Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 200 kW |
| Standby kVA | 250 |
| Prime power | 180 kW |
| Emissions | Tier 3 |
| Controller | APM402, APM603, Decision-Maker 550, Decision-Maker 6000 |
| Oil capacity | 32.5 L |
| Alternator | Kohler 4S13X, 4UA9, 4UA13 (4-pole, Class H insulation) |
| Voltage options | 120 V, 208 V, 277 V |
| Phase | 3 |
| Rated current | 694 A |
| Power factor | 0.8 |
| Battery group | 2 |
| Battery cranking | 925 CCA |
| Battery voltage | 12 V |
| Battery quantity | 2 |
| Coolant capacity | 27.6 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3000×1300×1672 mm |
| Dry weight | 1923 kg |
| Tank runtime | 48 hr |
Engine
| Oil capacity | 32.5 L |
|---|---|
| Coolant capacity | 27.6 L |
| Displacement | 6.8 L |
| Aspiration | Turbocharged, Charge Air-Cooled |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the John Deere 6068HFG85| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Dry | 4508301 | PartsGeek | ||
| Fuel filter | — | find | |||
| Fuel filter | Primary | GM50074 | Amazon eBay $70.33 PartsGeek | ||
| Fuel filter | Secondary | GM50006 | Amazon eBay $35.39 PartsGeek | ||
| Oil filter | Cartridge | ×1 | GM32809 | Amazon eBay $42.50 PartsGeek | |
| Belt | GM64496 | Amazon eBay $36.00 PartsGeek | |||
| Coolant | Water-Cooled | — | |||
| Oil | 32.5 L (qt.) | — |
Common questions
What is the power rating of the Kohler 200REOZJF?
The Kohler 200REOZJF is rated 200 kW standby (250.0 kVA).
What engine does the Kohler 200REOZJF use?
The Kohler 200REOZJF is powered by the John Deere 6068HFG85 engine.
What fuel does the Kohler 200REOZJF use?
The Kohler 200REOZJF runs on Diesel.
What is the oil capacity of the Kohler 200REOZJF?
The John Deere 6068HFG85 engine in the Kohler 200REOZJF has an oil capacity of 32.5 liters.
What alternator does the Kohler 200REOZJF use?
The Kohler 200REOZJF uses a Kohler 4S13X, 4UA9, 4UA13 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 16.6 | 4.4 |
| Prime | 50% | 25.7 | 6.8 |
| Prime | 75% | 36.1 | 9.5 |
| Prime | 100% | 50.1 | 13.2 |
| Standby | 25% | 19.7 | 5.2 |
| Standby | 50% | 31.4 | 8.3 |
| Standby | 75% | 43.3 | 11.4 |
| Standby | 100% | 58.0 | 15.3 |