HomeEnginesGenerac G-Force 800 Series

Generac G-Force 800 Series Engine

The Generac G-Force 800 Series is a 0.82 L 2-cylinder naturally aspirated engine rated at 3600 rpm. It powers generator sets from Generac, including the G007173-0, G007174-0, G007175-0 and G007176-0. It holds 2.1 L (0.6 gal) of oil.

Also known as: Generac G-Force 800 Series

0.816 L
Displacement
2
Cylinders
3600 rpm
Rated speed
2.1 L
Oil capacity

Engine specifications

Oil capacity2.1 L
Displacement0.816 L
Cylinders2
AspirationNaturally aspirated
Rated speed3600 rpm

Common problems

15
  • Wi-Fi network connection broken or intermittent
    Cause: Various.
    Fix: See Wi-Fi module owner’s manual.
  • Unit is set to OFF, but engine continues to run
    Cause: Controller wired incorrectly.
    Fix: Contact an IASD for assistance.
  • Unit consumes large amounts of oil
    Cause: Excessive engine oil.
    Fix: Adjust oil to correct level. See Checking Engine Oil Level.
  • No transfer to standby after utility source failure
    Cause: Generator MLCB (generator disconnect) is OFF (OPEN).
    Fix: Set generator MLCB (generator disconnect) to ON (CLOSED).
  • No AC output from generator
    Cause: Generator MLCB (generator disconnect) is OFF (OPEN).
    Fix: Set generator MLCB (generator disconnect) to ON (CLOSED).
  • Engine will not crank
    Cause: Blown fuse.
    Fix: Correct short circuit condition by replacing 7.5 A fuse in generator control panel. Contact an IASD if fuse continues to blow.
  • Engine starts hard and runs rough
    Cause: Plugged or damaged air cleaner.
    Fix: Inspect and clean air cleaner.
  • Engine cranks but will not start
    Cause: No fuel.
    Fix: Replenish fuel / turn on fuel valve.
  • NOT ACTIVATED!
    Fix: Press ESC and then ENTER to reset Install Wizard.
  • Engine damage.
    Fix: Verify proper type and quantity of engine oil prior to starting engine. Failure to do so could result in engine damage.
  • Wiring Error ALARM 2099
  • Voltage and Frequency Drop Excessively When Loads Are Applied
    Fix: TEST 14 - CHECK VOLTAGE AND FREQUENCY UNDER LOAD, BOTH LOW -> TEST 15 - CHECK FOR OVERLOAD CONDITION, NOT OVERLOADED -> GOOD -> IF RECONFIGURED TO LP GAS, VERIFY THAT PROPER PROCEDURE WAS FOLLOWED (REFER TO INSTALLATION MANUAL), GOOD -> OVERLOADED -> DISCONTINUE TESTING, REDUCE LOADS TO UNIT’S RATED CAPACITY, TEST 12 - CHECK STEPPER MOTOR CONTROL, GOOD -> BAD -> REPAIR OR REPLACE, LOOK FOR A SHORTED CONDITION IN A CONNECTED LOAD OR IN ONE OF THE LOAD CIRCUITS, GOOD -> TEST 7 - CHECK STATOR AC POWER WINDINGS, ENGINE CONDITION GOOD -> REPAIR OR REPLACE, BAD -> TEST 16 - CHECK ENGINE CONDITION, GOOD -> GO TO “PROBLEM 18 - ENGINE STARTS HARD AND RUNS ROUGH/LACKS POWER” SECTION 4.3
  • Utility failure 0
    Fix: Crank and start engine, transfer load to Generator if Utility returns above 75% nominal for 15 seconds
  • Unstable Voltage or Incorrect Output Which is Not Triggering a Shutdown
    Fix: TEST 1 - CHECK AC OUTPUT VOLTAGE, ERRATIC -> PROCEED TO PROBLEM 3
  • Undervoltage 1902

Compiled from service & troubleshooting documentation across every generator set that uses the Generac G-Force 800 Series.

Maintenance schedule

ItemSpecCapacityPart #Interval
Oil2.4 L200 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

36
ItemActionHoursMonthsNotes
Oil levelCheck24 hrMonthly or 24 hours of continuous operation
Aceite del motorChange25 hrFirst service — Después del período de asentamiento de 25 horas, se recomienda utilizar el aceite 5W-20 propiedad de Generac para uso continuo.
Huile moteur et filtre à huileChange25 hrFirst service — Après les premières 25 heures de marche
Jeu des soupapesAdjust25 hrFirst service — Après les premières 25 heures de marche; puis toutes les 400 heures
Engine oil and filterReplace100 hr12 moFirst service — After first 25 hours; then every 100 hours or 1 year. Cold weather (<4.4°C) or continuous hot (>29.4°C): every 100 hours or 1 year
Air cleanerInspect200 hr24 mo2Y or 200 hours
Air cleanerReplace200 hr24 mo2Y or 200 hours
Battery condition and chargeCheck200 hr24 moSchedule A maintenance
Complete tune-upOther200 hr24 mo2Y or 200 hours; to be completed by a dealer
OilChange200 hr24 mo2Y or 200 hours; change after first 8 hours
Oil filterChange200 hr24 mo2Y or 200 hours; change after first 8 hours
Óleo lubrificante e filtro de óleoChange200 hr24 moFirst service — Trocar após as primeiras 25 horas; Programação A (2 anos ou 200 h); em clima frio (<4,4 °C) ou quente contínuo (>29,4 °C) anualmente ou 100 h
Aceite del motor y filtro de aceiteReplace400 hr48 moFirst service — Programa B: cada cuatro años o 400 horas.
Air filterReplace400 hr48 moSchedule B maintenance
Bujía(s)Replace400 hr48 moPrograma B: cada cuatro años o 400 horas.
Engine air filterReplace400 hr48 moSchedule B. Emissions-critical.
Engine oil and oil filterChange400 hr48 moFirst service — Schedule B (every four years or 400 hours).
Filtro de aire del motorReplace400 hr48 moPrograma B: cada cuatro años o 400 horas.
Filtro de ar do motorReplace400 hr48 moProgramação B (4 anos ou 400 h)
Folga da válvulaAdjust400 hr48 moFirst service — Inspecionar/ajustar após as primeiras 25 h e depois a cada 400 h; Programação B; exclui 14/18 kW com motor 816 cc
Sediment trapClean400 hr48 moSchedule B maintenance
Separación de la válvulaAdjust400 hr48 moFirst service — Programa B. Inspeccione y ajuste después de las primeras 25 horas y luego cada 400 horas. No necesario en unidades 14/18 kW con motor 816 cc.
Spark plug(s)Inspect400 hr48 moSchedule B maintenance; clean, inspect gap, replace if necessary
Spark plug(s)Replace400 hr48 moSchedule B. Emissions-critical.
Valve clearanceAdjust400 hr48 moFirst service — Schedule B; inspect/adjust valve clearance after first 25 hours of operation, then at 400 hour intervals. Where applicable; excludes units with hydraulic lifters (14 or 18 kW with 816cc engine).
Vela(s) de igniçãoReplace400 hr48 moProgramação B (4 anos ou 400 h)
BateriaCheck12 moEstado da bateria; todos os anos
Battery charge stateCheck6 moEvery 6 months
Battery electrolyte levelCheck6 moEvery 6 months
Condición de la bateríaInspect12 moAnualmente (revisión de batería y carga).
Fuel systemTest12 moEvery year: perform fuel system leak test.
Fuel system leak testTest12 mo
Prueba de fugas del sistema de combustibleTest12 moAnualmente.
Sistema de combustívelTest12 moTeste de vazamento; todos os anos
Valve clearanceCheck6 moFirst service — After first 6 months of operation
Water intrusionInspect12 mo

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
GapFolga da vela de ignição0,020pol
GapFolga da vela de ignição0,040pol
GapFolga da vela de ignição0,508mm
GapFolga da vela de ignição1,02mm
GapIgnition magneto air gap0.008-0.012 inch (0.20-0.30 mm)gapV-twin engines; fixed non-adjustable on single cylinder
GapIgnition magneto air gap (V-twin)0.008-0.012 (0.20-0.30mm)inch
GapMagneto gap between flywheel (during replacement)0.010inch
GapSeparación de las bujías0.508mm (0.020 pulg.)
GapSeparación de las bujías1.02mm (0.040 pulg.)
GapSpark plug gap0.020in
GapSpark plug gap0.030inch8, 10 & 20kW
GapSpark plug gap0.040inch12, 14, 16 & 17kW
GapSpark plug gap0.508mm
GapSpark plug gap0.76mm8, 10 & 20kW
GapSpark plug gap0.76 mm (0.030 inch)gap410 cc and 530 cc engines
GapSpark plug gap1.02mm12, 14, 16 & 17kW
GapSpark plug gap1.02 mm (0.040 inch)gap990 cc and 999 cc engines
GapSpark plug gap (10 kW)0.020in (0.508 mm)
GapSpark plug gap (14-24 kW)0.040in (1.02 mm)
GapSpark plug gap (410cc 6/7 kW)0.030inch
GapSpark plug gap (530cc 9/10 kW)0.030inch
GapSpark plug gap (990cc 13/16/18 kW)0.040inch
GapÉcartement de bougie0,508mm (0,020 po)
GapÉcartement de bougie1,02mm (0,040 po)
OtherBattery charge output0.050 to 2.5amps
OtherCompression Ratio GH-4108.6:1
OtherCompression Ratio GT-5309.5:1
OtherCompression Ratio GT-9909.5:1
OtherCompression Ratio GT-9999.5:1
OtherFusível do painel de controle7,5A
OtherOrdem de partida (10 kW)15 s de arranque, 7 s de repouso, seguidos por quatro ciclos adicionais de 7 s de arranque e 7 s de repousocinco ciclos de manivela
OtherOrdem de partida (14 a 24 kW)16 s de arranque, 7 s de repouso, 16 s de arranque, 7 s de repouso, seguidos por três ciclos adicionais de 7 s de arranque e 7 s de repousocinco ciclos de manivela
OtherPerda de potência do motor por altitude3,5% a cada 304,8 m (1.000 pés) acima do nível do mar
OtherPerda de potência do motor por temperatura1% a cada 6 °C (10 °F) acima de 15 °C (60 °F)
OtherRated Horsepower @ 3,600 rpm GH-41014.8HP
OtherRated Horsepower @ 3,600 rpm GT-53018HP
OtherRated Horsepower @ 3,600 rpm GT-99032HP
OtherRated Horsepower @ 3,600 rpm GT-99936HP
OtherRedução de classificação GN vs PL10 a 20%
OtherStarter motor performance, V-twinMinimum rpm 3250; Maximum Amps 62
OtherStarter motor performance, single cylinderMinimum rpm 4500; Maximum Amps 9
OtherTamanho mínimo de tanque de PL ao converter de GN946L (250 gal)
PressureCompression difference between cylinders maximum25percent
PressureCompression minimum (single cylinder)60psicold
PressureCylinder leak down acceptable leakage20percent
PressureCylinder leak down regulated pressure80psi
PressureCylinder leak down tester regulated pressure80psiair source at least 90 psi
PressureFuel pressure (Liquid Propane)10-12in water column (2.49-2.99 kPa)at generator fuel inlet
PressureFuel pressure (Natural Gas)3.5-7.0in water column (0.87-1.74 kPa)at generator fuel inlet
PressureFuel pressure LP10 to 12inches water columnrequired
PressureFuel pressure LP maximum14inches water column
PressureFuel pressure LP minimum11inches water column
PressureFuel pressure LP never below10inches water column
PressureFuel pressure natural gas5 to 7inches water columnrequired
PressureFuel pressure natural gas maximum7inches water column
PressureFuel pressure natural gas minimum5inches water column
PressureFuel pressure natural gas never below4inches water column
PressureFuel pressure to regulator (LP)10-12in water column (2.49-2.99 kPa)
PressureFuel pressure to regulator (NG)3.5-7.0in water column (0.87-1.74 kPa)
PressureFuel pressure, LP vapor10-12inches water columnat fuel inlet

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilAPI SJ, SL ou mieuxChanger l'huile chaque année ou toutes les 100 heures par temps froid (< 4,4 °C) ou exploitation continue par temps chaud (> 29,4 °C)
Engine oil10W-30API Service Class SJ, SL or betterBetween 40° F and -10° F
Engine oil5W-20Aceite 5W-20 propiedad de Generac para uso continuo, después del período de asentamiento de 25 horas.
Engine oil5W-20 (Generac proprietary)API Service Class SJ, SL, or better1.03 LOil capacity including filter. Use for continuous use after the 25 hour break-in period; specifically formulated for gaseous powered Generac generators. Do not use special additives. Change every year or 100 hours in cold weather (below 40 F) or continuous hot weather (above 85 F).
Engine oil5W-30Aceite orgánico 5W-30 prellenado de fábrica.
Engine oilGenerac 5W-20 exclusiveAPI SJ, SL ou mieuxAprès la période de rodage de 25 heures et à chaque intervalle; spécialement formulée pour les génératrices Generac alimentées au gaz
Engine oilSAE 30 above 32°F; 10W-30 between 40°F and -10°F; Synthetic 5W-30 10°F and belowAPI Service Class SJ, SL or better; use no special additives1.5 QtsOil capacity including filter
Engine oilSAE 5W-20/5W-30API Service class SG, SH, or SJbelow -7°CBelow 20° F (-7° C)
Engine oilSAE 5W-30 SyntheticAPI Service class SG, SH, or SJFor all seasons
Engine oilSynthetic 5W-30API Service Class SJ, SL or better10° F and below
Engine oilSAE 10W-30API Service class SG, SH, or SJ-7°C to 15°C20° to 59° F (-7° to 15° C)
Engine oilSAE 30API Service class SG, SH, or SJabove 16°CAbove 60° F (16° C)
FuelGás natural: mínimo 37,26 MJ/m³ (1.000 BTU/pé³); PL: mínimo 93,15 MJ/m³ (2.500 BTU/pé³)Sistema de combustível de dupla carburação; configurado de fábrica para GN
FuelGas naturalContenido de BTU de al menos 37.26 MJ/m3 (1,000 BTU/pie3); presión de suministro 0.87 a 1.74 kPa (3.5 a 7.0 pulg. de columna de agua) en la entrada de combustibleTamaño mínimo de tanque/medidor debe cubrir el generador a carga completa más todas las cargas de los artefactos.
FuelLP gasAt least 2,520 Btus per cubic foot
FuelLiquid Propane (LP) VaporBtu content at least 2,520 Btus per cubic foot; pressure 10-12 inches water column (0.36-0.43 psi)Use vapor withdrawal system only
FuelLiquid Propane (vapor)2500.0 BTU/ft3 (93.15 MJ/m3) minimumVapor withdrawn; minimum tank size 250 gal (946 L) when converting from NG
FuelLiquid propane (LP) vaporBTU content at least 2,500 BTUs per ft3 (93.15 megajoules per m3)If converting to LP gas from NG, a minimum LP tank size of 250 gal (946 L) is recommended.
FuelNatural GasBtu content at least 1,000 Btus per cubic foot; pressure 5-7 inches water column (0.18-0.25 psi)
FuelNatural gasAt least 1,000 Btus per cubic foot
FuelNatural gas (NG)BTU content at least 1,000 BTUs per ft3 (37.26 megajoules per m3)Unit factory-configured to run on NG.
FuelNatural gas or LP gas (vapor withdrawal only for LP)Natural gas Btu content at least 1,000 Btus per cubic foot; LP gas at least 2,520 Btus per cubic footRequired fuel pressure: NG 5 to 7 inches water column; LP 10 to 12 inches water column. NFPA 54 for natural gas, NFPA 58 for liquid propane.
FuelPropano líquido (vapor)Contenido de BTU de al menos 93.15 MJ/m3 (2,500 BTU/pie3); presión de suministro 2.49 a 2.99 kPa (10 a 12 pulg. de columna de agua) en la entrada de combustible946.0 L (tamaño mínimo de tanque recomendado, 250 gal)Solo sistema de recuperación de vapor. No conectar a un tanque de propano líquido de 20 o 30 lb (9 o 14 kg).
OtherÁgua destilada (baterias não lacradas)Encha apenas com água destilada; NÃO use água comum de torneira
OtherSolución de bicarbonato de sodio454.0 Agente neutralizante de ácidos para derrames de electrolito de batería.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

72
CodeNameMeaningSeverityAction
ADVERTENCIA DEL CARGADORADVERTENCIA DEL CARGADORIndicador LED amarillo encendido en cualquier estado.WarningComuníquese con un IASD.
AUXILIARY SHUTDOWNDesligamento auxiliarL’appareil ne démarre pasShutdownMettre le ou les interrupteurs d’arrêt auxiliaires en position FERMÉE (I); effacer l’alarme.
BAJA PRESIÓN DEL ACEITEBAJA PRESIÓN DEL ACEITELa unidad no arranca en AUTO con una pérdida de energía eléctrica.ShutdownRevise el nivel de aceite y reponga si es necesario. Si el nivel de aceite es correcto, comuníquese con un IASD.
BAJA VELOCIDADBAJA VELOCIDADLa unidad no arranca en AUTO con una pérdida de energía eléctrica.ShutdownComuníquese con un IASD.
BATERÍA BAJABATERÍA BAJAIndicador LED amarillo encendido en cualquier estado.WarningBorre la alarma. Navegue hasta BATTERY MENU del MAIN MENU para revisar la batería. Si indica GOOD, comuníquese con un IASD. Si indica CHECK BATTERY, reemplace la batería.
BATTERY PROBLEMProblème de batterieVoyant JAUNE allumé dans tous les étatsWarningS’adresser à un IASD.
Battery ProblemBattery FaultBattery condition poor or battery charger issueWarningInspect battery condition and connections. Contact IASD if needed.
CARGADOR SIN CACARGADOR SIN CAIndicador LED amarillo encendido en cualquier estado.WarningComuníquese con un IASD.
CHARGER MISSING ACChargeur sans c.a.Voyant JAUNE allumé dans tous les étatsWarningS’adresser à un IASD.
CHARGER WARNINGAviso de carregadorVoyant JAUNE allumé dans tous les étatsWarningS’adresser à un IASD.
CONTROLLER FAULTAnomalia no controladorFalha do controlador.ShutdownEntre em contato com uma IASD.
Controller FaultControl Module FailureInternal controller fault detectedShutdownS’adresser à un IASD.
DESCONEXIÓN AUXILIARDESCONEXIÓN AUXILIARLa unidad no arranca.ShutdownColoque los interruptores de desconexión auxiliar en posición CERRADA (I).
DOWNLOAD FAILUREFalha na importaçãoFalha de download.WarningVerifique o ficheiro e tente novamente.
Download FailureÉchec du téléchargementAvertissement affiché par le contrôleurWarningS’adresser à un IASD.
EMERGENCY STOPParagem de emergênciaParagem de emergência ativada.ShutdownEntre em contato com uma IASD.
ERROR DE CABLEADOERROR DE CABLEADOLa unidad no arranca en AUTO con una pérdida de energía eléctrica.ShutdownComuníquese con un IASD.
EXERCISE SET ERRORErro de definição de exercícioErro de definição do funcionamento de teste.WarningEntre em contato com uma IASD.
Emergency StopArrêt d’urgenceAlarme affichée par le contrôleurShutdownS’adresser à un IASD.
FALLA DE ARRANQUEFALLA DE ARRANQUELa unidad no arranca en AUTO con una pérdida de energía eléctrica.ShutdownVerifique que la válvula de cierre de la tubería de combustible esté en la posición ON. Borre la alarma. Arranque la unidad en MANUAL. Si no arranca o funciona de forma dificultosa, comuníquese con un IASD.
FIRMWARE ERROR-7Erro de firmware 7Erro de firmware.ShutdownS’adresser à un IASD.
FIRMWARE ERROR-9Erro de firmware 9Erro de firmware.WarningS’adresser à un IASD.
Fuel PressurePression de carburantAvertissement affiché par le contrôleurWarningS’adresser à un IASD.
Fuse ProblemProblème de fusibleAlarme affichée par le contrôleurShutdownVérifier/changer le fusible de 7,5 A; s’adresser à un IASD si le fusible continue de griller.
HIGH TEMPERATURETempérature élevéeUnit shuts down during operationShutdownInspecione a ventilação ao redor do gerador, admissão, exaustão e parte traseira. Se não existirem obstruções, entre em contato com uma IASD.
High TemperatureOverheatEngine operating temperature too highShutdownInspect ventilation around generator, intake, exhaust, and rear. Ensure no obstructions present.
INSPECCIONE LA BATERÍAINSPECCIONE LA BATERÍAIndicador LED amarillo encendido en cualquier estado.WarningInspeccione la batería. Presione ENTER para borrar.
INSPECT BATTERYInspecter la batterieVoyant JAUNE allumé dans tous les étatsWarningInspecter la batterie; appuyer sur ENTER pour effacer.
LOW BATTERYLow Battery AlarmYellow LED illuminated in any stateWarningEffacer l’alarme; vérifier la batterie au MENU BATTERIE; si BON, s’adresser à un IASD; si VÉRIFICATION NÉCESSAIRE, changer la batterie.
LOW OIL PRESSUREPressão de óleo baixaUnit will not start in AUTO with utility lossShutdownVérifier le niveau d’huile et le compléter; si correct, s’adresser à un IASD.
LOW VOLTS REMOVE LOADTensão baixa, remova a cargaUnit will not start in AUTO with utility lossWarningEffacer l’alarme et séparer les circuits de charge, mettre en mode AUTO et redémarrer.
Loss of Serial LinkPerte de liaison sérieAlarme affichée par le contrôleurShutdownS’adresser à un IASD.
Loss of Speed SignalPerte de signal de vitesseAlarme affichée par le contrôleurShutdownS’adresser à un IASD.
Low BatteryBattery Voltage LowStarting battery voltage below acceptable levelWarningInspect battery and battery cables. Charge or replace battery if necessary.
Low Oil PressureLow Oil Level or PressureInsufficient oil pressure in engineShutdownCheck engine oil level and top up if necessary. Contact IASD if problem persists.
NINGUNANINGUNA (LED verde parpadeando)La unidad funciona en AUTO, pero no energiza la casa.InfoRevise el MLCB del generador (desconexión del generador). Si está encendido, comuníquese con un IASD.
NO ACTIVADANO ACTIVADALa unidad no arranca en AUTO con una pérdida de energía eléctrica.InfoVerifique si la pantalla indica que la unidad no está activada. Consulte Activación.
NOT ACTIVATEDNão ativadoNe démarre pas en mode AUTO en cas de panne de réseau électriqueInfoVoir la section Activation dans le manuel d’installation.
OVERCRANKOvercrank AlarmUnit will not start in AUTO with utility lossShutdownVérifier que le robinet d’arrêt de carburant est ouvert; effacer l’alarme; démarrer en mode MANUEL; sinon s’adresser à un IASD.
OVERLOAD REMOVE LOADSurcharge, retrait de charge nécessaireUnit shuts down during operationShutdownEffacer l’alarme et séparer les circuits de charge de la génératrice, mettre en mode AUTO et redémarrer.
OVERLOAD WARNINGAviso de sobrecargaAviso de sobrecarga.WarningRemova as cargas domésticas do gerador.
OVERSPEEDSurvitesseNe démarre pas en mode AUTO en cas de panne de réseau électriqueShutdownS’adresser à un IASD.
OVERVOLTAGETensão excessivaNe démarre pas en mode AUTO en cas de panne de réseau électriqueShutdownS’adresser à un IASD.
OvercrankExtended CrankingEngine failing to start after extended crank attemptsShutdownCheck fuel supply, spark plugs, and fuel system. Contact IASD for further diagnosis.
OverloadOverload DetectedElectrical load exceeds generator capacityShutdownRemove household electrical loads from generator
OverspeedRPM OverspeedEngine running at excessive RPMShutdownContact IASD for assistance
OvervoltageOutput Voltage HighGenerator voltage exceeding nominal ratingShutdownReduce electrical load and restart. Contact IASD if issue persists.
PROBLEMA DE BATERÍAPROBLEMA DE BATERÍAIndicador LED amarillo encendido en cualquier estado.WarningComuníquese con un IASD.
PÉRDIDA DE DETECCIÓN DE RPMPÉRDIDA DE DETECCIÓN DE RPMLa unidad funcionaba, se apagó e intenta reiniciarse, o no arranca en AUTO con una pérdida de energía eléctrica.ShutdownBorre la alarma y retire del generador las cargas del hogar. Vuelva a poner en AUTO y reinicie. Si el generador no arranca, comuníquese con un IASD.
RPM SENSE LOSSRPM Sense Loss AlarmUnit was running and shuts down, attempts to restartShutdownEffacer l’alarme et séparer les circuits de charge, mettre en mode AUTO et redémarrer; s’adresser à un IASD si la génératrice ne démarre pas.
RPM Sensor LossRPM Signal LossRPM sensor signal not detectedShutdownContact IASD for assistance
SEEPROM ABUSEAbus de SEEPROMAvertissement affiché par le contrôleurWarningS’adresser à un IASD.
SERVICE AService A Maintenance AlertYellow LED illuminated - maintenance dueWarningRealize a manutenção SERVICE A. Pressione ENTER para apagar.
SERVICE BService B Maintenance AlertYellow LED illuminated - maintenance dueWarningRealize a manutenção SERVICE B. Pressione ENTER para apagar.
SERVICIO ASERVICIO AIndicador LED amarillo encendido en cualquier estado.WarningRealice el mantenimiento SERVICIO A. Presione ENTER para borrar.
SERVICIO BSERVICIO BIndicador LED amarillo encendido en cualquier estado.WarningRealice el mantenimiento SERVICIO B. Presione ENTER para borrar.
SOBRECARGA. RETIRE LA CARGASOBRECARGALa unidad se apaga durante el funcionamiento.ShutdownBorre la alarma y retire del generador las cargas del hogar. Vuelva a poner en AUTO y reinicie.
SOBRECORRIENTE DEL MOTOR DE VELOCIDAD GRADUALSOBRECORRIENTE DEL MOTOR DE VELOCIDAD GRADUALLa unidad no arranca en AUTO con una pérdida de energía eléctrica.ShutdownComuníquese con un IASD.
SOBREVELOCIDADSOBREVELOCIDADLa unidad no arranca en AUTO con una pérdida de energía eléctrica.ShutdownComuníquese con un IASD.
SOBREVOLTAJESOBREVOLTAJELa unidad no arranca en AUTO con una pérdida de energía eléctrica.ShutdownComuníquese con un IASD.
STEPPER OVERCURRENTSurintensité du moteur pas-à-pasNe démarre pas en mode AUTO en cas de panne de réseau électriqueShutdownS’adresser à un IASD.
SUBVOLTAJESUBVOLTAJELa unidad no arranca en AUTO con una pérdida de energía eléctrica.ShutdownComuníquese con un IASD.
TEMPERATURA ALTATEMPERATURA ALTALa unidad se apaga durante el funcionamiento.ShutdownInspeccione la ventilación alrededor del generador, además de las secciones de entrada, escape y trasera. Si no hay obstrucciones, comuníquese con un IASD.
UNDERSPEEDSous-vitesseNe démarre pas en mode AUTO en cas de panne de réseau électriqueShutdownS’adresser à un IASD.
UNDERVOLTAGESubtensãoNe démarre pas en mode AUTO en cas de panne de réseau électriqueShutdownS’adresser à un IASD.
USB WARNINGAviso de USBAviso relacionado ao dispositivo USB.WarningTente novamente com USB de melhor qualidade. Os nomes dos ficheiros no USB não podem ter mais de 8 caracteres.
USB WarningAvertissement USBAvertissement affiché par le contrôleurWarningS’adresser à un IASD.
UnderspeedEngine Speed Too LowEngine RPM below nominal specificationShutdownContact IASD for assistance
UndervoltageOutput Voltage LowGenerator voltage below nominal ratingShutdownReduce electrical load and restart. Contact IASD if issue persists.
VOLTIOS BAJOS. RETIRE LA CARGAVOLTIOS BAJOSLa unidad no arranca en AUTO con una pérdida de energía eléctrica.ShutdownBorre la alarma y retire del generador las cargas del hogar. Ponga en AUTO y reinicie.
WIRING ERRORErro de fiaçãoNe démarre pas en mode AUTO en cas de panne de réseau électriqueShutdownS’adresser à un IASD.
Wiring ErrorElectrical Wiring FaultWiring configuration error detectedShutdownContact IASD for assistance

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjusting Magneto Flywheel Gap adjustment

⚠ Air gap between ignition magneto and flywheel on single cylinder engines is not adjustable.

Tools: 0.008-0.012 inch thickness gauge

  1. Rotate the flywheel until the magnet is under the module (armature) laminations.
  2. Place a 0.008-0.012 inch (0.20-0.30mm) thickness gauge between flywheel magnet and module laminations.
  3. Loosen the mounting screws and let the magnet pull the magneto down against the thickness gauge.
  4. Tighten both mounting screws.
  5. To remove the thickness gauge, rotate the flywheel.
  6. Repeat the above procedure for the second magneto.
Adjusting Valve Clearance adjustment

⚠ Risk of Burn. Allow the engine to cool before performing the following procedure.

Tools: feeler gauge, 10 mm wrench, 13 mm wrench, 14 mm wrench, 10 mm hex key

  1. Remove spark plug wire(s) and position away from spark plug(s).
  2. Remove spark plug(s).
  3. Remove the four screws attaching valve cover. Remove and discard gasket.
  4. Verify piston is at TDC of its compression stroke (both valves closed).
  5. Loosen rocker jam nut using a 10 mm wrench (10 kW units) or 13 mm wrench (20-24 kW units).
  6. Turn pivot ball stud using a 14 mm wrench (10 kW) or 10 mm hex key (20-24 kW) while checking clearance with a feeler gauge.
  7. Hold pivot ball stud and tighten rocker arm jam nut.
  8. Inspect valve clearance to verify it did not change.
  9. Install new valve cover gasket and valve cover; tighten fasteners in a cross pattern.
  10. Install spark plug(s) and tighten to 18 ft-lbs (25 Nm); attach spark plug wires.
  11. Repeat process for other cylinder if equipped.
Ajustar a folga das válvulas adjustment

⚠ Risco de queimaduras. Deixe o motor esfriar antes de executar o procedimento.

Tools: Chave de 10 mm, Chave de 13 mm, Chave de 14 mm, Chave sextavada de 10 mm, Calibrador

  1. Remova os fios das velas de ignição e remova as velas de ignição.
  2. Remova os quatro parafusos que prendem a tampa da válvula; descarte a junta.
  3. Verifique se o pistão está no TDC do seu curso de compressão.
  4. Solte a contraporca do balanceiro (C) com chave de 10 mm ou 13 mm.
  5. Gire o pino de esfera articulada (D) com chave de 14 mm ou sextavada de 10 mm e ajuste a folga.
  6. Aperte a contraporca do braço oscilante e inspecione a folga novamente.
  7. Instale a nova junta e as tampas das válvulas; aperte em padrão transversal.
  8. Instale as velas e aperte a 25 Nm; conecte os fios das velas.
Ajuste de la separación de la válvula adjustment

⚠ Deje que el motor se enfríe antes del procedimiento.

⚠ Desconecte el cable negativo y luego el positivo de la batería.

⚠ No necesario en unidades 14 o 18 kW con motor de 816 cc.

Tools: Llave de 10 mm, Llave de 13 mm, Llave de 14 mm, Llave hexagonal de 10 mm, Galga de espesores

  1. Retire los hilos de las bujías y las bujías.
  2. Retire los cuatro tornillos de la cubierta de la válvula y deseche la junta.
  3. Verifique que el pistón esté en el PMS de su carrera de compresión.
  4. Suelte la contratuerca del balancín (llave 10 mm en 10 kW, 13 mm en 20 a 24 kW).
  5. Gire el espárrago del pivote (llave 14 mm en 10 kW, hexagonal 10 mm en 20 a 24 kW) ajustando la separación.
  6. Sostenga el espárrago y apriete la contratuerca del balancín.
  7. Inspeccione la separación para verificar que no cambió.
  8. Instale una junta nueva y la cubierta de la válvula; apriete en patrón cruzado.
  9. Instale las bujías y apriete a 25 Nm (18 lb-pie).
  10. Conecte los hilos de las bujías.
Ajuster le jeu des soupapes adjustment

⚠ Risque de brûlure : laisser le moteur refroidir avant d’exécuter la procédure.

⚠ Réglage non requis sur les modèles de 14 ou 18 kW à moteur de 816 cc.

Tools: Clé de 10 mm ou 13 mm, Clé de 14 mm ou clé hexagonale de 10 mm, Jauge d’épaisseur

  1. Laisser le moteur refroidir.
  2. Débrancher les câbles de bougie et les placer à l’écart.
  3. Retirer les bougies.
  4. Retirer les quatre vis du cache-culbuteurs et mettre le joint au rebut.
  5. S’assurer que le piston est au point mort haut (PMH) de sa course de compression.
  6. Desserrer le contre-écrou de culbuteur.
  7. Faire tourner le goujon pivot tout en contrôlant le jeu avec une jauge d’épaisseur.
  8. Ajuster le jeu conformément à la section Moteur.
  9. Tenir le goujon pivot et serrer le contre-écrou au couple spécifié.
  10. Poser un joint de cache-culbuteurs neuf et remonter le cache-culbuteurs.
  11. Mettre les bougies en place au couple de 25 Nm (18 pi-lb).
Check and Adjust Engine Governor (Single Cylinder Units) adjustment

Tools: frequency meter

  1. Loosen governor clamp bolt.
  2. Hold governor lever at wide open throttle; rotate governor shaft clockwise fully; tighten clamp bolt to 70 inch-pounds.
  3. Start generator and let stabilize at no-load.
  4. Connect frequency meter across AC output leads.
  5. Turn primary adjust screw to obtain 61.5 Hz.
  6. Turn secondary adjust screw to obtain 62.5 Hz.
  7. Check AC voltage; adjust voltage regulator if needed.
Check and Adjust Ignition Magnetos adjustment

⚠ Magneto air gap on single cylinder engines is non-adjustable.

Tools: VOM, thickness gauge 0.008-0.012 inch

  1. Disconnect Wire 18 from terminal by oil cooler.
  2. Disconnect spark plug wires from spark plugs.
  3. Measure primary winding resistance: approximately 300K ±10K ohms.
  4. Measure secondary winding resistance: approximately 14K ±3K ohms.
  5. Check diode isolation between magnetos; INFINITY should be measured.
  6. For V-twin, rotate flywheel until magnet is under laminations.
  7. Place 0.008-0.012 inch thickness gauge between magnet and laminations.
  8. Loosen mounting screws and let magnet pull magneto down against gauge.
  9. Tighten both mounting screws.
  10. Remove gauge by rotating flywheel.
  11. Repeat for second magneto.
  12. Retest for spark.
Check and Adjust Valves adjustment

⚠ Make sure piston is at TDC of compression stroke with both valves closed.

Tools: 10mm allen wrench, flat feeler gauge, torque wrench

  1. Remove four screws from rocker cover.
  2. Remove rocker cover and gasket.
  3. Loosen rocker arm jam nut.
  4. Use 10mm allen wrench to turn pivot ball stud; check clearance with flat feeler gauge.
  5. When correct, hold stud and tighten jam nut to 174 inch pounds.
  6. Recheck valve clearance.
  7. Re-install gasket, cover, and four screws.
Conversión de combustible (GN a PL) adjustment

⚠ La perilla del selector de combustible debe ajustarse al combustible correcto para que el generador funcione correctamente.

  1. Ubique la perilla de conversión de combustible naranja (bajo el mezclador en 10 kW; sobre el mezclador en 14 a 24 kW).
  2. Gire la perilla de conversión hacia la flecha del tipo de combustible marcado hasta que se detenga.
  3. La perilla gira 180° y se desliza hacia dentro del mezclador al convertir a propano líquido.
  4. Ingrese la selección de combustible (PL/GN) en el controlador mediante el Asistente de instalación o el menú EDITAR.
Reconfiguring The Fuel System (6/7 kW, 410cc Engine) adjustment

⚠ Use approved pipe sealant or joint compound on all threaded fittings.

  1. Turn off main gas supply.
  2. Open roof and remove door.
  3. Remove battery if installed.
  4. Disconnect Wire 0 and Wire 14 from gas solenoid.
  5. Remove carburetor fuel hose from demand regulator outlet.
  6. Remove demand regulator mounting fastener.
  7. Swap pipe plug and brass hose barb between outlet ports.
  8. Reverse steps to reinstall demand regulator.
  9. Insert plastic plug into 3/4 inch hole on air cleaner base.
  10. Check for gas leakage at plug, hose, and fittings.
Reconfiguring The Fuel System (9, 10, 13, 16, 18 kW V-twin Engines) adjustment
  1. Open the roof.
  2. For 9/10 kW: loosen clamp and slide back air inlet hose; slide fuel selector out toward back; return hose and tighten clamp.
  3. For 13/16/18 kW: remove air cleaner cover; slide selector lever out toward back; return cover and tighten thumb screws.
  4. Close the roof.
  5. Reverse procedure to convert back to natural gas.
Reconfiguring the Fuel System (8kW) adjustment

⚠ Gaseous fuels are highly explosive. No leakage permitted.

Tools: plastic T-handle fuel selector

  1. Turn off main gas supply.
  2. Open roof and remove door.
  3. Remove battery if installed.
  4. Insert T-handle pin into selector knob hole.
  5. Pull out to overcome spring pressure, twist clockwise 90 degrees.
  6. Allow selector to return once aligned with LP position.
  7. Save tool with Owner's Manual.
  8. Install battery, door, close roof; reverse to convert back.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
Control system interconnectionsN1, N2, 0, 15B, 23Can be run in same conduit as AC power if length < 35 feet and all wiring rated 600V
N1, N2, T1, Leads 23 and 194All conductors rated for minimum 300VClass 1 remote control/signaling circuits. Install per NEC Article 300 and recognized wiring methods. Sense wires through wire tie C1 to sense wire terminal block B. Control wires through wire tie C2 to control wire terminal block A.
1Connect a 2008 and later load center switch to a pre-2008 air-cooled generator: Wire 0 will not be utilized. Remove battery charger from the transfer switch. Connect N1 (BLU) to N1 (YEL), N2 (YEL) to N2 (YEL), 23 (BRN) to 23 (WHT), 194 (ORG) to 15B (RED) using UL approved wire nuts.N1, N2, 23, 194, 15B, 0Battery charger in transfer switch will not be utilized in operation of the generator.
1Connect a pre-2008 load center switch to a current or future air-cooled generator: Wire 0 will not be utilized. Connect N1 (BLU) to N1 (YEL), N2 (YEL) to N2 (YEL), 23 (BRN) to 23 (WHT), 194 (ORG) to 15B (RED) using UL approved wire nuts.N1, N2, 23, 194, 15B, 0Wire 194 changed to 15B on current model air-cooled generators.
1201Battery charger AC input to generator backed-up 120VAC circuit120VAC hot, neutralConnect via wire nuts
120/2401GENERATOR (STANDBY) source power cables to ATS GENERATOR supply terminalsE1, E2200A models
120/2401Non-essential customer LOAD leads to LSS switch terminalsE1, E2Load shed switch
120/2401UTILITY (NORMAL) power source cables to top of UTILITY SERVICE DISCONNECT circuit breakerN1, N2200A models
2401Transfer switch terminal lugs: connect utility source hot lines to N1 and N2; connect standby source hot lines (E1, E2) to E1 and E2; connect load lines from T1 and T2 to electrical load circuit; connect UTILITY, STANDBY and LOAD neutral lines to neutral block.N1, N2, E1, E2, T1, T2In 1-phase systems with a 2-pole transfer switch.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Generac G-Force 800 Series?

The Generac G-Force 800 Series engine has an oil capacity of 2.1 liters.

What is the displacement of the Generac G-Force 800 Series?

The Generac G-Force 800 Series has a displacement of 0.816 liters with 2 cylinders.

Which generators use the Generac G-Force 800 Series engine?

The Generac G-Force 800 Series powers 16 generator set(s), including Generac G007173-0, Generac G007174-0, Generac G007175-0, Generac G007176-0, Generac G007177-0.

How often should you change the oil in the Generac G-Force 800 Series?

The Generac G-Force 800 Series oil change interval is every 200 hours.

What is a common problem with the Generac G-Force 800 Series engine?

A commonly reported issue on generators using the Generac G-Force 800 Series is: Wi-Fi network connection broken or intermittent. Cause: Various.. Fix: See Wi-Fi module owner’s manual..