| AUXILIARY SHUTDOWN | Auxiliary Shutdown | Unit will not start | Shutdown | Set auxiliary shutdown switch(es) to CLOSED (I); clear alarm |
| BATERÍA BAJA | BATERÍA BAJA | Indicador LED amarillo encendido en cualquier estado. | Warning | Borre la alarma. Navegue hasta BATTERY MENU del MAIN MENU para revisar la batería. Si indica GOOD, comuníquese con un IASD. Si indica CHECK BATTERY, reemplace la batería. |
| Battery Problem | Battery Fault | Battery condition poor or battery charger issue | Warning | Inspect battery condition and connections. Contact IASD if needed. |
| BATTERY PROBLEM | Problema de batería | El LED amarillo se ilumina en cualquier estado | Warning | Contactar un IASD |
| CARGADOR SIN CA | CARGADOR SIN CA | Indicador LED amarillo encendido en cualquier estado. | Warning | Comuníquese con un IASD. |
| CHARGER MISSING AC | Charger Missing AC | Yellow LED illuminated in any state | Warning | Contact an IASD |
| CHARGER WARNING | Advertencia del cargador | El LED amarillo se ilumina en cualquier estado | Warning | Contactar un IASD |
| Controller Fault | Control Module Failure | Internal controller fault detected | Shutdown | Contact IASD for assistance |
| CONTROLLER FAULT | Controller Fault | Alarm message listed on controller menu. | Shutdown | Contact an IASD. |
| DESCONEXIÓN AUXILIAR | DESCONEXIÓN AUXILIAR | La unidad no arranca. | Shutdown | Coloque los interruptores de desconexión auxiliar en posición CERRADA (I). |
| EMERGENCY STOP | Emergency Stop | Alarm message listed on controller menu. | Shutdown | Check emergency shutdown switch and reset. |
| FUSE PROBLEM | Fuse Problem | Unit will not start in AUTO with utility loss. (Firmware 1.11 and older only.) | Shutdown | Check the 7.5 amp fuse. If blown, replace with an ATO 7.5 amp fuse. If intact, contact an IASD. |
| High Temperature | Overheat | Engine operating temperature too high | Shutdown | Inspect ventilation around generator, intake, exhaust, and rear. Ensure no obstructions present. |
| HIGH TEMPERATURE | High Temperature | Unit shuts down during operation. | Shutdown | Check ventilation around the generator, intake, exhaust, and rear of generator. If no obstructions are present, contact an IASD. |
| INSPECCIONE LA BATERÍA | INSPECCIONE LA BATERÍA | Indicador LED amarillo encendido en cualquier estado. | Warning | Inspeccione la batería. Presione ENTER para borrar. |
| INSPECT BATTERY | Inspeccionar batería | El LED amarillo se ilumina en cualquier estado | Warning | Inspeccionar la batería; pulsar ENTER para desactivar |
| Low Battery | Battery Voltage Low | Starting battery voltage below acceptable level | Warning | Inspect battery and battery cables. Charge or replace battery if necessary. |
| LOW BATTERY | Batería baja | El LED amarillo se ilumina en cualquier estado | Warning | Desactivar la alarma; comprobar batería en BATTERY MENU; si GOOD contactar un IASD, si CHECK BATTERY sustituir la batería |
| Low Oil Pressure | Low Oil Level or Pressure | Insufficient oil pressure in engine | Shutdown | Check engine oil level and top up if necessary. Contact IASD if problem persists. |
| LOW OIL PRESSURE | Low Oil Pressure | Unit will not start in AUTO with utility loss. | Shutdown | Check oil level and add oil as needed. If oil level is correct, contact an IASD. |
| LOW VOLTS REMOVE LOAD | Low Volts | Unit will not start in AUTO with utility loss. | Shutdown | Clear alarm and remove household loads from the generator. Put in AUTO and restart. |
| MISWIRE | Miswire / Wiring Error | Unit will not start in AUTO with utility loss. | Shutdown | Contact an IASD. |
| NOT ACTIVATED | Not Activated | Unit will not start in AUTO with utility loss. | | Refer to 'Activation' in installation manual. |
| Overcrank | Extended Cranking | Engine failing to start after extended crank attempts | Shutdown | Check fuel supply, spark plugs, and fuel system. Contact IASD for further diagnosis. |
| OVERCRANK | Overcrank | Unit will not start in AUTO with utility loss. | Shutdown | Check fuel line shutoff valve is ON. Clear alarm. Start the unit in MANUAL. If it does not start or runs rough, contact an IASD. |
| Overload | Overload Detected | Electrical load exceeds generator capacity | Shutdown | Remove household electrical loads from generator |
| OVERLOAD REMOVE LOAD | Overload | Unit shuts down during operation. | Shutdown | Clear alarm and remove household loads from the generator. Put in AUTO and restart. |
| OVERLOAD WARNING | Aviso de sobrecarga | Aviso de sobrecarga. | Warning | Remova as cargas domésticas do gerador. |
| Overspeed | RPM Overspeed | Engine running at excessive RPM | Shutdown | Contact IASD for assistance |
| OVERSPEED | Overspeed | Unit will not start in AUTO with utility loss. | Shutdown | Contact an IASD. |
| Overvoltage | Output Voltage High | Generator voltage exceeding nominal rating | Shutdown | Reduce electrical load and restart. Contact IASD if issue persists. |
| OVERVOLTAGE | Overvoltage | Unit will not start in AUTO with utility loss. | Shutdown | Contact an IASD. |
| PROBLEMA DE BATERÍA | PROBLEMA DE BATERÍA | Indicador LED amarillo encendido en cualquier estado. | Warning | Comuníquese con un IASD. |
| RPM SENSE LOSS | Pérdida de detección de rpm | La unidad se para e intenta volver a ponerse en marcha | Shutdown | Desactivar la alarma, retirar cargas, poner en AUTO y reanudar; si no arranca contactar un IASD |
| RPM Sensor Loss | RPM Signal Loss | RPM sensor signal not detected | Shutdown | Contact IASD for assistance |
| SERVICE A | Service A | Yellow LED illuminated in any state. | Warning | Perform SERVICE A maintenance. Press ENTER to clear. |
| SERVICE B | Service B | Yellow LED illuminated in any state. | Warning | Perform SERVICE B maintenance. Press ENTER to clear. |
| SHUTDOWN SWITCH | Shutdown Switch | Unit will not start. Flashing red LED. | Shutdown | Check emergency shutdown switches. Set switch(es) to CLOSED (I). Clear alarm. |
| STEPPER OVERCURRENT | Stepper Overcurrent | Unit will not start in AUTO with utility loss. | Shutdown | Contact an IASD. |
| Underspeed | Engine Speed Too Low | Engine RPM below nominal specification | Shutdown | Contact IASD for assistance |
| UNDERSPEED | Underspeed | Unit will not start in AUTO with utility loss. | Shutdown | Contact an IASD. |
| Undervoltage | Output Voltage Low | Generator voltage below nominal rating | Shutdown | Reduce electrical load and restart. Contact IASD if issue persists. |
| UNDERVOLTAGE | Undervoltage | Unit will not start in AUTO with utility loss. | Shutdown | Contact an IASD. |
| USB WARNING | Aviso de USB | Aviso relacionado ao dispositivo USB. | Warning | Tente novamente com USB de melhor qualidade. Os nomes dos ficheiros no USB não podem ter mais de 8 caracteres. |
| Wiring Error | Electrical Wiring Fault | Wiring configuration error detected | Shutdown | Contact IASD for assistance |
| WIRING ERROR | Wiring Error | Unit will not start in AUTO with utility loss | Shutdown | Contact an IASD |