Home›Engines›Generac G-Force 1000 Series

Generac G-Force 1000 Series Engine

The Generac G-Force 1000 Series is a 1 L 2-cylinder air-cooled engine rated at 3600 rpm. It powers generator sets from Generac, including the 15 kW EcoGen, G007034-0, G007035 and G007036. It holds 1.8 L (0.5 gal) of oil.

Also known as: Generac G-Force 1000 Series, G-Force 1000 Series

Part of the Generac G-Force 1000 engine family — 3 variants share parts & fitment.

0.999 L
Displacement
2
Cylinders
3600 rpm
Rated speed
1.8 L
Oil capacity

Engine specifications

Oil capacity1.8 L
Displacement0.999 L
Cylinders2
AspirationAir-cooled
Rated speed3600 rpm

Troubleshooting

42

Fault codes

CodeMeaningRemedy
HIGH TEMPERATUREUnit shuts down during operation — LED REDInspect ventilation around generator, intake, exhaust, and rear of generator. If no obstructions are present, contact an IASD.
OVERLOAD REMOVE LOADUnit shuts down during operation — LED REDClear alarm and remove household loads from generator. Put back in AUTO and restart.
RPM SENSE LOSSUnit was running and shuts down, attempts to restart — LED REDClear alarm and remove household loads from generator. Put back in AUTO and restart. If generator does not start, contact an IASD.
NOT ACTIVATEDUnit will not start in AUTO with utility loss — LED NONEVerify if screen says unit not activated. See Activation.
LOW OIL PRESSUREUnit will not start in AUTO with utility loss — LED RED

Symptoms & remedies

SymptomCauseRemedy
Engine will not crankBlown fuseCorrect short circuit condition by replacing 7.5A fuse in generator control panel; Contact an IASD if fuse continues to blow
Engine will not crankLoose, corroded, or faulty battery cablesTighten, clean, or replace as necessary
Engine will not crankFaulty starter contact
Engine will not crankFaulty starter motor
Engine will not crankDischarged batteryCharge or replace battery
Engine cranks but will not startNo fuelReplenish fuel / turn on fuel shutoff valve
Engine cranks but will not startHigh fuel pressureCheck and adjust fuel pressure
Engine cranks but will not startFuel selector in wrong positionSet fuel conversion valve to correct position and program controller for fuel type, if necessary
Engine cranks but will not startFaulty fuel solenoid (FS)Contact an IASD for assistance
Engine cranks but will not startHarness/wiring issue
Engine cranks but will not startFaulty spark plug(s)Replace spark plug(s)
Engine cranks but will not startValve clearance out of adjustment. (If applicable. See Specification section in owner's manual.)Inspect and adjust valve clearance
Engine starts hard and runs roughPlugged or damaged air cleanerInspect and clean or replace air cleaner
Engine starts hard and runs roughFaulty spark plug(s)Replace spark plug(s)
Engine starts hard and runs roughIncorrect fuel pressureVerify fuel pressure to fuel regulator is 10–12 in water column (2.49–2.99 kPa) for LP, and 3.5–7.0 in water column (0.87–1.74 kPa) for NG
Engine starts hard and runs roughFuel selector in wrong positionSet fuel conversion valve to correct position and program controller for fuel type, if necessary
Engine starts hard and runs roughValve clearance out of adjustment. (If applicable. See Specification section in owner's manual.)Inspect and adjust valve clearance
Engine starts hard and runs roughInternal engine issueContact an IASD for assistance
Unit is set to OFF, but engine continues to runController wired incorrectlyContact an IASD for assistance
Unit is set to OFF, but engine continues to runFaulty control board
No AC output from generatorGenerator MLCB (generator disconnect) is OFF (OPEN)Set generator MLCB (generator disconnect) to ON (CLOSED)
No AC output from generatorGenerator internal failureContact an IASD for assistance
No AC output from generatorEngine may be warming up. See Cold Smart Start.Check controller screen to verify status
No transfer to standby after utility source failureGenerator MLCB (generator disconnect) is OFF (OPEN)Set generator MLCB (generator disconnect) to ON (CLOSED)
No transfer to standby after utility source failureFaulty transfer switch coilContact an IASD for assistance
No transfer to standby after utility source failureFaulty transfer relay
No transfer to standby after utility source failureTransfer relay circuit open
No transfer to standby after utility source failureFaulty control logic board
No transfer to standby after utility source failureEngine may be warming up. See Cold Smart Start.Check controller screen to verify status
Unit consumes large amounts of oilExcessive engine oilAdjust oil to correct level. See checking engine oil level section in owner's manual.
Unit consumes large amounts of oilFaulty engine breatherContact an IASD for assistance
Unit consumes large amounts of oilIncorrect type or viscosity of oilSee engine oil requirements in owner's manual.
Unit consumes large amounts of oilDamaged gasket, seal, or hoseInspect for oil leaks.
Unit consumes large amounts of oilRestricted air filterReplace air filter.
Wi-Fi network connection broken or intermittentVariousSee Wi-Fi module owner's manual.
Unit running in AUTO but no power in house — LED FLASHING GREENCheck generator MLCB (generator disconnect). If it is ON, contact an IASD.
Unit will not start in AUTO with utility loss — LED GREENCheck screen for start delay countdown. If startup delay is greater than expected, contact an IASD to adjust between 2 to 1500 seconds.

Fault codes and symptom→remedy steps extracted from this engine’s service/owner documentation; verify against the official manual before servicing.

Common problems

15
  • Unit will not start in AUTO with utility loss — LED RED LOW OIL PRESSURE
    Cause: Check LEDs / screen for alarms.
    Fix: Check oil level and add oil as needed. If oil level is correct, contact an IASD.
  • Engine cranks but will not start
    Cause: No fuel
    Fix: Replenish fuel / turn on fuel valve.
  • Engine starts hard and runs rough
    Cause: Plugged or damaged air cleaner
    Fix: Inspect and clean air cleaner.
  • No transfer to standby after utility source failure
    Cause: Generator MLCB (generator disconnect) is OFF (OPEN)
    Fix: Set generator MLCB (generator disconnect) to ON (CLOSED).
  • Unit will not start in AUTO with utility loss
    Cause: Start delay countdown
    Fix: If the start up delay is greater than expected, contact servicing dealer to adjust from 2 to 1500 seconds.
  • Engine will not crank
    Cause: Blown fuse
    Fix: Correct short circuit condition by replacing 7.5 A fuse in generator control panel. Contact an IASD if fuse continues to blow.
  • Unit consumes large amounts of oil
    Cause: Excessive engine oil
    Fix: Adjust oil to correct level. See Checking Engine Oil Level.
  • Yellow LED illuminated in any state LOW BATTERY
    Fix: Clear alarm. Using control panel, check battery by navigating to BATTERY MENU option from MAIN MENU. If battery condition displays GOOD, contact an IASD. If control panel displays CHECK BATTERY, replace battery
  • Unit will not start in AUTO with utility loss — LED: RED LOW OIL PRESSURE
    Fix: Check oil level and add oil as needed. If oil level is correct, contact an IASD
  • Unit will not start in AUTO with utility loss. NOT ACTIVATED
    Cause: Unit not activated
    Fix: Refer to activation section in owners manual.
  • No AC output from generator
    Cause: Generator MLCB (generator disconnect) is OFF (OPEN)
    Fix: Set generator MLCB (generator disconnect) to ON (CLOSED).
  • Engine cranks but won't start
    Cause: Fuel supply and pressure faulty
    Fix: Test 66 - Check fuel supply and pressure; find and correct cause of no fuel or low pressure
  • Yellow LED illuminated in any state — LED YELLOW LOW BATTERY
    Cause: Check screen for additional information.
    Fix: Clear alarm. Using control panel, check battery by navigating to BATTERY MENU option from MAIN MENU. If battery condition displays GOOD, contact an IASD. If control panel displays CHECK BATTERY, replace battery.
  • Unit shuts down during operation — LED RED HIGH TEMPERATURE
    Cause: Check LEDs / screen for alarms.
    Fix: Inspect ventilation around generator, intake, exhaust, and rear of generator. If no obstructions are present, contact an IASD.
  • Engine will not crank when AUTO-OFF-MANUAL switch is set to "MANUAL"
    Cause: Battery faulty
    Fix: Test 61 - Check battery; replace

Compiled from service & troubleshooting documentation across every generator set that uses the Generac G-Force 1000 Series.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter0J84781000 hr Amazon eBay $20.00 NAPA $24.32 KuduParts $15.00
Fuel filterApprox. 1.9 qt/1.8 L—200 hr
Oil filter070185E500 hr Amazon eBay $30.00 NAPA $9.09 FridayParts $45.99
Battery12 volts, Group 26R-540CCA minimum or Group 35AGM-650CCA minimum0H3421S Amazon eBay $283.32
BeltApprox. 1.9 qt/1.8 L—200 hr
Coolant—
OilSynthetic SAE 5W-30 for all temperature ranges; API SJ, SL, or better3.75 Quarts (3.55 Liters)—500 hr
Spark plugGap 0.040 in. (1.02 mm); torque to 18.4 ft-lbs (25 Nm)RC12YC1000 hr Amazon eBay $12.90 NAPA $11.52 FridayParts $19.99

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

40
ItemActionHoursMonthsNotes
Oil levelCheck24 hr1 moMonthly or 24 hours of continuous operation
Aceite del motorChange25 hrFirst service — Después del período de asentamiento de 25 horas, se recomienda utilizar el aceite 5W-20 propiedad de Generac para uso continuo.
Huile moteur et filtre à huileChange25 hrFirst service — Après les premières 25 heures de marche
OilChange200 hr24 moFirst service — After the first 25 hours of operation
Oil filterChange200 hr24 moFirst service — After the first 25 hours of operation
Valve ClearanceCheck400 hrFirst service — Check/adjust after first 25 hours of operation
Engine governor oil levelCheck50 hrCheck prior to initial use and every 50 operating hours thereafter.
Engine oil and filterReplace100 hr12 moFirst service — After first 25 hours; then every 100 hours or 1 year. Cold weather (<4.4°C) or continuous hot (>29.4°C): every 100 hours or 1 year
Coolant Level and HosesCheck125 hr12 moSchedule A; also daily if running continuously
Enclosure LouversCheck125 hr12 moSchedule A; also daily if running continuously
Fuel LinesCheck125 hr12 moSchedule A; also daily if running continuously
Lubricating Oil Level and Drain HoseCheck125 hr12 moSchedule A; also daily if running continuously
Lubricating Oil and Oil FilterReplace125 hr12 moFirst service — Schedule A
Radiator for CloggingCheck125 hr12 moSchedule A; also daily if running continuously
Aceite de motor y filtro de aceiteChange200 hr24 moFirst service — Programa de mantenimiento A
Air cleanerInspect200 hr2 years or 200 hours; replace as necessary
Batería (condición, nivel de electrolito y estado de carga)Check200 hr24 moPrograma de mantenimiento A
Battery conditionCheck200 hr24 moSchedule A.
Battery condition and chargeCheck200 hr24 moSchedule A maintenance
Change Air FilterChange200 hr200 hours or 2 years
Change Oil & FilterChange200 hr200 hours or 2 years; 20kW: 100 hours or 2 years
Complete Tune-UpOther200 hr24 moIndependent Authorized Dealer must perform; 2 years or 200 hours
Engine oilChange200 hr24 moFirst service — up to a 2 year/200 hour oil change interval
Huile à moteur et filtre à huileChange200 hr24 moFirst service — Calendrier A: tous les deux ans ou toutes les 200 heures. Changer l'huile et le filtre après les 25 premières heures. En conditions froides (moins de 4,4 °C/40 °F) ou fonctionnant en continu à plus de 29,4 °C/85 °F, changer annuellement ou toutes les 100 heures.
Inspect Air FilterInspect200 hr200 hours or 2 years
Inspect Spark PlugsInspect200 hr200 hours or 2 years
Óleo lubrificante e filtro de óleoChange200 hr24 moFirst service — Trocar após as primeiras 25 horas; Programação A (2 anos ou 200 h); em clima frio (<4,4 °C) ou quente contínuo (>29,4 °C) anualmente ou 100 h
Aceite del motor y filtro de aceiteReplace400 hr48 moFirst service — Programa B: cada cuatro años o 400 horas.
Air cleanerClean400 hrClean or replace as necessary; R = Replace as Necessary; 400 hours
Air filterReplace400 hr48 moSchedule B maintenance
Battery condition, electrolyte level, and state of chargeInspect400 hr48 moSchedule B
Bougies d'allumageClean400 hr48 moNettoyer les bougies, vérifier l'écartement ou les remplacer. Calendrier A et Calendrier B.
Bujía(s)Replace400 hr48 moPrograma B: cada cuatro años o 400 horas.
BujíasReplace400 hr48 moPrograma B; limpiar, comprobar separación y sustituir
Change spark PlugsChange400 hr400 hours or 10 years
Engine air filterReplace1000 hr48 moSchedule B; emissions-critical maintenance
Engine oil and oil filterChange400 hr48 moFirst service — Schedule B.
Engine oil and oil filterReplace400 hr48 moFirst service — Schedule B
Filtre à air du moteurReplace400 hr48 moCalendrier B: tous les quatre ans ou toutes les 400 heures.
Filtro de aire del motorReplace400 hr48 moPrograma de mantenimiento B

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceBelt deflection3/8 - 5/8in22 Ibs (10 kgf) force midway between water pump and alternator pulleys
ClearanceBelt deflection7.6 - 12.7mm22 Ibs (10 kgf) force midway between water pump and alternator pulleys
GapArmature Air Gap0.008-0.012inch
GapBreaker Point Gap0.018-0.022inch
GapFolga da vela de ignição0,020pol
GapFolga da vela de ignição0,040pol
GapFolga da vela de ignição0,508mm
GapFolga da vela de ignição1,02mm
GapIgnition magneto air gap0.008-0.012inch
GapIgnition magneto air gap0.008-0.012 inch (0.20-0.30 mm)gapV-twin engines; fixed non-adjustable on single cylinder
GapIgnition magneto air gap (V-twin)0.008-0.012 inch (0.20-0.30 mm)inch / mm
GapIgnition magneto gap to flywheel (replacement)0.010 inchinch
GapSeparación de electrodos de bujía (11 kW)0.030in (0.76 mm)
GapSeparación de electrodos de bujía (16/20/22 kW)0.040in (1.02 mm)
GapSeparación de electrodos de bujía (9 kW)0.020in (0.508 mm)
GapSeparación de las bujías0.508mm (0.020 pulg.)
GapSeparación de las bujías1.02mm (0.040 pulg.)
GapSpark Plug Gap0.030in (0.76 mm)11 kW (GTH-530)
GapSpark Plug Gap0.031-0.035inch
GapSpark Plug Gap0.040in. (1.02 mm)
GapSpark Plug Gap1.02mmrecommended specification
GapSpark Plug Gap (1.5L engines, 25/30 kW)0.9mm
GapSpark Plug Gap (2.4L engines, 22/27/36/45 kW)1.07-1.17mm
GapSpark Plug Gap (32/38 kW and 60 kW)0.71mm
GapSpark plug gap0.020in (0.508 mm)
GapSpark plug gap0.020 in (0.508 mm)in (mm)
GapSpark plug gap0.040 in (1.02 mm)in (mm)
GapSpark plug gap0.508mm
GapSpark plug gap0.76mm (0.030 in)
GapSpark plug gap0.76 mm (0.030 inch)gap410 cc and 530 cc engines
GapSpark plug gap1.02 mm (0.040 inch)gap990 cc and 999 cc engines
GapSpark plug gap (10 kW)0.020in (0.508 mm)
GapSpark plug gap (11 kW)0.030in (0.76 mm)
GapSpark plug gap (12/14/16/17/20 kW)1.02mm
GapSpark plug gap (14-24 kW)0.040in (1.02 mm)
GapSpark plug gap (14–24 kW)0.040in (1.02 mm)cold
GapSpark plug gap (16/20/22 kW)0.040in (1.02 mm)
GapSpark plug gap (8/10 kW)0.76mm
GapSpark plug gap (9 kW)0.020in (0.508 mm)
GapSpark plug gap 10kW0.030 inchinch
GapSpark plug gap 13/14/15/16/17kW0.040 inchinch
GapSpark plug gap 20kW0.030 inchinch
GapSpark plug gap 8kW0.030 inchinch
GapÉcartement de bougie0,508mm (0,020 po)
GapÉcartement de bougie1,02mm (0,040 po)
GapÉcartement des électrodes des bougies d'allumage0.508mm (0,020 po)
GapÉcartement des électrodes des bougies d'allumage0.76mm (0,030 po)
GapÉcartement des électrodes des bougies d'allumage1.02mm (0,040 po)
OtherCold Smart Start fixed temperature20 F (-7 C)F (C)22-26 kW
OtherCold Smart Start fixed temperature50 F (10 C)F (C)10-20 kW
OtherCompression Ratio (1.5L)11:1
OtherCompression Ratio (2.4L)9.5:1
OtherCompression difference maximum between cylinders25 percentpercent
OtherCompression ratio9.5:1
OtherCylinder leak down acceptable leakage20percent
OtherEngine start sequence16 sec on, 7 rest90 sec maximum durationcyclic cranking
OtherExercise time length (16-22 kW)5minutes
OtherExercise time length (9-11 kW)12minutes
OtherFusível do painel de controle7,5A
OtherOrdem de partida (10 kW)15 s de arranque, 7 s de repouso, seguidos por quatro ciclos adicionais de 7 s de arranque e 7 s de repousocinco ciclos de manivela

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50 percent soft water and 50 percent ethylene glycol base anti-freezelow silicate anti-freeze2.0 U.S. gallonsDo not use chromate base rust inhibitor or high silicate anti-freeze boosters.
Coolant50/50 ethylene glycolGenerac 50/50 ethylene glycol type coolant9.5 litersUse demineralized or distilled water; do not use propylene glycol. Coolant mix 40-60% volume.
Engine oilAPI SJ, SL ou mieuxChanger l'huile chaque année ou toutes les 100 heures par temps froid (< 4,4 °C) ou exploitation continue par temps chaud (> 29,4 °C)
Engine oil10W-30API Service Class SJ, SL or betterBetween 40ºF and -10ºF
Engine oil30 weight organic oil (factory fill)Units run and tested at factory prior to shipping, no break-in required
Engine oil5W-20Generac proprietary 5W-20 Synthetic (after 30 hour break-in)3.8 litersFactory filled with 5W-20; 60 kW capacity 5.25 quarts (5 liters). Do not use special additives.
Engine oil5W-20 (Generac proprietary)API Service Class SJ, SL, or better1.03 LOil capacity including filter. Use for continuous use after the 25 hour break-in period; specifically formulated for gaseous powered Generac generators. Do not use special additives. Change every year or 100 hours in cold weather (below 40 F) or continuous hot weather (above 85 F).
Engine oil5W-30Aceite orgánico 5W-30 (la unidad se entrega de fábrica llena con este aceite)Compruebe el nivel de aceite y, de ser necesario, añada la cantidad apropiada con la viscosidad correcta. No llene en exceso. Consulte 'Recomendaciones para el aceite de motor' para tipo/viscosidad.
Engine oil5W-30 (factory fill) / 5W-20 GEO (continuous)Generac proprietary gaseous engine oil (GEO)Unit comes filled with 5W-30 organic oil; after 25 hour break-in use 5W-20 GEO
Engine oilGenerac 5W-20 exclusiveAPI SJ, SL ou mieuxAprès la période de rodage de 25 heures et à chaque intervalle; spécialement formulée pour les génératrices Generac alimentées au gaz
Engine oilSAE 30API Service Class SJ, SL or better1.5 QtsAbove 32ºF; capacity varies by engine
Engine oilSAE 30 above 32°F; 10W-30 between 40°F and -10°F; Synthetic 5W-30 10°F and belowAPI Service Class SJ, SL or better; use no special additives1.5 QtsOil capacity including filter
Engine oilSAE 40 above 86 F; SAE 30 32-85 F; SAE 20W below 32 F; SAE 10W-30 all seasonsAPI Service SC, SD, SE or SF3.0 U.S. quartsLiquid-cooled 1.2 liter engine with filter change; 2.5 U.S. quarts without filter change.
Engine oilSAE 5W-30 SyntheticAPI Service Class SJ, SL or betterDo not use special additives
Engine oilSAE 5W-30 sintéticoAPI SJ, SL o mejor1.03 l9 kW; no usar aditivos especiales
Engine oilSAE 5W-30 synthetic; SAE 30 above 60 F; SAE 10W-30 20-59 F; SAE 5W-20/5W-30 below 20 FAPI Service SF, SF/CC, or SF/CD1.5 U.S. quartsAir-cooled V-Twin engine crankcase capacity about 1.5 U.S. quarts. Oil makeup tank capacity about 2.5 U.S. quarts on Model 9067.
Engine oilSAE 5W-30 synthétiqueAPI classe de service SJ, SL ou supérieureHuile SAE 5W-30 synthétique pour toutes les plages de température. N'utilisez aucun additif spécial.
Engine oilSynthetic 5W-30API Service Class SJ, SL or better10ºF and below
Engine oilSynthetic SAE 5W-30API SJ, SL, or better3.75 Quarts (3.55 Liters)For all temperature ranges; do not use special additives
FuelGas natural: contenido de BTU de por lo menos 1000 BTU/ft3 (37,26 MJ/m3). Gas LP: por lo menos 2500 BTU/ft3 (93,15 MJ/m3)250.0 gal (946 l)Tamaño mínimo del tanque de LP es 250 gal (946 l), salvo que los cálculos de la unidad indiquen uno mayor. Solo sistema de extracción de vapor para LP.
FuelGas naturalmínimo 1000 BTU por pie cúbico (37.26 megajulios por metro cúbico)Reducciones típicas de gas natural 10-20 % respecto a LP
FuelGaz naturel37.26 mégajoules par mètre cube (1 000 BTU par pied cube) minimumTeneur en BTU minimale du gaz naturel.
FuelGaz naturel d'au moins 37,26 mégajoules par mètre cube (1 000 BTU par pied cube)NFPA 54
FuelGaz propane liquide (gazeux)93.15 mégajoules par mètre cube (2 500 BTU par pied cube) minimumCapacité de réservoir de gaz propane liquide minimum recommandée de 946 litres (250 gallons).
FuelGaz propane liquide d'au moins 93,15 mégajoules par mètre cube (2 500 BTU par pied cube)NFPA 58 / ICC IFGCRéservoir de gaz propane liquide d'une capacité minimale de 946 litres (250 gallons).
FuelLP (vapor)mínimo 2500 BTU por pie cúbico (93.15 megajulios por metro cúbico)946.0 lSe recomienda tanque de LP de 250 gal. (946 l) de tamaño mínimo si se convierte de NG a LP
FuelLP Gasat least 2,520 Btus per cubic footVapor withdrawal; required pressure 10-12 inches water column
FuelLP Gas (vapor), min 2500 BTU/ft3 (93.15 MJ/m3)Minimum LP tank size 250 gal (946 L) recommended when converting
FuelLP gas (vapor), minimum 2,500 BTUs per ft3 (93.15 megajoules per m3)Vapor withdrawn liquid propane.
FuelLP vaporat least 2,520 BTU’s per cubic feetRequired pressure 10 inches to 12 inches water column; vapor withdrawal system only

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

66
CodeNameMeaningSeverityAction
1048VSCF OverloadUnit shuts down during operationShutdownAlternator, AVR or wiring damaged. Contact servicing dealer.
1049VSCF OverloadUnit shuts down during operationShutdownGenerator output shorted or severely overloaded; clear overload and restart
1051VSCF High BatteryYellow LED illuminated in any stateWarningVoltage supply to AVR is high; check external battery charger installation or contact servicing dealer
1052VSCF DC OvervoltageUnit shuts down during operationShutdownGenerator temporarily overloaded or output shorted; try restart
1053VSCF Gate FaultUnit shuts down during operation or startingShutdownAVR is damaged; contact servicing dealer
1054VSCF IGBT Overtemp.Unit shuts down during operation or startingShutdownReplace AVR filter, inspect fan, check intake/exhaust, check ambient temperature; contact servicing dealer
1055VSCF Phase ErrorUnit shuts down during startingShutdownCheck stepper motor, linkage, gas pressure; contact servicing dealer if alternator damaged
1056VSCF UndervoltageUnit shuts down during operation or startingShutdownLoad too large, remove and restart; or alternator/AVR damage, contact servicing dealer
1057VSCF OvervoltageUnit shuts down during operation or startingShutdownGenerator overloaded; remove load and restart
1058VSCF DC UndervoltageUnit shuts down during operation or startingShutdownAlternator damage; contact servicing dealer
1059VSCF Field LossUnit shuts down during startingShutdownAlternator damage; contact servicing dealer
1060Big Fan FailureUnit shuts down during operationShutdownAVR electronics exceeded 70°C; replace AVR filter, check intake/exhaust/ambient temp; contact servicing dealer
1061VSCF Field LossUnit shuts down during operationShutdownAlternator damage; contact servicing dealer
1065OverfrequencyUnit shuts down during operationShutdownOverload, RPM sensor failure, or stepper motor problem; contact servicing dealer
1066VSCF Speed mismatchUnit shuts down during operation or startingShutdownFuel pressure loss, large overload, or throttle/engine problem; contact servicing dealer
1070Small fan failureSmall fan failure displayed; continues 80 minutes without fan if running in AUTOWarningCheck fan wiring/mechanical, check AVR filter for blocked air path
AUXILIARY SHUTDOWNAuxiliary ShutdownUnit will not startShutdownSet auxiliary shutdown switch(es) to CLOSED (I); clear alarm
BATERÍA BAJABATERÍA BAJAIndicador LED amarillo encendido en cualquier estado.WarningBorre la alarma. Navegue hasta BATTERY MENU del MAIN MENU para revisar la batería. Si indica GOOD, comuníquese con un IASD. Si indica CHECK BATTERY, reemplace la batería.
BATTERY PROBLEMBattery ProblemYellow LED illuminatedWarningContact servicing dealer
Battery ProblemBattery FaultBattery condition poor or battery charger issueWarningInspect battery condition and connections. Contact IASD if needed.
CARGADOR SIN CACARGADOR SIN CAIndicador LED amarillo encendido en cualquier estado.WarningComuníquese con un IASD.
CHARGER MISSING ACCharger Missing ACAC power unavailable for battery chargingWarningRestore AC power supply or check generator AC output.
CHARGER WARNINGCharger WarningYellow LED illuminatedWarningContact servicing dealer
Controller FaultControl Module FailureInternal controller fault detectedShutdownContact IASD for assistance
CONTROLLER FAULTController FaultAlarm message listed on controller menu.ShutdownContact an IASD.
DESCONEXIÓN AUXILIARDESCONEXIÓN AUXILIARLa unidad no arranca.ShutdownColoque los interruptores de desconexión auxiliar en posición CERRADA (I).
DOWNLOAD FAILUREDownload FailureFirmware download or update failedWarningRetry firmware update. Contact authorized service dealer if problem persists.
EMERGENCY STOPEmergency StopAlarm message listed on controller menu.ShutdownCheck emergency shutdown switch and reset.
FUSE PROBLEMFuse ProblemUnit will not start in AUTO with utility lossWarningCheck 7.5amp fuse, replace with ATO 7.5Amp fuse if bad
HIGH TEMPERATUREHigh TemperatureUnit shuts down during operationShutdownCheck ventilation around generator, intake, exhaust and rear of generator
High TemperatureOverheatEngine operating temperature too highShutdownInspect ventilation around generator, intake, exhaust, and rear. Ensure no obstructions present.
INSPECCIONE LA BATERÍAINSPECCIONE LA BATERÍAIndicador LED amarillo encendido en cualquier estado.WarningInspeccione la batería. Presione ENTER para borrar.
INSPECT BATTERYInspect BatteryYellow LED illuminated indicating battery inspection dueWarningInspect battery. Press ENTER to clear.
LOW BATTERYLow BatteryYellow LED illuminatedWarningClear alarm; check battery via control panel BATTERY MENU; if GOOD contact dealer, else replace battery
Low BatteryBattery Voltage LowStarting battery voltage below acceptable levelWarningInspect battery and battery cables. Charge or replace battery if necessary.
LOW OIL PRESSURELow Oil PressureUnit will not start in AUTO with utility lossShutdownCheck oil level / add oil per Owners Manual
Low Oil PressureLow Oil Level or PressureInsufficient oil pressure in engineShutdownCheck engine oil level and top up if necessary. Contact IASD if problem persists.
LOW VOLTSLow Volts / Remove LoadUnit will not start in AUTO with utility lossShutdownClear alarm and remove household loads from the generator. Put in AUTO and restart.
LOW VOLTS REMOVE LOADLow Volts Remove LoadUnit will not start in AUTO with utility lossShutdownClear alarm and remove household loads, put back in AUTO and restart
MISWIREMiswireUnit will not start in AUTO with utility lossShutdownContact servicing dealer
NOT ACTIVATEDNot ActivatedUnit will not start in AUTO with utility lossWarningRefer to activation section in owners manual
OVERCRANKOvercrankUnit will not start in AUTO with utility lossShutdownCheck fuel line shutoff valve ON, clear alarm, attempt manual start
OvercrankExtended CrankingEngine failing to start after extended crank attemptsShutdownCheck fuel supply, spark plugs, and fuel system. Contact IASD for further diagnosis.
OVERLOADOverloadLoad current exceeds generator rated capacityShutdownClear alarm and remove household loads from the generator. Put back in AUTO and restart.
OverloadOverload DetectedElectrical load exceeds generator capacityShutdownRemove household electrical loads from generator
OVERLOAD REMOVE LOADOverload Remove LoadUnit shuts down during operationShutdownClear alarm, remove household loads, put back in AUTO and restart
OVERLOAD WARNINGAviso de sobrecargaAviso de sobrecarga.WarningRemova as cargas domésticas do gerador.
OVERSPEEDOverspeedUnit will not start in AUTO with utility lossShutdownContact servicing dealer
OverspeedRPM OverspeedEngine running at excessive RPMShutdownContact IASD for assistance
OVERVOLTAGEOvervoltageUnit will not start in AUTO with utility lossShutdownContact servicing dealer
OvervoltageOutput Voltage HighGenerator voltage exceeding nominal ratingShutdownReduce electrical load and restart. Contact IASD if issue persists.
PROBLEMA DE BATERÍAPROBLEMA DE BATERÍAIndicador LED amarillo encendido en cualquier estado.WarningComuníquese con un IASD.
RPM SENSE LOSSRPM Sense LossUnit was running and shuts down, attempts to restartShutdownClear alarm, remove household loads, put back in AUTO and restart; may be fuel issue, contact servicing dealer
RPM SENSOR LOSSRPM Sensor LossEngine speed sensor failure or loss of RPM signalShutdownClear alarm and remove household loads from generator. Set back to AUTO and restart. If alarm returns, contact servicing dealer to investigate possible fuel issue.
RPM Sensor LossRPM Signal LossRPM sensor signal not detectedShutdownContact IASD for assistance
SERVICE AService AYellow LED illuminated, maintenance dueInfoPerform SERVICE A maintenance, hit ENTER to clear
SERVICE BService BYellow LED illuminated, maintenance dueInfoPerform SERVICE B maintenance, hit ENTER to clear
SHUTDOWN SWITCHShutdown SwitchUnit will not start. Flashing red LED.ShutdownCheck emergency shutdown switches. Set switch(es) to CLOSED (I). Clear alarm.
STEPPER OVERCURRENTStepper OvercurrentUnit will not start in AUTO with utility lossShutdownContact servicing dealer
UNDERSPEEDUnderspeedUnit will not start in AUTO with utility lossShutdownContact servicing dealer
UnderspeedEngine Speed Too LowEngine RPM below nominal specificationShutdownContact IASD for assistance
UNDERVOLTAGEUndervoltageUnit will not start in AUTO with utility lossShutdownContact servicing dealer
UndervoltageOutput Voltage LowGenerator voltage below nominal ratingShutdownReduce electrical load and restart. Contact IASD if issue persists.
USB WARNINGUSB WarningUSB port firmware update issue detectedWarningCheck USB device compatibility or firmware update status.
WIRING ERRORWiring ErrorElectrical wiring configuration error detectedShutdownContact authorized service dealer.
Wiring ErrorElectrical Wiring FaultWiring configuration error detectedShutdownContact IASD for assistance

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjust Valve Clearance adjustment

⚠ Allow engine to cool before adjusting valve clearance

⚠ AVR fan operates for 80 minutes after shutdown

Tools: 13mm wrench, 10mm Allen wrench, Feeler gauge

  1. Remove spark plug wires and spark plugs
  2. Remove four screws attaching valve cover, discard gasket
  3. Verify piston at top dead center (TDC) of compression stroke
  4. Loosen rocker jam nut with 13mm wrench
  5. Turn pivot ball stud with 10mm Allen wrench while checking clearance with feeler gauge
  6. Tighten jam nut to 174 in-lbs (19.68 Nm) while holding pivot ball stud
  7. Recheck valve clearance
  8. Install new valve cover gasket and valve cover, torque fasteners to 60 in-lbs (6.8 Nm) in cross pattern
  9. Install spark plugs, torque to 18 ft-lbs (25 Nm)
  10. Connect AVR fan and 4-pin connector
  11. Install AVR filter housing, torque to 50-96 in-lbs (6-11 Nm)
  12. Repeat for other cylinder if necessary
Adjust ignition magneto air gap — V-twin adjustment

Tools: 0.008-0.012 inch thickness gauge

  1. Rotate flywheel until magnet is under module laminations.
  2. Place 0.008-0.012 inch (0.20-0.30mm) thickness gauge between magnet and laminations.
  3. Loosen mounting screws and let magnet pull magneto against gauge.
  4. Tighten both mounting screws.
  5. Rotate flywheel to remove thickness gauge.
  6. Repeat for second magneto.
Adjusting Magneto Flywheel Gap adjustment

⚠ Air gap between ignition magneto and flywheel on single cylinder engines is not adjustable.

Tools: 0.008-0.012 inch thickness gauge

  1. Rotate the flywheel until the magnet is under the module (armature) laminations.
  2. Place a 0.008-0.012 inch (0.20-0.30mm) thickness gauge between flywheel magnet and module laminations.
  3. Loosen the mounting screws and let the magnet pull the magneto down against the thickness gauge.
  4. Tighten both mounting screws.
  5. To remove the thickness gauge, rotate the flywheel.
  6. Repeat the above procedure for the second magneto.
Adjusting Valve Clearance adjustment

⚠ Risk of Burn. Allow the engine to cool before performing the following procedure.

Tools: Feeler gauge, 10 mm wrench, 13 mm wrench, 14 mm wrench, 10 mm hex key

  1. Allow engine to cool before adjusting valve clearance.
  2. Remove spark plug wire(s) away from plugs and remove spark plug(s).
  3. Remove the four screws attaching the valve cover; remove and discard gasket.
  4. Verify piston is at TDC of its compression stroke (both valves closed).
  5. Loosen rocker jam nut using a 10 mm wrench (10 kW) or 13 mm wrench (20–22 kW).
  6. Turn pivot ball stud with a 14 mm wrench (10 kW) or 10 mm hex key (20–22 kW) while checking clearance with a feeler gauge.
  7. Hold pivot ball stud and tighten rocker arm jam nut to specification.
  8. After tightening jam nut, verify valve clearance did not change.
  9. Install new valve cover gasket and valve cover; tighten fasteners in a cross pattern.
  10. Install spark plugs and tighten to 18 ft-lbs (25 Nm).
  11. Attach spark plug wire to spark plug.
  12. Repeat process for other cylinder if equipped.
Ajustar a folga das válvulas adjustment

⚠ Risco de queimaduras. Deixe o motor esfriar antes de executar o procedimento.

Tools: Chave de 10 mm, Chave de 13 mm, Chave de 14 mm, Chave sextavada de 10 mm, Calibrador

  1. Remova os fios das velas de ignição e remova as velas de ignição.
  2. Remova os quatro parafusos que prendem a tampa da válvula; descarte a junta.
  3. Verifique se o pistão está no TDC do seu curso de compressão.
  4. Solte a contraporca do balanceiro (C) com chave de 10 mm ou 13 mm.
  5. Gire o pino de esfera articulada (D) com chave de 14 mm ou sextavada de 10 mm e ajuste a folga.
  6. Aperte a contraporca do braço oscilante e inspecione a folga novamente.
  7. Instale a nova junta e as tampas das válvulas; aperte em padrão transversal.
  8. Instale as velas e aperte a 25 Nm; conecte os fios das velas.
Ajuste de la luz de válvulas adjustment

⚠ Dejar enfriar el motor antes de ajustar.

⚠ Iniciar los cuatro tornillos antes de apretar.

Tools: Calibre de espesores, Llaves de 8/10/13/14 mm, Llave de casquillo, Casquillo grande

  1. Cerrar la válvula de combustible y desconectar la batería.
  2. Retirar cable(s) de bujía y alejarlos.
  3. Retirar la(s) bujía(s).
  4. Llevar el pistón al PMS de la carrera de compresión.
  5. Retirar los cuatro tornillos de la cubierta de válvulas y desechar la junta.
  6. Aflojar la contratuerca del balancín.
  7. Girar el prisionero de bola pivote para ajustar la luz con calibre.
  8. Sostener el prisionero y apretar la contratuerca; verificar y reinstalar con junta nueva.
Ajuste de la separación de la válvula adjustment

⚠ Deje que el motor se enfríe antes del procedimiento.

⚠ Desconecte el cable negativo y luego el positivo de la batería.

⚠ No necesario en unidades 14 o 18 kW con motor de 816 cc.

Tools: Llave de 10 mm, Llave de 13 mm, Llave de 14 mm, Llave hexagonal de 10 mm, Galga de espesores

  1. Retire los hilos de las bujías y las bujías.
  2. Retire los cuatro tornillos de la cubierta de la válvula y deseche la junta.
  3. Verifique que el pistón esté en el PMS de su carrera de compresión.
  4. Suelte la contratuerca del balancín (llave 10 mm en 10 kW, 13 mm en 20 a 24 kW).
  5. Gire el espárrago del pivote (llave 14 mm en 10 kW, hexagonal 10 mm en 20 a 24 kW) ajustando la separación.
  6. Sostenga el espárrago y apriete la contratuerca del balancín.
  7. Inspeccione la separación para verificar que no cambió.
  8. Instale una junta nueva y la cubierta de la válvula; apriete en patrón cruzado.
  9. Instale las bujías y apriete a 25 Nm (18 lb-pie).
  10. Conecte los hilos de las bujías.
Ajuster le jeu des soupapes adjustment

⚠ Risque de brûlure : laisser le moteur refroidir avant d’exécuter la procédure.

⚠ Réglage non requis sur les modèles de 14 ou 18 kW à moteur de 816 cc.

Tools: Clé de 10 mm ou 13 mm, Clé de 14 mm ou clé hexagonale de 10 mm, Jauge d’épaisseur

  1. Laisser le moteur refroidir.
  2. Débrancher les câbles de bougie et les placer à l’écart.
  3. Retirer les bougies.
  4. Retirer les quatre vis du cache-culbuteurs et mettre le joint au rebut.
  5. S’assurer que le piston est au point mort haut (PMH) de sa course de compression.
  6. Desserrer le contre-écrou de culbuteur.
  7. Faire tourner le goujon pivot tout en contrôlant le jeu avec une jauge d’épaisseur.
  8. Ajuster le jeu conformément à la section Moteur.
  9. Tenir le goujon pivot et serrer le contre-écrou au couple spécifié.
  10. Poser un joint de cache-culbuteurs neuf et remonter le cache-culbuteurs.
  11. Mettre les bougies en place au couple de 25 Nm (18 pi-lb).
Check and Adjust Accessory / Drive Belt adjustment

Tools: Belt deflection gauge

  1. Inspect belt for cracks, fraying, excessive wear or other damage.
  2. Verify belt is free of grease and oil; replace if contaminated.
  3. Using a suitable gauge, apply 22 Ibs (10 kgf) force midway between water pump and alternator pulleys.
  4. Loosen DC alternator tension bracket screw.
  5. Rotate alternator outward to reduce belt deflection.
  6. Rotate inward to increase belt deflection.
  7. Tighten DC alternator tension bracket screw to 17-22 ft-lbs (23-30 Nm).
  8. Recheck belt deflection and repeat steps as necessary.
Check and Adjust Engine Governor (Single Cylinder Units) adjustment

Tools: Frequency meter, torque wrench

  1. Loosen the governor clamp bolt.
  2. Hold the governor lever at wide open throttle position.
  3. Rotate the governor shaft clockwise as far as it will go.
  4. Tighten the governor lever clamp bolt to 70 inch-pounds (8 N-m).
  5. Start the generator; let it stabilize and warm up at no-load.
  6. Connect a frequency meter across the generator AC output leads.
  7. Turn the primary adjust screw to obtain a frequency of 61.5 Hz.
  8. Turn the secondary adjust screw to obtain a frequency of 62.5 Hz.
Check and Adjust Ignition Magnetos adjustment

Tools: 0.008-0.012 inch thickness gauge

  1. Rotate flywheel until magnet is under module laminations.
  2. Place 0.008-0.012 inch thickness gauge between magnet and laminations.
  3. Loosen mounting screws and let magnet pull magneto down.
  4. Tighten both mounting screws.
  5. Rotate flywheel to remove gauge.
  6. Repeat for second magneto.
Check and Adjust Valves adjustment

Tools: 10mm allen wrench, flat feeler gauge, torque wrench

  1. Remove the four (4) screws from the rocker cover.
  2. Remove the rocker cover and rocker cover gasket.
  3. Loosen the rocker arm jam nut.
  4. Use a 10mm allen wrench to turn the pivot ball stud.
  5. Check clearance between rocker arm and valve stem with a flat feeler gauge.
  6. Set valve clearance to 0.05-0.1mm (0.002-0.004 in.) cold.
  7. Hold pivot ball stud with allen wrench and tighten rocker arm jam nut to 174 inch pounds.
  8. Recheck valve clearance to make sure it did not change.
  9. Re-install rocker cover gasket, rocker cover and the four screws.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
0 – c.c. (-)NOIR no 3Fil de mise à la terre normal; obligatoire si jumelé à un commutateur de transfert de gestion intelligente de l'alimentation de Generac.
23BLANCO Núm. 5Cable de señal lógica del control de transferencia
23 (White #5)ETransfer Control Signal Wire
Conductor Lug250 MCM - #6Transfer switch wire range
Generator control wiring - 1-115 ft (1-35 m)N1, N2, T1, 23, 194No. 18 AWG
Generator control wiring - 116-185 ft (36-56 m)N1, N2, T1, 23, 194No. 16 AWG
Generator control wiring - 186-295 ft (57-89 m)N1, N2, T1, 23, 194No. 14 AWG
Generator control wiring - 296-460 ft (90-140 m)N1, N2, T1, 23, 194No. 12 AWG
Ground Lug2/0 - #14Transfer switch wire range
Longueur de fil 1 à 35 m (1 à 115 pi)Calibre 18 AWGConducteurs en cuivre seulement.
Longueur de fil 35 à 56 m (115 à 185 pi)Calibre 16 AWGConducteurs en cuivre seulement.
Longueur de fil 56 à 89 m (185 à 295 pi)Calibre 14 AWGConducteurs en cuivre seulement.
Longueur de fil 89 à 140 m (295 à 460 pi)Calibre 12 AWGConducteurs en cuivre seulement.
Neutral Lug350 MCM - #6Transfer switch wire range
Neutral for battery chargerWHITE NEU/00Must be connected to keep battery charged whether unit is running or not
1Connect a 2008 and later load center switch to a pre-2008 air-cooled generator: Wire 0 will not be utilized. Remove battery charger from the transfer switch. Connect N1 (BLU) to N1 (YEL), N2 (YEL) to N2 (YEL), 23 (BRN) to 23 (WHT), 194 (ORG) to 15B (RED) using UL approved wire nuts.N1, N2, 23, 194, 15B, 0Battery charger in transfer switch will not be utilized in operation of the generator.
1Connect a pre-2008 load center switch to a current or future air-cooled generator: Wire 0 will not be utilized. Connect N1 (BLU) to N1 (YEL), N2 (YEL) to N2 (YEL), 23 (BRN) to 23 (WHT), 194 (ORG) to 15B (RED) using UL approved wire nuts.N1, N2, 23, 194, 15B, 0Wire 194 changed to 15B on current model air-cooled generators.
0 VCC0NEGRO Núm. 3CC (-) Cable común de conexión a tierra. Requerido si el generador está apareado con un interruptor de transferencia de gestión de alimentación inteligente Generac.
12 V c.c.194 – c.c. (+)ROUGE no 4Pour les commandes de transfert.
12 VCC194ROJO núm. 4CC (+) para los controles de transferencia
12 VDC194 (Red #4)DDC (+) 12 VDC for Transfer Controls
12 VDCDC (+) 12 VDC for transfer controlsRED 194
12 VDCDC (-) common ground wireBLACK 0
12 VDCTransfer control signal wireWHITE 23Required if generator is paired with optional Digital Power Management (DPM) smart technology
120 V c.a.T1BLEU no 3Avec fusible 120 V c.a. pour le chargeur de la batterie; doit être branché pour que la batterie demeure chargée.
120 VACFused 120 VAC for battery chargerBLUE T1Must be connected to keep battery charged whether unit is running or not
120 VACT1 (White #3)BFused 120VAC for Battery Charger
120 VCAT1AZUL Núm. 3Con fusible para el cargador de baterías (debe estar conectado para mantener la batería cargada, esté o no funcionando la unidad)
120/2083parallel wyeS1 through S12; bolted junctions: 4,5,6,10,11,12 to Neutral (00); S1 and S7 to Line E1; S2 and S8 to Line E2; S3 and S9 to Line E3Voltage Code B. Six coils, twelve leads brought out to AC connection panel.
120/24013-wireLeads 11 and 44 are hot; junction of Leads 22 and 33 is neutralVoltage Code A. Stator AC power windings each supply 120 volts AC; in series they supply 240 volts AC.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Generac G-Force 1000 family

70
Part #DescriptionCategory
0J8478Air FilterAir filter
0J8478SAir filterAir filter
0K3054AVR Air filterAir filter
A0006487350AGM Group BTX20L BatteryBattery
G005819-026R Wet Cell BatteryBattery
0J8318Rotor BrushesBrush
0C2979GASKET, VALVE COVERGasket
070185EOil FilterOil filter
070185ESFiltre à huile recommandéOil filter
070185FRecommended Oil FilterOil filter
073590AFUSE 5A X BUSSService part / kit
098290ASM MOTOR STEPPERService part / kit
098941AHOUSING GOVERNOR CONNECTORService part / kit
098958ACONNECTOR INTERFACE ASSEMBLYService part / kit
0A7568Door weldment 1.5EPSService part / kit
0D7178TControl panel fuseService part / kit
0D8656BASE MOUNTING 1.5L STNRD & ACSTCService part / kit
0D8657Radiator support 1.5L MitsubishiService part / kit
0D8660Side brace 1.5L MitsubishiService part / kit
0D8664Duct acoustic & standard compartment 1.5LService part / kit
0D8666Roof acoustic & standard compartment 1.5LService part / kit
0E7886GCB 70A 2P 240V S BQ2 LB (16KW, 15KW ECOGEN)Service part / kit
0G66240KEYJuego de llaves (solo para personal de mantenimiento)Service part / kit
0G7714ASSY PCB TRI LED DISPLAYService part / kit
0H3421526R Exide BatteryService part / kit
0H3421S26R Exide batteryService part / kit
0H7853TERM BLOCK 3P UL 12-20 AWG LBLService part / kit
0H7853ATERM BLOCK 3P UL 12-20 AWG LBLService part / kit
0K2098RELAY 12VDC 30A SPST PILOT DUTY (13, 16-24KW, 15KW ECOGEN)Service part / kit
0L4836AFUEL LINE FLEX 3/4 NO PVC (13,16-24KW)Service part / kit
10000003275ASSY CONTROLLER 2020 AC HSBService part / kit
10000013645DECAL AUX SHUTDOWN (13,16-24KW)Service part / kit
10000016218SWITCH ROCKER SPST ON-OFF IP65Service part / kit
10000028268HARN AC HSB EVO2 60HZ 999 ECOGEN W/ CT (15KW ECOGEN) (NOT SHOWN)Service part / kit
10000029476BADGE ADHESITIVE GUARDIAN (24KW)Service part / kit
10000044454EWAR SEGSI (ESE1) EN (13, 16-24KW)Service part / kit
A0002197676WIFI ASSY HSBService part / kit
G005621-0Auxiliary Transfer Switch Contact KitService part / kit
G005703-0Paint KitService part / kit
G005704-0Paint KitService part / kit
G006186-0Power Management Module (50 Amps)Service part / kit
G006463-4Mobile LinkService part / kit
G006485-0Scheduled Maintenance KitService part / kit
G006829-0Scheduled Maintenance KitService part / kit
G007000-0Smart Management Module (50 amp)Service part / kit
G007000-1Generac Load Manager (50 amp)Service part / kit
G007005-0Wi-Fi LP Fuel Level MonitorService part / kit
G007006-0Smart Management Module (100 amp)Service part / kit
G007006-1Generac Load Manager (100 amp)Service part / kit
G007009-0LTE LP Tank Fuel Level MonitorService part / kit
G007027-0Fascia Base Wrap KitService part / kit
G007101-0Battery Pad WarmerService part / kit
G007102-0Oil WarmerService part / kit
G007102-1Oil HeaterService part / kit
G007103-1Breather WarmerService part / kit
G007103-2Breather HeaterService part / kit
G007169-0Mobile Link® Cellular Accessories - 4G LTEService part / kit
G007170-0Mobile Link® Cellular Accessories - Wi-Fi/EthernetService part / kit
G007211-0Battery HeaterService part / kit
G007216-0Scheduled Maintenance KitService part / kit
G007220-0Base Plug Kit - BisqueService part / kit
G007301-0High Altitude KitService part / kit
G007303-0High Altitude Kit (20 kW)Service part / kit
G007305-0High Altitude KitService part / kit
G009918-0Touch-Up Paint KitService part / kit
G050277DECAL OIL DRAIN (10,20-24KW)Service part / kit
0K3717EcoGen Oil System Drain Pump KitPump
0G0767ASpark Plug (RC12YC or equivalent)Spark plug
RC12YCRecommended Spark PlugSpark plug
G006199-0PMM Starter KitStarter

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Generac G-Force 1000 Series?

The Generac G-Force 1000 Series engine has an oil capacity of 1.8 liters.

What is the displacement of the Generac G-Force 1000 Series?

The Generac G-Force 1000 Series has a displacement of 0.999 liters with 2 cylinders.

Which generators use the Generac G-Force 1000 Series engine?

The Generac G-Force 1000 Series powers 14 generator set(s), including Generac 15 kW EcoGen, Generac G007034-0, Generac G007035, Generac G007036, Generac G007037.

How often should you change the oil in the Generac G-Force 1000 Series?

The Generac G-Force 1000 Series oil change interval is every 500 hours.

What is a common problem with the Generac G-Force 1000 Series engine?

A commonly reported issue on generators using the Generac G-Force 1000 Series is: Unit will not start in AUTO with utility loss — LED RED. Cause: Check LEDs / screen for alarms.. Fix: Check oil level and add oil as needed. If oil level is correct, contact an IASD..