Specifications
| Fuel | diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 2000 kW |
| Standby kVA | 2500 |
| Prime power | 1825 kW |
| Emissions | EPA Tier 2 |
| Controller | Digital Control Panel |
| Oil capacity | 300.0 L |
| Voltage options | 380 V, 416 V, 440 V, 480 V, 600 V, 4160 V, 1247 V, 1320 V, 1380 V |
| Phase | 3 |
| Rated current | [3419, 2706, 2165, 312, 104, 98, 94] A |
| Power factor | 0.8 |
| Battery group | 8D |
| Battery cranking | 2800 CCA |
| Battery voltage | 24 V |
| Battery quantity | 4 |
| Coolant capacity | 547 L |
| Max ambient | 45 °C |
| Dimensions (L×W×H) | 6432×2338×3191 mm |
| Dry weight | 21554 kg |
| Sound level | 98.6 dBA @ 7 m |
Engine
| Oil capacity | 300.0 L |
|---|---|
| Coolant capacity | 175.0 L |
| Displacement | 76.3 L |
| Aspiration | 4-cycle |
| Rated speed | 1800 rpm |
Filters for the MTU 16V4000G14S
1Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Fuel / water separator | P552006 | Fuel Filter, Water Separator Spin-On Twist&Drain | MTU 4202934, NAPA 3645, BALDWIN BF1262, SISU 1273400331 | FridayParts $42.88 |
Maintenance & consumables
for the MTU 16V4000G14S| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Medium duty - double cartridge | — | |||
| Fuel filter | Secondary 8 Microns @ 98% Efficiency | — | |||
| Oil filter | Medium duty - double cartridge | — | |||
| Battery | 24 V | — | |||
| Belt | N/A | — | |||
| Coolant filter | N/A | — | |||
| Spark plug | N/A | — |
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | Diesel #2 | Recommended Fuel for diesel gensets (e.g. DS30, DS40, DS50, DS80, DS100, DS125, DS150, DS180, DS200, DS230, DS250, DS275, DS300, DS350, DS400, DS450, DS500) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 208V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 240V | 1 | 12 LEAD | Example from MTU 4R0063 GS30 SYSTEM RATINGS connection row | |
| 240V | 1 | 4 LEAD | Example from MTU 4R0063 GS30 | |
| 240V | 3 | 12 LEAD DELTA | Example from MTU 4R0063 GS30 | |
| 380V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 480V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 600V | 3 | 4 LEAD WYE DOUBLE DELTA | Example from MTU 4R0063 GS30 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the MTU 16V4000 DS2000?
The MTU 16V4000 DS2000 is rated 2000 kW standby (2500.0 kVA).
Which engine powers the MTU 16V4000 DS2000?
The MTU 16V4000 DS2000 is powered by the MTU 16V4000G14S engine.
What fuel does the MTU 16V4000 DS2000 use?
The MTU 16V4000 DS2000 runs on diesel.
How much oil does the MTU 16V4000 DS2000 take?
The MTU 16V4000G14S engine in the MTU 16V4000 DS2000 has an oil capacity of 300.0 liters.
How much coolant does the MTU 16V4000 DS2000 hold?
The MTU 16V4000 DS2000 cooling system holds 547 liters (144.5 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the MTU 16V4000 DS2000?
The MTU 16V4000 DS2000 is rated 1825 kW prime (2281 kVA), against 2000 kW standby.
How loud is the MTU 16V4000 DS2000?
The MTU 16V4000 DS2000 is rated at 98.6 dBA at 7 m, per the manufacturer specification sheet.
How much does the MTU 16V4000 DS2000 weigh?
The MTU 16V4000 DS2000 has a dry weight of 21554 kg (47518 lb).
What voltage does the MTU 16V4000 DS2000 produce?
The MTU 16V4000 DS2000 is offered in 380 V, 416 V, 440 V, 480 V, 600 V, 4160 V, 3-phase.
How many cold cranking amps does the MTU 16V4000 DS2000 require?
The MTU 16V4000 DS2000 uses 4 batteryies, 24 V each, 2800 CCA, group 8D, per the manufacturer specification sheet.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 30.4 | 8.03 |
| Prime | 75% | 42.5 | 11.23 |
| Prime | 100% | 56.1 | 14.82 |
| Standby | 558.0 | 147.3 | |
| Standby | 50% | 5.2 | 1.4 |
| Standby | 75% | 7.5 | 2.0 |
| Standby | 100% | 9.9 | 2.6 |
Available documents