Home›Repair guides›Generac›Transfer to Utility Power Source

Generac G-Force 1000 Series — Transfer to Utility Power Source

Operation · Transfer switch

For the Generac G-Force 1000 Series, from the Generac owner's manual.

Applies to: Generac G-Force 400 Series engine, Generac G-Force 800 Series engine, Generac G-Force 1000 Series engine

Procedure

  1. Set MLCB (generator disconnect) to OFF (OPEN).
  2. Run engine for one minute at no-load to stabilize internal temperature.
  3. Press OFF button on control panel; engine will shut down.
  4. Verify utility power supply to transfer switch is turned off.
  5. Set main contacts to UTILITY using manual transfer handle inside transfer switch.
  6. Turn on utility power supply to transfer switch using means provided.
  7. Press AUTO button on control panel.
  8. Return MLCB (generator disconnect) to ON (CLOSED).
  9. Close and lock lid.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.