptaclePlug devices into respective receptacles
Cranks but does not startController and Emergency Stop Switch
Display is blackNo/low battery chargeRecharge/replace battery
Display locks upNo/low battery chargeRecharge/replace battery
Display shows an EEPROM WRITE ERROR messageEEPROM fault caused by component failure, lightening strike, or voltage spikeReinitialize the problem data block; Contact an Authorized Distributor/Dealer
Display shows an error messageController firmware or pushbutton/rotary selector dial entry errorReview the System Fault Shutdown Lamp With Digital Displays section
Display shows single segmentLow battery voltageRecharge battery
Displays error message/locks upController master control buttons inoperativeReplace the controller master control button circuit board.
Does not crankController and Emergency Stop Switch
Duplex circuit breaker(s) tripped or trips when resetCircuit breaker overloadedReduce circuit load. Reset duplex circuit breaker(s).
Duplex receptacles have no powerGenerator set not runningPower to duplex receptacles is from the generator set—not shore power.
Excessive or abnormal noiseVibration excessiveTighten loose components.
Exercise run time and/or event records inoperativeController clock not setReset time and date.
High fuel consumptionCompression weakCheck the compression.
Lacks powerAir cleaner cloggedClean or replace the filter element.
Low oil pressureOil level lowRestore the oil level. Inspect the generator set for oil leaks.
Main circuit breaker(s) tripped or trips when resetCircuit breaker overloadedReduce circuit load. Reset circuit breaker.
No or low output voltageVoltage regulation inoperativeReplace the junction box sensing fuses. If the fuse blows again, troubleshoot the controller.
Output voltage rampsDefective exciter windingTroubleshoot alternator components
Output voltage unstableVoltage regulation calibration incorrectReadjust voltage regulation
OverheatsGovernor inoperativeAdjust the governor.
Speed adjust does not functionAnalog input A06 is supported with Doosan, GM, and Volvo engines onlyCheck calibration values
Starts hardController faultTroubleshoot the controller.
Stops suddenlyEngine overloadReduce the electrical load. See the generator set spec sheet for wattage specifications.
Tow vehicle and trailer are unstable or noisy during brakingTow vehicle brakes wornCheck brake fluid level. Add fluid as necessary.
Trailer is unstable or noisy during towing.Tire(s) worn or damagedCheck tire condition. Repair or replace.
Unable to change voltage and current calibrationsCalibration not enabledEnable calibration in Generator Metering section 2.6.3 Calibration Submenu
Unable to find volt select menuVolt select not enabledEnable volt select in SiteTech
User-supplied wiring between customer connection panel and load devices feels hot or has burning odorWiring undersized for applicationContact onsite electrician or rental distributor.
Voltage adjust does not function for paralleling applicationsAnalog input A07 description does not match Analog Volt AdjustChange description to Analog Volt Adjust using Monitor III software or enable analog voltage adjust in Menu 11
Voltage selector switch knob does not rotate.Padlock installed on lockout featureContact onsite electrician or rental distributor.
Voltage selector switch position does not match load voltage.Unit not set up for applicationContact onsite electrician or rental distributor. See Section 3, Electrical Connections and Requirements, for more information.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.