HomeEnginesPower Solutions International 8.8L Industrial Powertrain

Power Solutions International 8.8L Industrial Powertrain Engine

The Power Solutions International 8.8L Industrial Powertrain is a 8.8 L -8-cylinder turbo charge air cooled engine rated at 1800 rpm, producing up to 193 kW. It powers generator sets from Cummins/Onan and Kohler, including the GFPA, 125ERES, 125REZGC and 125REZGT. It holds 7.6 L (2.0 gal) of oil and 13.7 L (3.6 gal) of coolant.

Also known as: PSI 8.8L Industrial Powertrain

8.8 L
Displacement
-8
Cylinders
1800 rpm
Rated speed
193 kW
Gross power

Engine specifications

Oil capacity7.6 L
Coolant capacity13.7 L
Displacement8.8 L
Cylinders-8
AspirationTurbo Charge Air Cooled
Rated speed1800 rpm
Gross power193 kW

Generator sets powered by this engine

5

Shared across brands: Cummins/Onan, Kohler

Maintenance schedule

ItemSpecCapacityPart #Interval
Oil filter
CoolantClosed-Loop Radiator System49.2 L
Oil8.5 L

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

2
ItemActionHoursMonthsNotes
Paralleling boxInspect12 moAnnually by a Kohler authorized distributor/dealer, or when wear, damage, deterioration, or malfunction is evident or suspected.
Paralleling box internal componentsInspect1 moMonthly or when a condition noticed during external inspection may have affected internal components; enclosure cover must be removed by trained personnel.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

43
TypeItemValueUnitCondition
Other10 in. weld flange bolt circle diameter B361.95mm (14.25 in.)
Other10 in. weld flange outside diameter C406.4mm (16.0 in.)
Other10 in. weld flange quantity of bolts / bolt hole diameter D12, 25.40mm (1.00 in.)
Other12 in. weld flange bolt circle diameter B431.80mm (17.00 in.)
Other12 in. weld flange outside diameter C482.6mm (19.0 in.)
Other12 in. weld flange quantity of bolts / bolt hole diameter D12, 25.40mm (1.00 in.)
Other14 in. weld flange bolt circle diameter B476.25mm (18.75 in.)
Other14 in. weld flange outside diameter C533.4mm (21.0 in.)
Other14 in. weld flange quantity of bolts / bolt hole diameter D12, 28.58mm (1.13 in.)
Other16 in. weld flange bolt circle diameter B539.75mm (21.25 in.)
Other16 in. weld flange outside diameter C596.9mm (23.5 in.)
Other16 in. weld flange quantity of bolts / bolt hole diameter D16, 28.58mm (1.13 in.)
Other18 in. weld flange bolt circle diameter B577.85mm (22.75 in.)
Other18 in. weld flange outside diameter C635.0mm (25.0 in.)
Other18 in. weld flange quantity of bolts / bolt hole diameter D16, 31.75mm (1.25 in.)
Other20 in. weld flange bolt circle diameter B635.00mm (25.00 in.)
Other20 in. weld flange outside diameter C698.5mm (27.5 in.)
Other20 in. weld flange quantity of bolts / bolt hole diameter D20, 31.75mm (1.25 in.)
Other5 in. weld flange bolt circle diameter B215.90mm (8.50 in.)
Other5 in. weld flange outside diameter C241.30mm (9.50 in.)
Other5 in. weld flange quantity of bolts / bolt hole diameter D8, 22.23mm (0.88 in.)
Other6 in. weld flange bolt circle diameter B254.0mm (10.0 in.)
Other6 in. weld flange outside diameter C279.4mm (11.0 in.)
Other6 in. weld flange quantity of bolts / bolt hole diameter D8, 22.23mm (0.88 in.)
Other8 in. weld flange bolt circle diameter B298.45mm (11.75 in.)
Other8 in. weld flange outside diameter C342.9mm (13.5 in.)
Other8 in. weld flange quantity of bolts / bolt hole diameter D8, 22.23mm (0.88 in.)
OtherEngine speed adjustment50default setting; settings between 40 and 60 acceptable; 52 increases speed by 2 RPM, 49 decreases by 1 RPM
OtherFrequency regulation steady state0.5%Electronic isochronous governor
OtherGenerator to bus phase angle-10 to 10degreesverify with contactor closed
OtherReactive droop1%default setting; range 0.5 - 2%
OtherVoltage regulation no-load to full-load±0.5%Alternator
OtherWeld flange angle A (10, 12, 14 in. nominal pipe size)30deg.
OtherWeld flange angle A (16, 18, 20 in. nominal pipe size)22.5deg.
OtherWeld flange angle A (5, 6, 8 in. nominal pipe size)45deg.
PressureLPG vapor withdrawal fuel supply pressure1.24--2.74kPaNormal operation
PressureNatural gas fuel supply pressure1.74--2.74kPaNormal operation
TemperatureAmbient temperature45°CMaximum for radiator-cooled system
TemperatureExhaust temperature at rated kW, dry exhaust649°CAt rated kW
TemperatureMaximum allowable exhaust back pressure10.2kPaAt rated kW
TorquePGEN terminal block connections0.5Nm
TorquePGEN terminal block connections4.4in. lbs.
VoltageController measurement accuracy2%without calibration; requires a calibrated multimeter for calibration

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilKohler Genuine oil recommended8.5 LFull pressure lubrication system
FuelNatural Gas minimum 33.2 MJ/m³Natural Gas: Methane 90% min, Ethane 4.0% max, Propane 1.0% max, Propene 0.1% max, C4+ 0.3% max, Sulfur 25 ppm max; LPG: Propane 96% max, Ethane 10% max, Propene 3% max, C4+ 3% max, Sulfur 25 ppm maxDual fuel capable: Natural Gas or LPG vapor withdrawal

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Calibration adjustment

⚠ Copying personality profiles from one controller to another can overwrite calibration coefficients and requires re-calibration.

Tools: Calibrated multimeter with recent calibration verification

  1. Use a calibrated multimeter to measure the generator voltage and enter the correct value in the CONTROLLER CONFIG -> CALIBRATION screen.
  2. Use a calibrated multimeter to measure the bus voltage and enter the correct value in the CONTROLLER CONFIG -> CALIBRATION screen.
Verify Generator Operation diagnostic

⚠ Generators must all operate at the same frequency, voltage, and phase connection in order to parallel.

Tools: SiteTech software

  1. Ensure the load is not connected or is drawing less power than a single generator can provide.
  2. Navigate to CONTROLLER CONFIG -> COMMUNICATION SETUP and verify PGEN Nodes Online indicates the correct number of nodes.
  3. Verify alternator connection (voltage selector switch position), system voltage, and voltage regulator target on each generator.
  4. Start a single generator by pressing the Run button; the paralleling box contactor should close and the Generator Connected to Bus indicator should light.
  5. Verify bus and generator voltages match and generator to bus phase angle is between -10 and 10 degrees.
  6. Verify the load bus is energized and available at the load.
  7. Stop the generator by pressing the OFF button; the contactor should open.
  8. Repeat for each generator in the paralleling system.
Verify Paralleling and Load Sharing diagnostic

Tools: Load bank (optional)

  1. Place all generators in automatic mode by pressing the Auto button; verify the red shutdown indicator is not illuminated.
  2. Provide a local start request by holding AUTO, pressing RUN, releasing RUN, then releasing AUTO.
  3. Verify all generators start, one generator closes its contactor, and the others synchronize and close their contactors.
  4. Verify that the % of rated power of the generators matches, showing the generators are sharing load equally.
  5. If a load bank is available, test the system under load.
Control Harness Connections installation

⚠ The control harness connections for GEN 1 and GEN 2 must correspond to the source camlock cable connections.

  1. Connect the control harness from the generator set connected to the GEN 1 camlock connectors to GEN 1 CONTROL.
  2. Connect the control harness from the generator set connected to the GEN 2 camlock connectors to GEN 2 CONTROL.
  3. When not used, store the control harnesses on the storage rack inside the enclosure.
Grounding installation

⚠ Grounding electrical equipment: hazardous voltage can cause severe injury or death. Turn off the main circuit breakers of all power sources before servicing.

  1. Connect the ground lug on the paralleling box to earth ground according to applicable state and local codes.
  2. Follow NEC guidelines for grounding electrical equipment.
  3. The neutral is bonded to ground inside the paralleling box; if required, remove the bonding bus to disconnect neutral from ground.
Load Connections installation

⚠ Multiple power sources can automatically energize the distribution bus. Disconnect all power sources before connecting to the distribution bus.

  1. Remove the camlock security guard from one row of connectors for each generator and store the guard.
  2. Connect the load side ground (green) camlock cables to the distribution bus and then to the paralleling box.
  3. Connect the load side neutral (white) camlock cables to the distribution bus and then to the paralleling box.
  4. Connect the load side L1 (black), L2 (red), and L3 (blue) camlock cables to the distribution bus and then to the paralleling box.
Multiple Paralleling Boxes (PGEN Connections) installation
  1. Connect one or two generators to each paralleling box.
  2. Use Belden cable #9841 (or equivalent) shielded twisted-pair communication cable to connect the PGEN terminal blocks on the paralleling boxes.
  3. Tighten the connections to 0.5 Nm (4.4 in. lbs.).
Paralleling System Setup installation

⚠ Generator management must be disabled manually at each generator set controller.

Tools: Personal computer with SiteTech software

  1. Check that the voltage selector switch and/or alternator wiring matches the building voltage configuration for all generator sets.
  2. Set the digital output to Contactor (SiteTech Programmable Digital Output 116).
  3. Set reactive droop to 0.5-2% (default 1%), using the same reactive droop setting on all generators.
  4. Set the target voltage on all paralleled generators to the same value.
  5. Set engine speed adjustment to 50 on all generators (default 50; range 40-60).
  6. Verify metering; if voltage is incorrect, use the calibration procedure.
  7. Set Sync Mode in AUTO to ACTIVE and Sync Mode in Run to CHECK on all generators.
  8. Set Generator Management Enabled to OFF at each generator unless generator management is requested.
  9. Set up load management (load shed priorities) for non-critical loads.
  10. Stop all generators by pressing the OFF button on each controller.
Source Connections installation

⚠ Hazardous voltage. This equipment must be installed and serviced by qualified electrical personnel. Do not connect or disconnect cables under load.

  1. Remove the camlock security guard from one row of connectors for each generator and store the guard.
  2. Generator 2 connects to the upper set of camlocks; generator 1 connects to the lower set.
  3. Connect the source side ground (green) camlock cables to the paralleling box first and then to each generator.
  4. Connect the source side neutral (white) camlock cables to the paralleling box first and then to each generator.
  5. Connect the source side L1 (black), L2 (red), and L3 (blue) camlock cables to the paralleling box first and then to each generator.
Storage Procedure maintenance

⚠ Do not open the electrical compartment on the opposite side of the enclosure; that compartment should be opened only by Kohler authorized distributors or dealers.

  1. Store control harnesses on the storage rack inside the box when not in use.
  2. Lock the cabinet door with the key provided and store the key in a secure location.
  3. Use the guards to cover the camlock connectors.
  4. Attach padlocks to the electrical panel cover and the camlock guards to prevent unauthorized access.
Disable the Generator Sets operation

⚠ Accidental starting can cause severe injury or death. Remove the negative (-) lead first when disconnecting the battery; reconnect it last.

  1. Press the generator set master control OFF/RESET button.
  2. Disconnect the power to the battery charger, if equipped.
  3. Disconnect the generator set engine starting battery(ies), negative (-) lead first.
Re-enable the Generator Sets operation

⚠ Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage.

  1. Check that the generator set is OFF.
  2. Reconnect the generator set engine starting battery, negative (-) lead last.
  3. Reconnect power to the battery charger, if equipped.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
Alternator Reconnection drawing ADV-5875U--144--Lead

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Power Solutions International 8.8L Industrial Powertrain?

The Power Solutions International 8.8L Industrial Powertrain engine has an oil capacity of 7.6 liters.

What is the displacement of the Power Solutions International 8.8L Industrial Powertrain?

The Power Solutions International 8.8L Industrial Powertrain has a displacement of 8.8 liters with -8 cylinders.

Which generators use the Power Solutions International 8.8L Industrial Powertrain engine?

The Power Solutions International 8.8L Industrial Powertrain powers 5 generator set(s), including Cummins/Onan GFPA, Kohler 125ERES, Kohler 125REZGC, Kohler 125REZGT, Kohler 150ERES.