Specifications
| Fuel | natural gas / LP |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 200 kW |
| Standby kVA | 250 |
| Prime power | 175 kW |
| Controller | APM402, Decision-Maker 550, Decision-Maker 6000 |
| Oil capacity | 27.0 L |
| Alternator | Fast-Response PMG (Class Class H insulation) |
| Voltage options | 480 V |
| Phase | 3-phase |
| Power factor | 0.8 |
| Battery cranking | 925 CCA |
| Battery voltage | 12 V |
| Battery quantity | 2 |
| Coolant capacity | 116.0 L |
| Engine jacket water | 21.0 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3575×1350×1908 mm |
| Dry weight | 2722 kg |
| Sound level | 71.0 dBA @ 23 m |
Engine
| Oil capacity | 27.0 L |
|---|---|
| Coolant capacity | 116.0 L |
| Displacement | 11.05 L |
| Aspiration | Turbocharged, Aftercooled |
| Rated speed | 1800 rpm |
Same engine, other brands
2 brandsThe Doosan D111TIC in this set also powers 2 generator sets sold under 2 other brands. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| Generac | MGG210 |
| Magnum | MGG210N2 |
Maintenance & consumables
for the Doosan D111TIC| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Oil filter | Cartridge | ×1 | — | ||
| Coolant | 116.0 L | — | |||
| Oil | 27.0 L | — |
Service specifications
30| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | 10 in. weld flange bolt circle diameter B | 361.95 | mm (14.25 in.) | |
| Other | 10 in. weld flange outside diameter C | 406.4 | mm (16.0 in.) | |
| Other | 10 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 12 in. weld flange bolt circle diameter B | 431.80 | mm (17.00 in.) | |
| Other | 12 in. weld flange outside diameter C | 482.6 | mm (19.0 in.) | |
| Other | 12 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 14 in. weld flange bolt circle diameter B | 476.25 | mm (18.75 in.) | |
| Other | 14 in. weld flange outside diameter C | 533.4 | mm (21.0 in.) | |
| Other | 14 in. weld flange quantity of bolts / bolt hole diameter D | 12, 28.58 | mm (1.13 in.) | |
| Other | 16 in. weld flange bolt circle diameter B | 539.75 | mm (21.25 in.) | |
| Other | 16 in. weld flange outside diameter C | 596.9 | mm (23.5 in.) | |
| Other | 16 in. weld flange quantity of bolts / bolt hole diameter D | 16, 28.58 | mm (1.13 in.) | |
| Other | 18 in. weld flange bolt circle diameter B | 577.85 | mm (22.75 in.) | |
| Other | 18 in. weld flange outside diameter C | 635.0 | mm (25.0 in.) | |
| Other | 18 in. weld flange quantity of bolts / bolt hole diameter D | 16, 31.75 | mm (1.25 in.) | |
| Other | 20 in. weld flange bolt circle diameter B | 635.00 | mm (25.00 in.) | |
| Other | 20 in. weld flange outside diameter C | 698.5 | mm (27.5 in.) | |
| Other | 20 in. weld flange quantity of bolts / bolt hole diameter D | 20, 31.75 | mm (1.25 in.) | |
| Other | 5 in. weld flange bolt circle diameter B | 215.90 | mm (8.50 in.) | |
| Other | 5 in. weld flange outside diameter C | 241.30 | mm (9.50 in.) | |
| Other | 5 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 6 in. weld flange bolt circle diameter B | 254.0 | mm (10.0 in.) | |
| Other | 6 in. weld flange outside diameter C | 279.4 | mm (11.0 in.) | |
| Other | 6 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 8 in. weld flange bolt circle diameter B | 298.45 | mm (11.75 in.) | |
| Other | 8 in. weld flange outside diameter C | 342.9 | mm (13.5 in.) | |
| Other | 8 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | Weld flange angle A (10, 12, 14 in. nominal pipe size) | 30 | deg. | |
| Other | Weld flange angle A (16, 18, 20 in. nominal pipe size) | 22.5 | deg. | |
| Other | Weld flange angle A (5, 6, 8 in. nominal pipe size) | 45 | deg. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12-lead optional voltage connections | 12 | Alternator optional feature | ||
| 4-lead dedicated voltages | 4 | Alternator standard feature | ||
| 110/127/139/240/254/277 | single-phase | switchable | Towable generator model specifications; some models n/a | |
| 208/220/240/415/440/480 | 3-phase | reconnectable | Towable generator model specifications | |
| 208/220/240/415/440/480 | 3-phase | switchable | Towable generator model specifications |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
How many kW is the Kohler 200REZX?
The Kohler 200REZX is rated 200 kW standby (250.0 kVA).
What engine is in the Kohler 200REZX?
The Kohler 200REZX is powered by the Doosan D111TIC engine.
What fuel type does the Kohler 200REZX take?
The Kohler 200REZX runs on natural gas / LP.
What is the oil capacity of the Kohler 200REZX?
The Doosan D111TIC engine in the Kohler 200REZX has an oil capacity of 27.0 liters.
How much coolant does the Kohler 200REZX hold?
The Kohler 200REZX cooling system holds 116 liters (30.6 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the prime power rating of the Kohler 200REZX?
The Kohler 200REZX is rated 175 kW prime (219 kVA), against 200 kW standby.
What is the sound level of the Kohler 200REZX?
The Kohler 200REZX is rated at 71.0 dBA at 23 m, per the manufacturer specification sheet.
What is the dry weight of the Kohler 200REZX?
The Kohler 200REZX has a dry weight of 2722 kg (6000 lb).
What voltage does the Kohler 200REZX produce?
The Kohler 200REZX is offered in 480 V, 3-phase-phase.
What size battery does the Kohler 200REZX need?
The Kohler 200REZX uses 2 batteryies, 12 V each, 925 CCA, per the manufacturer specification sheet.
Which alternator is fitted to the Kohler 200REZX?
The Kohler 200REZX uses a Fast-Response PMG alternator. Insulation class Class H.
Parts
19model family| Part # | Description | Qty | System | |
|---|---|---|---|---|
| G6-110 | Decision-Maker® Paralleling System (DPS) Spec Sheet | Spec sheet | Amazon eBay | |
| 11808000100 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
| 11808000200 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
| 11808000300 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
| G6-76 | Monitor III Software Spec Sheet | Service part / kit | Amazon eBay | |
| G6-79 | Monitor III Converter, Modbusr/Ethernet Spec Sheet | Service part / kit | Amazon eBay | |
| GM39515 | Vibration Isolators | 2 | Service part / kit | Amazon eBay |
| GM41122 | Vibration Isolators | 2 | Service part / kit | Amazon eBay |
| GM66019 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
| GM66020 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
| GM66022 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
| GM66023 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
| GM66024 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
| GM66025 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
| GM66304 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
| GM66313 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
| GM76149 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
| GM84038 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
| GM84954 | Vibration Isolator | 1 | Service part / kit | Amazon eBay |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 17.6 | 4.65 |
| Prime | 50% | 29.7 | 7.85 |
| Prime | 75% | 41.7 | 11.02 |
| Prime | 100% | 53.6 | 14.16 |
| Standby | 25% | 20.0 | 5.28 |
| Standby | 50% | 32.8 | 8.66 |
| Standby | 75% | 46.7 | 12.34 |
| Standby | 100% | 59.9 | 15.82 |
Available documents
This page was generated from the 9 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.