AKSA APD-ULJ200 Generator Set

The AKSA APD-ULJ200 is a 200 kW (250 kVA) DIESEL standby generator set powered by a John Deere 6068HFG85 engine. It is available at 480 V, 240 V, 208 V and 600 V, 3-phase, 60 Hz and rated 301 A. It holds about 12.6 L (3.3 gal) of oil and 12.6 L (3.3 gal) of coolant, with a maximum ambient rating of 50 °C. Starting uses 1 group-80 battery at 12 V. The set measures 3200×1400×1564 mm (126.0×55.1×61.6 in), weighs about 2154 kg (4749 lb) and produces 75 dBA at 7 m. An integrated tank holds 370 L (97.7 gal), roughly 24 hours of runtime. The same 6068HFG85 engine also powers generator sets from Kohler and MTU.

200 kW
Standby
6.8 L
Displacement
12.6 L
Oil capacity
1
Document types

Typical fuel consumption for 200–205 kW Diesel generators →

Compare with other 200–205 kW Diesel generators →

Service parts for the APD-ULJ200

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required

Fuel system

2 required
GM50074Fuel filter (primary)$70.33eBay
GM50006Fuel filter (secondary)$23.99Amazon

Oil system

1 required

Belts

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

FuelDIESEL
Frequency60.0 Hz
Standby power200 kW
Standby kVA250
EmissionsEPA Tier 3
ControllerDSE 7320 MK II
Oil capacity12.6 L
AlternatorStamford/AvK UCDI274K (Wnd-311)
Voltage options480 V, 277 V, 240 V, 120 V, 208 V, 600 V, 347 V
Phase3
Rated current301 A
Power factor0.8
Circuit breaker602 A
Battery group80Ah
Battery voltage12 V
Battery quantity1
Coolant capacity12.6 L
Max ambient50 °C
Dimensions (L×W×H)3200×1400×1564 mm
Dry weight2154 kg
Sound level75.0 dBA @ 7 m
Fuel tank370.0 L
Tank runtime24 hr

Engine

John Deere 6068HFG85
Oil capacity32.2 L
Coolant capacity29.3 L
Displacement6.8 L
AspirationTurbocharged, Charge Air-Cooled
Rated speed1800 rpm

Maintenance & consumables

for the John Deere 6068HFG85
ItemSpecCapacityPart #Interval
Air filterHeavy Duty Air Cleaner4508301 Amazon eBay $11.96
Fuel filter
Fuel filterPrimaryGM50074 Amazon $76.45 eBay $70.33
Fuel filterSecondaryGM50006 Amazon $23.99 eBay $26.99
Oil filterGM32809 Amazon $57.96 eBay $26.25
BatteryBattery, Battery Charger, Battery Heater
BeltGM64496 Amazon eBay $36.00
Coolant
Oil33.4 L
Spark plug

Common questions

How many kW is the AKSA APD-ULJ200?

The AKSA APD-ULJ200 is rated 200 kW standby (250.0 kVA).

What engine does the AKSA APD-ULJ200 use?

The AKSA APD-ULJ200 is powered by the John Deere 6068HFG85 engine.

Is the AKSA APD-ULJ200 diesel or gas?

The AKSA APD-ULJ200 runs on DIESEL.

How much oil does the AKSA APD-ULJ200 take?

The John Deere 6068HFG85 engine in the AKSA APD-ULJ200 has an oil capacity of 32.2 liters.

What alternator comes on the AKSA APD-ULJ200?

The AKSA APD-ULJ200 uses a Stamford/AvK UCDI274K (Wnd-311) alternator.

What oil filter does the AKSA APD-ULJ200 use?

The AKSA APD-ULJ200 uses oil filter part number GM32809.

What fuel filter fits the AKSA APD-ULJ200?

The AKSA APD-ULJ200 uses fuel filter part numbers GM50074, GM50006.

What air filter fits the AKSA APD-ULJ200?

The AKSA APD-ULJ200 uses air filter part number 4508301.

Fuel consumption

RatingLoadL/hgal/h
Standby25%4.2516.1
Standby50%7.9129.9
Standby75%11.3342.7
Standby100%15.4659.4

Available documents

Reference — APD-ULJ200 rev1 (AKSA)
Full service, cheapest listings

Priced items from this model's own parts manual.

Air filter 4508301$11.96
Fuel filter (primary) GM50074$70.33
Fuel filter (secondary) GM50006$23.99
Oil filter GM32809$26.25
Belt GM64496$36.00
5 priced items$168.53