Home›Engines›General Motors Industrial Powertrain Vortec 5.0 L

General Motors Industrial Powertrain Vortec 5.0 L Engine

The General Motors Industrial Powertrain Vortec 5.0 L is a 5 L 8-cylinder natural engine rated at 1800 rpm, producing up to 66.4 kW. It powers generator sets from Kohler and SDMO, including the 48RCL, 48RCL-LPG, 48RCL-NG and 50REZG. It holds 4.7 L (1.2 gal) of oil and 17 L (4.5 gal) of coolant.

Also known as: General Motors Industrial Powertrain Vortec 5.0 L

5.0 L
Displacement
8
Cylinders
1800 rpm
Rated speed
66 kW
Gross power

Engine specifications

Oil capacity4.7 L
Coolant capacity17.0 L
Displacement5.0 L
Cylinders8
Aspirationnatural
Rated speed1800 rpm
Gross power66 kW

Generator sets powered by this engine

6

Shared across brands: Kohler, SDMO

Common problems

15
  • Does not crank
    Cause: Controller and Emergency Stop Switch
  • Cranks but does not start
    Cause: Controller and Emergency Stop Switch
  • Trailer is unstable or noisy during towing.
    Cause: Tire(s) worn or damaged
    Fix: Check tire condition. Repair or replace.
  • Starts hard
    Cause: Controller fault
    Fix: Troubleshoot the controller.
  • Lacks power
    Cause: Air cleaner clogged
    Fix: Clean or replace the filter element.
  • Overheats
    Cause: Governor inoperative
    Fix: Adjust the governor.
  • No or low output voltage
    Cause: Voltage regulation inoperative
    Fix: Replace the junction box sensing fuses. If the fuse blows again, troubleshoot the controller.
  • Stops suddenly
    Cause: Engine overload
    Fix: Reduce the electrical load. See the generator set spec sheet for wattage specifications.
  • Excessive or abnormal noise
    Cause: Vibration excessive
    Fix: Tighten loose components.
  • Tow vehicle and trailer are unstable or noisy during braking
    Cause: Tow vehicle brakes worn
    Fix: Check brake fluid level. Add fluid as necessary.
  • Duplex circuit breaker(s) tripped or trips when reset
    Cause: Circuit breaker overloaded
    Fix: Reduce circuit load. Reset duplex circuit breaker(s).
  • Voltage selector switch knob does not rotate.
    Cause: Padlock installed on lockout feature
    Fix: Contact onsite electrician or rental distributor.
  • Main circuit breaker(s) tripped or trips when reset
    Cause: Circuit breaker overloaded
    Fix: Reduce circuit load. Reset circuit breaker.
  • High fuel consumption
    Cause: Compression weak
    Fix: Check the compression.
  • Duplex receptacles have no power
    Cause: Generator set not running
    Fix: Power to duplex receptacles is from the generator set—not shore power.

Compiled from service & troubleshooting documentation across every generator set that uses the General Motors Industrial Powertrain Vortec 5.0 L.

Maintenance schedule

ItemSpecCapacityPart #Interval
Oil filterCartridgeGM16703 Amazon eBay $58.00 NAPA $3.59
Coolant20.8 L—
Oil6.2 L—

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

24
ItemActionHoursMonthsNotes
Engine oil levelCheck24 hrCheck the oil level in the crankcase every 24 hours of operation or before the engine is started each day
Air cleaner elementInspect100 hr
Change engine oil and filterChange100 hr
Check all bolts and nuts for tightnessCheck100 hr
Filter(s)Replace150 hr3 moService more frequently if operated in dusty areas
OilChange150 hr3 moEvery 150 Hours or 3 Months
Blow dust out of alternatorClean300 hr2 Yrs or 300 Hrs; service more frequently in dusty areas
Valve clearanceAdjust500 hr3 Yrs or 500 Hrs
Wire-cable insulation breakdownTest500 hr3 Yrs or 500 Hrs
Air cleaner elementReplace1000 hr
Belts and belt tensionCheck1000 hr
CoolantChange1500 hr1500 Hours
Engine coolantReplace5000 hr60 moWhen long-life coolant used
Alternator end bracket bearingReplace10000 hr20--300 kW models; prime power applications
Check coolant levelCheck0 mo
Check engine oil levelCheck0 mo
Check for fluid leaksCheck0 mo
Coolant temperature protection levelCheck6 moSix Months
Paralleling boxInspect12 moAnnually by a Kohler authorized distributor/dealer, or when wear, damage, deterioration, or malfunction is evident or suspected.
Paralleling box internal componentsInspect1 moMonthly or when a condition noticed during external inspection may have affected internal components; enclosure cover must be removed by trained personnel.
Safety and alarm operationCheck6 moSix Months
Safety and alarm operationTest6 moSix Months
Tighten DC electrical connectionsCheck6 moSix Months
Wheel lug nut torqueCheckFirst service — First 80/160 km (50/100 miles); then Quarterly or 3000 Miles

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
GapSpark plug gap0.51mm (0.02 in.)
GapSpark plug gap0.7--0.8mm (0.028--0.030 in.)
GapSpark plug gap0.76mm (0.03 in.)
GapSpark plug gap0.8--0.9mm (0.03--0.04 in.)
GapSpark plug gap0.89mm (0.035 in.)
GapSpark plug gap0.9--1.0mm (0.036--0.04 in.)
Other10 in. weld flange bolt circle diameter B361.95mm (14.25 in.)
Other10 in. weld flange outside diameter C406.4mm (16.0 in.)
Other10 in. weld flange quantity of bolts / bolt hole diameter D12, 25.40mm (1.00 in.)
Other12 in. weld flange bolt circle diameter B431.80mm (17.00 in.)
Other12 in. weld flange outside diameter C482.6mm (19.0 in.)
Other12 in. weld flange quantity of bolts / bolt hole diameter D12, 25.40mm (1.00 in.)
Other14 in. weld flange bolt circle diameter B476.25mm (18.75 in.)
Other14 in. weld flange outside diameter C533.4mm (21.0 in.)
Other14 in. weld flange quantity of bolts / bolt hole diameter D12, 28.58mm (1.13 in.)
Other16 in. weld flange bolt circle diameter B539.75mm (21.25 in.)
Other16 in. weld flange outside diameter C596.9mm (23.5 in.)
Other16 in. weld flange quantity of bolts / bolt hole diameter D16, 28.58mm (1.13 in.)
Other18 in. weld flange bolt circle diameter B577.85mm (22.75 in.)
Other18 in. weld flange outside diameter C635.0mm (25.0 in.)
Other18 in. weld flange quantity of bolts / bolt hole diameter D16, 31.75mm (1.25 in.)
Other20 in. weld flange bolt circle diameter B635.00mm (25.00 in.)
Other20 in. weld flange outside diameter C698.5mm (27.5 in.)
Other20 in. weld flange quantity of bolts / bolt hole diameter D20, 31.75mm (1.25 in.)
Other5 in. weld flange bolt circle diameter B215.90mm (8.50 in.)
Other5 in. weld flange outside diameter C241.30mm (9.50 in.)
Other5 in. weld flange quantity of bolts / bolt hole diameter D8, 22.23mm (0.88 in.)
Other6 in. weld flange bolt circle diameter B254.0mm (10.0 in.)
Other6 in. weld flange outside diameter C279.4mm (11.0 in.)
Other6 in. weld flange quantity of bolts / bolt hole diameter D8, 22.23mm (0.88 in.)
Other8 in. weld flange bolt circle diameter B298.45mm (11.75 in.)
Other8 in. weld flange outside diameter C342.9mm (13.5 in.)
Other8 in. weld flange quantity of bolts / bolt hole diameter D8, 22.23mm (0.88 in.)
OtherAlternator protection current/time limits200%: 40 seconds; 300%: 10 seconds; 425%: 5 seconds; 950%: 1 secondrated current percentage
OtherBattery specific gravity (charge threshold)1.215specific gravityat 26.7 C (80 F); charge if below
OtherBattery specific gravity (fully charged)1.260specific gravityat 26.7 C (80 F) electrolyte temperature
OtherController operating temperature range--40 to 70 C (--40 to 158 F)
OtherController power drain400 milliamps at 12V; 200 milliamps at 24V
OtherEngine speed adjustment50default setting; settings between 40 and 60 acceptable; 52 increases speed by 2 RPM, 49 decreases by 1 RPM
OtherGaseous fuel tank maximum safe fill level80% of total fuel tank volume
OtherGenerator to bus phase angle-10 to 10degreesverify with contactor closed
OtherLP gas fuel system leak test pressure6--8 ounces per square inch (10--14 inches water column)oz/in2 (in. water column)test pressurized
OtherReactive droop1%default setting; range 0.5 - 2%
OtherWeld flange angle A (10, 12, 14 in. nominal pipe size)30deg.
OtherWeld flange angle A (16, 18, 20 in. nominal pipe size)22.5deg.
OtherWeld flange angle A (5, 6, 8 in. nominal pipe size)45deg.
OtherWheel stud size1/2-20
PressureFuel tank pressure relief valve (close)1937--2130kPa (281--309 psi)
PressureFuel tank pressure relief valve (open)2151kPa (312 psi) min
PressureLPG vapor fuel supply pressure1.24-2.74kPaat inlet
PressureNatural gas fuel supply pressure1.74-2.74kPaat inlet
PressureTire inflation pressure @ rated load552 (80 psi)kPa (psi)
SpeedOverfrequency default setting110% of nominal%
SpeedOverfrequency setting range102%--140% of nominal%
SpeedOverfrequency time delay10sec
SpeedUnderfrequency default setting90% of nominal%
SpeedUnderfrequency setting range80%--95% of nominal%
SpeedUnderfrequency time delay10 (short term), 60 (long term)sec
TemperatureBlock heater thermostat cut-off temperature27--38°Ccoolant temperature
TemperatureBlock heater thermostat cut-off temperature80--100°Fcoolant temperature

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50% ethylene glycol0.6 LProvides freezing protection to --37_C (--34_F) and overheating protection to 129_C (265_F). Do not use alcohol or methanol antifreeze. Coolant added after block heater installation is approximately 0.6 L (0.2 gal).
CoolantLong-life coolantChange interval 5000 hours or 5 years when long-life coolant used; do not mix coolant types
Engine oilSAE 5W-30API Starburst (for gasoline engines)below -18°C4.7 LFor below -18C (0F)
Engine oilSAE 10W-30API Starburst (for gasoline engines)above -18°C4.7 LFor -18C (0F) and above; CC/CD classification and straight-weight industrial/stationary oils not acceptable
GreaseLithium complexAxle bearing grease type
GreaseMultipurpose greaseLubricate trailer hitch/coupler contact points
GreasePetroleum jelly, silicon grease, or other nonconductive greaseCoat battery terminals after reconnecting
GreaseWhite lithium greaseApply a small amount behind the brake shoe where it rubs against the backing plate

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

66
CodeNameMeaningSeverityAction
AC Sens LostAC Sensing LostIn Auto mode, generator output AC sensing is lost; starts 10 seconds after crank disconnect. Warning after 1 second if no output detected after crank disconnect; shutdown after 3 seconds if voltage was present and then lost.WarningContact an authorized distributor/dealer for service.
AC Sensing LostWarning
Accy PwrOverAccessory Power OverloadOver current fault on the accessory controller power outputWarning
Accy PwrOver WarningAccessory Power OverloadAn over current fault (short circuit) on the accessory controller power output.WarningContact an authorized distributor/dealer for service.
Alt Protect ShtdwnAlternator Protection ShutdownHigh generator current detected; shuts down to protect alternator windings from overheating (38RCL only).ShutdownReduce the load.
Alternator ProtectionShutdown
ATS Com ErrorATS Communication ErrorWarning is displayed if RXT interface connection is lost.WarningCheck communication wiring between transfer switch interface board and generator set.
ATS PhaseRotATS Phase Rotation MismatchTransfer switch phase rotation does not match; ATS will not transfer.WarningCorrect the ATS connection per the ATS Installation manual, wiring diagrams, and labels on the transfer switch.
Aux InputAuxiliary InputAn optional customer-connected input is closed (digital input from optional PIM).ShutdownCheck customer-supplied equipment.
Auxiliary InputWarning
Avg CurrentHighWarning
Avg Gen Voltage L-LLowWarning
Batt Chg FltBattery Charger FaultInput to PIM from an external battery charger (not the built-in charger).WarningCheck external battery charger.
Battery Charger FaultWarning
Battery Voltage HighBattery Voltage HighEngine starting battery voltage rises above 125% of the battery voltage setting for more than 10 seconds; inhibited during crank cycle.WarningCheck the battery rating and condition; check the battery charger operation.
Battery Voltage LowBattery Voltage LowEngine starting battery voltage falls below the battery voltage setting (typically 12.5 volts) for more than 90 seconds when engine not running; inhibited during crank cycle.WarningCheck the battery rating and condition; check the battery charger operation; charge or replace the battery.
Cabinet Intrusion AlarmWarning
CAN comm faultCAN Communications FaultEngine CAN communications fault.ShutdownCheck wiring to ECM; check power to ECM.
Coolant PressureLowWarning
Cranking VoltageLowWarning
ECM Communication LossShutdown
ECM Model MismatchShutdown
Electrical Metering Communication LossShutdown
Emergency StopShutdown
Engine Coolant LevelLowShutdown
Engine Coolant TemperatureLowWarning
Engine Coolant Temperature HighEngine Coolant Temperature HighEngine coolant temperature exceeds the maximum temperature for more than 5 seconds; active after crank disconnect.ShutdownCheck for blocked air inlets and exhaust outlets.
Engine Derate ActiveWarning
Engine Fuel LevelLowWarning
Engine Oil LevelLowWarning
Engine Oil PressureShorted HighWarning
Engine Oil Pressure LowEngine Oil Pressure LowEngine ECM indicates low oil pressure for more than 5 seconds; active 30 seconds after crank disconnect.ShutdownCheck for leaks in the lubrication system; check the oil level and add oil if low.
EngineSpeed HighEngine Speed HighEngine speed exceeds 115% of normal running speed for more than 0.3 seconds.ShutdownContact an authorized distributor/dealer for service.
EngineSpeed LowEngine Speed LowEngine speed drops below 85% of normal running speed for more than 3 seconds.ShutdownReduce the load; contact an authorized distributor/dealer for service.
Exer Not SchExercise Not ScheduledNo exercise has been scheduled on the RDC2 controller.WarningSee exerciser setup instructions.
Failure To SynchronizeWarning
Fuel PressureLowWarning
Fuel Tank LeakWarning
Fuel TemperatureHighWarning
Gen Battery VoltageLowWarning
Generator FrequencyLowWarning
Generator Frequency HighGenerator Frequency HighGoverned frequency exceeds 110% of the system's frequency setpoint for more than 10 seconds; active 10 seconds after engine start.ShutdownContact an authorized distributor/dealer for service.
Generator Frequency LowGenerator Frequency LowGoverned frequency falls below 90% of system frequency setting for more than 10 seconds, or 1 Hz below setting for more than 60 seconds; active 10 seconds after engine start.ShutdownReduce the load and restart the generator set; contact an authorized distributor/dealer for service.
Generator Voltage L1-L2LowShutdown
Generator VoltageL1-L2 HighGenerator Voltage HighOutput voltage exceeds 120% of the system nominal voltage for more than 2 seconds.ShutdownContact an authorized distributor/dealer for service.
Generator VoltageL1-L2 LowGenerator Voltage LowOutput voltage falls below 80% of the nominal system voltage for more than 10 seconds.ShutdownReduce the load and restart the generator set; contact an authorized distributor/dealer for service.
Ground Fault InputWarning
Injector Wiring FaultWarning
Intake Air TemperatureHighWarning
Lo Crank VltLow Cranking VoltageBattery voltage falls below 60% of system battery voltage for more than 6 seconds while the starter is engaged.WarningCharge or replace the battery.
Locked RotorLocked RotorNo engine rotation is sensed during cranking; shuts down 3 seconds after the fault is detected.ShutdownCheck the battery; check for loose connections; contact an authorized distributor/dealer for service.
MainPwrOverL ShutdownMain Power OverloadAn over current fault on the controller power output (short circuit).ShutdownContact an authorized distributor/dealer for service.
Maximum Alternator CurrentLowShutdown
Not in AutoNot in Automatic ModeThe generator set is not in Automatic (standby) mode; remote start/stop commands from a transfer switch or remote switch will be ignored.WarningPress AUTO to place the generator set in Automatic mode, when appropriate.
Not In AutoWarning
Over CrankOver CrankThree unsuccessful starting attempts.ShutdownCheck the fuel supply, spark plug, and battery; check for loose connections; contact an authorized distributor/dealer for service.
Reserve Oil EmptyWarning
Run Relay Coil OverloadShutdown
Speed Sensor FaultSpeed Sensor FaultEngine speed sensor has failed or engine stalled.ShutdownContact an authorized distributor/dealer for service.
Starter Relay Coil OverloadShutdown
System FrequencyHighWarning
System VoltageHighWarning
Total Power (Generator Total Real Power)LowWarning
Total Power High ShtDwnTotal Power High ShutdownMeasured load is greater than 102% of the generator set power rating for more than 1 minute (38RCL only).ShutdownReduce the load.
Total Reactive PowerLowWarning
Water In FuelWarning

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Calibration adjustment

⚠ Copying personality profiles from one controller to another can overwrite calibration coefficients and requires re-calibration.

Tools: Calibrated multimeter with recent calibration verification

  1. Use a calibrated multimeter to measure the generator voltage and enter the correct value in the CONTROLLER CONFIG -> CALIBRATION screen.
  2. Use a calibrated multimeter to measure the bus voltage and enter the correct value in the CONTROLLER CONFIG -> CALIBRATION screen.
Electric Brake Adjustment adjustment

⚠ Never use compressed air to clean brake components; some components may contain asbestos.

Tools: Adjustment tool or large slotted screwdriver, Jack stands

  1. Raise the trailer with wheels off the ground and block safely with jack stands; remove the wheel.
  2. Remove the rubber plug from the backing plate slot.
  3. Insert an adjustment tool or large slotted screwdriver in the slot and rotate the star wheel to expand the shoe against the drum.
  4. Expand the shoe until the drum can't be turned by hand to center each shoe.
  5. Back off the adjustment in the other direction until the drum turns freely with slight resistance.
  6. Replace the rubber plug in the backing plate slot.
  7. Repeat procedure for remaining wheels.
RDC2 Voltage Calibration Using SiteTech adjustment

Tools: digital voltmeter, personal computer, SiteTech software

  1. Connect PC to controller via USB
  2. With generator off, connect multimeter across L1/L2 (AC volts)
  3. Start generator set
  4. Compare voltmeter reading to controller display
  5. Calculate new Genset Calibration Factor Voltage using (Vmeter / Vcontrol) x Fold = Fnew
  6. Enter new value into SiteTech and click Apply Changes
  7. Verify voltmeter matches controller display
  8. Repeat for L2-L3 and L3-L1 if three-phase
  9. Press OFF to stop generator set
RDC2 Voltage Calibration Using the Controller Keypad adjustment

Tools: digital voltmeter

  1. With generator off, connect digital multimeter across L1 and L2, set to AC volts
  2. Start generator set with RUN button
  3. Navigate to Generator Metering menu, press Select; Volts L1-L2 displayed
  4. Press Select; voltage number flashes
  5. Use up/down arrows to match voltmeter reading
  6. Press Select to confirm
  7. Step to Return screen
  8. Press OFF to stop generator set
VSC Current (Load) Calibration Using the Controller Keypad adjustment

Tools: clamp-on DC current probe or DC current meter

  1. Connect DC current probe/clamp meter to measure generator current
  2. Start generator with RUN button
  3. Adjust system voltage to obtain rated current output with battery bank attached (or use load bank)
  4. Trip output breaker
  5. Navigate to Generator Metering menu, select Generator Load
  6. Press and hold Select for No-Load Calibration; verify breaker open, confirm Yes
  7. Close output breaker; verify rated output current, confirm Yes
  8. Verify displayed load is correct; recalibrate if necessary
  9. Press OFF to stop generator set
Obtain DC2 Controller Password and Serial Number diagnostic
  1. Press OFF and verify that the generator set is not running.
  2. Press and hold the Exercise button until Press Again to Reset OnCue Plus PW is displayed.
  3. Release the Exercise button and press it again within 5 seconds.
  4. Write down the serial number (S/N) and password.
Obtain RDC/DC Controller Password diagnostic
  1. Press OFF to place the controller into OFF mode.
  2. Press the down arrow button (RDC) or exercise button (DC) 5 times.
  3. Note the four-digit code displayed on the controller; this is the controller password.
  4. Write down the password and press OFF to clear the display.
Obtain RDC2 or VSC Controller Password and Serial Number diagnostic
  1. Press the controller down arrow button to navigate to the Networking Information menu.
  2. Follow the reset password procedure shown in Figure 1-3.
  3. Write down the serial number (S/N) and password displayed for 10 seconds.
Power Cycle the Controller diagnostic
  1. Disconnect all input power for two minutes to allow capacitors to discharge.
  2. Remove the battery negative cable or disconnect P1 from the back of the controller.
  3. Disconnect the battery charger 120 VAC input power supply or disconnect P5 from the back of the controller.
  4. Unplug the USB mini-B connector from the front of the controller if plugged in.
  5. Wait two minutes, then reconnect power, hooking up battery power (P1) first.
Procedure to Reset the Controller after a Fault Shutdown diagnostic

⚠ Always identify and correct the cause of a fault shutdown before resetting the controller.

  1. Press the Select button to go to the Overview menu.
  2. Press Select again to display the active fault.
  3. Press Select; Confirm Clear Fault: NO is displayed.
  4. Press the Up arrow button; Confirm Clear Fault: YES is displayed.
  5. Press the Select button to enter YES and clear the fault.
  6. Press the Select button to return to the overview menu.
  7. Press AUTO to put the generator set into automatic mode.
Use Telnet to Check Server Connection diagnostic

Tools: Command prompt, Telnet Client

  1. Activate Telnet Client on the computer if necessary.
  2. Open a command prompt window.
  3. Enter telnet devices.kohler.com 5253.
  4. Successful connection displays the symbols shown in Figure 3-8.
Verify Generator Operation diagnostic

⚠ Generators must all operate at the same frequency, voltage, and phase connection in order to parallel.

Tools: SiteTech software

  1. Ensure the load is not connected or is drawing less power than a single generator can provide.
  2. Navigate to CONTROLLER CONFIG -> COMMUNICATION SETUP and verify PGEN Nodes Online indicates the correct number of nodes.
  3. Verify alternator connection (voltage selector switch position), system voltage, and voltage regulator target on each generator.
  4. Start a single generator by pressing the Run button; the paralleling box contactor should close and the Generator Connected to Bus indicator should light.
  5. Verify bus and generator voltages match and generator to bus phase angle is between -10 and 10 degrees.
  6. Verify the load bus is energized and available at the load.
  7. Stop the generator by pressing the OFF button; the contactor should open.
  8. Repeat for each generator in the paralleling system.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
12-LeadAlternator Reconnections diagram ADV-5875B-M (page 16)
12-lead optional voltage connections12Alternator optional feature
4-LeadAlternator Reconnections diagram ADV-5875A-M (page 15)
4-lead dedicated voltages4Alternator standard feature
1Camlocks (left to right)Green=GND; White=L0; Black=L1; Red=L2Single-phase uses four camlocks
3Camlocks (left to right)Green=GND; White=L0; Black=L1; Red=L2; Blue=L3Three-phase uses all five camlocks
100/2001Single
100/2003Delta
110/127/139/240/254/277single-phaseswitchableTowable generator model specifications; some models n/a
110/2201Single
110/2203Delta
115/2301Single
1201SingleGenset System Voltage/Frequency/Phase table for controller setup
120/20834P7BX 12-lead12Three-phase
120/2083Low wyeL0-L1: 120; L1-L2: 208; L1-L3: 208; L2-L3: 208Voltage selector switch position Low wye; selector switch factory set Pos. 2 Volts 120/208, 60 Hz, Three Phase Wye
120/2083Wye
120/24014Q7BX 4-lead4Single-phase
120/2401Single
120/2401Single-phaseL0-L1: 120; L1-L2: 240Voltage selector switch position Single-phase; selector switch factory set Pos. 3 Volts 120/240, 60 Hz, Single Phase Dogleg (3-position switch only)
120/2403Delta
127/22034P7BX 12-lead12Three-phase
127/2203Wye
208/220/240/415/440/4803-phasereconnectableTowable generator model specifications
208/220/240/415/440/4803-phaseswitchableTowable generator model specifications
2201Single
220/3803Wye
2301Single
230/4003Wye
2401Single
240/4163Wye

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the General Motors Industrial Powertrain Vortec 5.0 L?

The General Motors Industrial Powertrain Vortec 5.0 L engine has an oil capacity of 4.7 liters.

What is the displacement of the General Motors Industrial Powertrain Vortec 5.0 L?

The General Motors Industrial Powertrain Vortec 5.0 L has a displacement of 5.0 liters with 8 cylinders.

Which generators use the General Motors Industrial Powertrain Vortec 5.0 L engine?

The General Motors Industrial Powertrain Vortec 5.0 L powers 6 generator set(s), including Kohler 48RCL, Kohler 48RCL-LPG, Kohler 48RCL-NG, Kohler 50REZG, Kohler 50RZG.

What is a common problem with the General Motors Industrial Powertrain Vortec 5.0 L engine?

A commonly reported issue on generators using the General Motors Industrial Powertrain Vortec 5.0 L is: Does not crank. Cause: Controller and Emergency Stop Switch.