HomeMTUMTU 16V4000 DS2000

MTU 16V4000 DS2000 Generator Set

The MTU 16V4000 DS2000 is a 2000 kW (2500 kVA) diesel standby generator set powered by a MTU 16V4000G14S engine. It is available at 380 V, 416 V, 440 V, 480 V, 600 V, 4160 V, 1247 V, 1320 V and 1380 V, 3-phase, 60 Hz and rated 3419 A. It holds about 300 L (79.3 gal) of oil and 547 L (144.5 gal) of coolant, with a maximum ambient rating of 45 °C. Starting uses 4 group-8 batteries rated 2800 CCA at 24 V. The set measures 6432×2338×3191 mm (253.2×92.0×125.6 in), weighs about 20720 kg (45680 lb) and produces 98.6 dBA at 7 m.

2000 kW
Standby
76.3 L
Displacement
300.0 L
Oil capacity
2
Document types

How to read your MTU serial & model number →

Specifications

Fueldiesel
Frequency60.0 Hz
Standby power2000 kW
Standby kVA2500
Prime power1825 kW
EmissionsTier 2
Oil capacity300.0 L
Voltage options380 V, 416 V, 440 V, 480 V, 600 V, 4160 V, 1247 V, 1320 V, 1380 V
Phase3
Rated current[3419, 2706, 2165, 312, 104, 98, 94] A
Power factor0.8
Battery group8D
Battery cranking2800 CCA
Battery voltage24 V
Battery quantity4
Coolant capacity547 L
Max ambient45 °C
Dimensions (L×W×H)6432×2338×3191 mm
Dry weight20720 kg
Sound level98.6 dBA @ 7 m

Engine

MTU 16V4000G14S
Oil capacity300.0 L
Coolant capacity175.0 L
Displacement76.3 L
Aspiration4-Cycle
Rated speed1800 rpm

Common questions

What is the power rating of the MTU 16V4000 DS2000?

The MTU 16V4000 DS2000 is rated 2000 kW standby (2500.0 kVA).

What engine does the MTU 16V4000 DS2000 use?

The MTU 16V4000 DS2000 is powered by the MTU 16V4000G14S engine.

What fuel does the MTU 16V4000 DS2000 use?

The MTU 16V4000 DS2000 runs on diesel.

What is the oil capacity of the MTU 16V4000 DS2000?

The MTU 16V4000G14S engine in the MTU 16V4000 DS2000 has an oil capacity of 300.0 liters.

Fuel consumption

RatingLoadL/hgal/h
Prime
Prime50%265.069.9
Prime75%381.0100.7
Prime100%487.0128.6
Standby
Standby50%299.078.9
Standby75%426.0112.6
Standby100%558.0147.3

Available documents

Brochure — 16120643 PowerGeneration Solutionguide 1 2020 (MTU)Spec sheet — 231151 PG Spec 16V4000DS2000G04 2000kW 3D T2 SCAQMD 60Hz 50C (MTU)Spec sheet — 231158 PG Spec 16V4000DS2000G04 1825kW 3F T2 SCAQMD 60Hz 50C (MTU)Spec sheet — 231205 PG Spec 16V4000DS2000G04 2000kW 3D T2 SCAQMD 60Hz 45C (MTU)Spec sheet — 231206 PG Spec 16V4000DS2000G04 2000kW 3D FC 60Hz 45C (MTU)Spec sheet — 231207 PG Spec 16V4000DS2000G04 2000kW 3D FC 60Hz 50C (MTU)Spec sheet — 231232 PG Spec 16V4000DS2000G04 1825kW 3F T2 SCAQMD 60Hz 45C (MTU)Spec sheet — 231233 PG Spec 16V4000DS2000G04 1825kW 3F FC 60Hz 45C (MTU)Spec sheet — 231234 PG Spec 16V4000DS2000G04 1825kW 3F FC 60Hz 50C (MTU)Spec sheet — EngineersGuidebook (MTU)Spec sheet — EngineersGuidebookUpdate102017 (MTU)Spec sheet — MTU-Engineers-Guidebook-2014 (MTU)Spec sheet — MTU16V4000DS2000 1800kW Prime (MTU)Spec sheet — MTU16V4000DS2000 1825kW DCCP (MTU)Spec sheet — MTU16V4000DS2000 2000kW Standby (MTU)Spec sheet — MTU 16V4000 DS2000 2000kW Standby (MTU)Spec sheet — mtu4000-16v-ds2000-dccp (MTU)