Specifications
| Fuel | diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 2060 kW |
| Standby kVA | 2575 |
| Prime power | 1850 kW |
| Emissions | Tier 2 |
| Controller | Decision-Maker 550, Decision-Maker 6000 |
| Oil capacity | 300.0 L |
| Alternator | Fast-Response PMG (Class Class H insulation) |
| Voltage options | 480 V |
| Phase | 3-phase |
| Power factor | 0.8 |
| Battery cranking | 1150 CCA |
| Battery voltage | 12 V |
| Battery quantity | 4 |
| Coolant capacity | 623.0 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 6905×2232×2564 mm |
Engine
| Oil capacity | 300.0 L |
|---|---|
| Coolant capacity | 260.0 L |
| Displacement | 76.3 L |
| Aspiration | Exhaust turbocharging (ETC) and charge air cooling (CAC) |
| Rated speed | 1800 rpm |
Filters for the MTU 16V 4000 G43
1Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Fuel / water separator | P552006 | Fuel Filter, Water Separator Spin-On Twist&Drain | MTU 4202934, NAPA 3645, BALDWIN BF1262, SISU 1273400331 | FridayParts $42.88 |
Same engine, other brands
2 brandsThe MTU 16V 4000 G43 in this set also powers 6 generator sets sold under 2 other brands. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| MTU | 16 V 4000 G43, 16V4000 DS2000, DP 1900 D6S RW, DS 2185 D6S RW, HMW 1975 T6 |
| Hipower | HMW 1975 T6 |
Maintenance & consumables
for the MTU 16V 4000 G43| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Medium duty - double cartridge | — | |||
| Fuel filter | Secondary 8 Microns @ 98% Efficiency | — | |||
| Oil filter | Medium duty - double cartridge | — | |||
| Battery | 24 V | — | |||
| Belt | N/A | — | |||
| Coolant filter | N/A | — | |||
| Spark plug | N/A | — |
Service specifications
30| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | 10 in. weld flange bolt circle diameter B | 361.95 | mm (14.25 in.) | |
| Other | 10 in. weld flange outside diameter C | 406.4 | mm (16.0 in.) | |
| Other | 10 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 12 in. weld flange bolt circle diameter B | 431.80 | mm (17.00 in.) | |
| Other | 12 in. weld flange outside diameter C | 482.6 | mm (19.0 in.) | |
| Other | 12 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 14 in. weld flange bolt circle diameter B | 476.25 | mm (18.75 in.) | |
| Other | 14 in. weld flange outside diameter C | 533.4 | mm (21.0 in.) | |
| Other | 14 in. weld flange quantity of bolts / bolt hole diameter D | 12, 28.58 | mm (1.13 in.) | |
| Other | 16 in. weld flange bolt circle diameter B | 539.75 | mm (21.25 in.) | |
| Other | 16 in. weld flange outside diameter C | 596.9 | mm (23.5 in.) | |
| Other | 16 in. weld flange quantity of bolts / bolt hole diameter D | 16, 28.58 | mm (1.13 in.) | |
| Other | 18 in. weld flange bolt circle diameter B | 577.85 | mm (22.75 in.) | |
| Other | 18 in. weld flange outside diameter C | 635.0 | mm (25.0 in.) | |
| Other | 18 in. weld flange quantity of bolts / bolt hole diameter D | 16, 31.75 | mm (1.25 in.) | |
| Other | 20 in. weld flange bolt circle diameter B | 635.00 | mm (25.00 in.) | |
| Other | 20 in. weld flange outside diameter C | 698.5 | mm (27.5 in.) | |
| Other | 20 in. weld flange quantity of bolts / bolt hole diameter D | 20, 31.75 | mm (1.25 in.) | |
| Other | 5 in. weld flange bolt circle diameter B | 215.90 | mm (8.50 in.) | |
| Other | 5 in. weld flange outside diameter C | 241.30 | mm (9.50 in.) | |
| Other | 5 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 6 in. weld flange bolt circle diameter B | 254.0 | mm (10.0 in.) | |
| Other | 6 in. weld flange outside diameter C | 279.4 | mm (11.0 in.) | |
| Other | 6 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 8 in. weld flange bolt circle diameter B | 298.45 | mm (11.75 in.) | |
| Other | 8 in. weld flange outside diameter C | 342.9 | mm (13.5 in.) | |
| Other | 8 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | Weld flange angle A (10, 12, 14 in. nominal pipe size) | 30 | deg. | |
| Other | Weld flange angle A (16, 18, 20 in. nominal pipe size) | 22.5 | deg. | |
| Other | Weld flange angle A (5, 6, 8 in. nominal pipe size) | 45 | deg. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12-lead optional voltage connections | 12 | Alternator optional feature | ||
| 4-lead dedicated voltages | 4 | Alternator standard feature | ||
| 110/127/139/240/254/277 | single-phase | switchable | Towable generator model specifications; some models n/a | |
| 208/220/240/415/440/480 | 3-phase | reconnectable | Towable generator model specifications | |
| 208/220/240/415/440/480 | 3-phase | switchable | Towable generator model specifications |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the Kohler 2000REOZDD?
The Kohler 2000REOZDD is rated 2060 kW standby (2575.0 kVA).
What engine is in the Kohler 2000REOZDD?
The Kohler 2000REOZDD is powered by the MTU 16V 4000 G43 engine.
Is the Kohler 2000REOZDD diesel or gas?
The Kohler 2000REOZDD runs on diesel.
How much oil does the Kohler 2000REOZDD take?
The MTU 16V 4000 G43 engine in the Kohler 2000REOZDD has an oil capacity of 300.0 liters.
How much coolant does the Kohler 2000REOZDD hold?
The Kohler 2000REOZDD cooling system holds 623 liters (164.6 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the prime power rating of the Kohler 2000REOZDD?
The Kohler 2000REOZDD is rated 1850 kW prime (2313 kVA), against 2060 kW standby.
What voltages is the Kohler 2000REOZDD available in?
The Kohler 2000REOZDD is offered in 480 V, 3-phase-phase.
How many cold cranking amps does the Kohler 2000REOZDD require?
The Kohler 2000REOZDD uses 4 batteryies, 12 V each, 1150 CCA, per the manufacturer specification sheet.
What alternator does the Kohler 2000REOZDD use?
The Kohler 2000REOZDD uses a Fast-Response PMG alternator. Insulation class Class H.
Parts
16model family| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 279720 | Hose, hump | 4 | Hose | Amazon |
| 279736 | Element, primary | 2 | Air filter | Amazon eBay NAPA $228.15 |
| 279737 | Element, secondary | 2 | Air filter | Amazon eBay |
| 279738 | Element, primary | 1 | Air filter | Amazon eBay KuduParts $248.00 |
| 279739 | Element, air cleaner, inner | 1 | Air filter | Amazon eBay FridayParts $165.75 |
| 347957 | Hose, 45 deg elbow, 8.00 in. ID | 1 | Hose | buy |
| GM23518 | Hose, hump, 8.00 in. ID | 1 | Hose | buy |
| GM23519 | Hose, 90 deg elbow, 8.00 in. ID | 1 | Hose | buy |
| GM24553 | Alternator Belt | Belt | Amazon eBay | |
| GM28302 | Hose, straight air, 8.00 in. ID | 1 | Hose | buy |
| GM30213 | Thermostat | Thermostat | eBay | |
| GM35390 | Seal | Seal | eBay $27.99 | |
| GM51785 | Alternator Belt | Belt | Amazon eBay | |
| GM64086 | Alternator Belt | Belt | Amazon eBay | |
| GM69997 | Element, Primary (Outer) | 1 | Air filter | Amazon eBay $108.80 |
| GM69998 | Element, Secondary (Inner) | 1 | Air filter | Amazon eBay $66.30 |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 153.2 | 40.5 |
| Prime | 50% | 265.9 | 70.2 |
| Prime | 75% | 382.8 | 101.1 |
| Prime | 100% | 488.9 | 129.2 |
| Standby | 25% | 170.9 | 45.2 |
| Standby | 50% | 300.1 | 79.3 |
| Standby | 75% | 428.0 | 113.1 |
| Standby | 100% | 559.9 | 147.9 |
Available documents
This page was generated from the 4 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.