Generac G-Force 400 Series Engine

The Generac G-Force 400 Series is a 0.46 L 1-cylinder air-cooled engine rated at 3600 rpm. It powers generator sets from Generac, including the G007029-1, G007030-1, G007171-0 and G007172-0. It holds 1.03 L (0.3 gal) of oil.

Also known as: Generac G-Force 400 Series

Part of the Generac G-Force 400 engine family — 5 variants share parts & fitment.

0.46 L
Displacement
1
Cylinders
3600 rpm
Rated speed
1.03 L
Oil capacity

Engine specifications

Oil capacity1.03 L
Displacement0.46 L
Cylinders1
AspirationAir-cooled
Rated speed3600 rpm

Common problems

15
  • Unit will not start in AUTO with utility loss — LED RED LOW OIL PRESSURE
    Cause: Check LEDs / screen for alarms.
    Fix: Check oil level and add oil as needed. If oil level is correct, contact an IASD.
  • Unit will not start in AUTO with utility loss
    Cause: Start delay countdown
    Fix: If the start up delay is greater than expected, contact servicing dealer to adjust from 2 to 1500 seconds.
  • Engine starts hard and runs rough
    Cause: Plugged or damaged air cleaner
    Fix: Inspect and clean air cleaner.
  • Engine cranks but will not start
    Cause: No fuel
    Fix: Replenish fuel / turn on fuel valve.
  • Unit consumes large amounts of oil
    Cause: Excessive engine oil
    Fix: Adjust oil to correct level. See Checking Engine Oil Level.
  • No transfer to standby after utility source failure
    Cause: Generator MLCB (generator disconnect) is OFF (OPEN)
    Fix: Set generator MLCB (generator disconnect) to ON (CLOSED).
  • Yellow LED illuminated in any state LOW BATTERY
    Fix: Clear alarm. Using control panel, check battery by navigating to BATTERY MENU option from MAIN MENU. If battery condition displays GOOD, contact an IASD. If control panel displays CHECK BATTERY, replace battery
  • Unit will not start in AUTO with utility loss — LED: RED LOW OIL PRESSURE
    Fix: Check oil level and add oil as needed. If oil level is correct, contact an IASD
  • Generator produces zero voltage or residual voltage (12-20 kW)
    Cause: Main circuit breaker open or failed
    Fix: Reset to "ON" or replace if bad
  • Engine starts hard and runs rough / lacks power / backfires
    Cause: Fuel supply and pressure faulty
    Fix: Test 66 - Check fuel supply and pressure; find and correct cause of no fuel or low pressure
  • Engine cranks but won't start
    Cause: Fuel supply and pressure faulty
    Fix: Test 66 - Check fuel supply and pressure; find and correct cause of no fuel or low pressure
  • Engine will not crank
    Cause: Blown fuse
    Fix: Correct short circuit condition by replacing 7.5 A fuse in generator control panel. Contact an IASD if fuse continues to blow.
  • Voltage and Frequency Drop Excessively When Loads Are Applied
    Cause: Overload condition; if reconfigured to LP gas, improper procedure followed; stepper motor control; shorted condition in a connected load or in one of the load circuits; stator AC power windings; engine condition
    Fix: Discontinue testing; reduce loads to unit's rated capacity; verify that proper procedure was followed (refer to installation manual); repair or replace; look for a shorted condition in a connected load or in one of the load circuits; Test 7 – Check Stator AC Power Windings; Test 16 – Check Engine Condition; go to Problem 18 – Engine Starts Hard and Runs Rough/Lacks Power Section 4.3
  • No AC output from generator
    Cause: Generator MLCB (generator disconnect) is OFF (OPEN)
    Fix: Set generator MLCB (generator disconnect) to ON (CLOSED).
  • Shutdown alarm/fault occurred
    Cause: AC output frequency faulty (single cylinder units)
    Fix: Test 14 - Check AC output frequency; refer to engine service manual

Compiled from service & troubleshooting documentation across every generator set that uses the Generac G-Force 400 Series.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter0E9371AS400 hr Amazon eBay $19.99
Fuel filterServicing the air cleaner.—1200 hr
Oil filterChange the oil and oil filter.070185ES500 hr Amazon eBay $30.00 NAPA $9.09 FridayParts $22.99
Battery12 volts, Group 26R-540CCA or Group 35AGM-650CCA0H3421S200 hr Amazon eBay $283.32
Belt—
Coolant—
OilSynthetic SAE 5W-30070185E100 hr Amazon eBay $30.00 NAPA $9.09 FridayParts $45.99
Spark plugSpark plug gap 0.040 in (1.02 mm)0G0767A400 hr Amazon eBay $18.00

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

40
ItemActionHoursMonthsNotes
Aceite del motorChange25 hrFirst service — Después del período de asentamiento de 25 horas, se recomienda utilizar el aceite 5W-20 propiedad de Generac para uso continuo.
Huile moteur et filtre à huileChange25 hrFirst service — Après les premières 25 heures de marche
Engine oil and filterReplace100 hr12 moFirst service — After first 25 hours; then every 100 hours or 1 year. Cold weather (<4.4°C) or continuous hot (>29.4°C): every 100 hours or 1 year
Aceite de motor y filtro de aceiteChange200 hr24 moFirst service — Programa de mantenimiento A
Batería (condición, nivel de electrolito y estado de carga)Check200 hr24 moPrograma de mantenimiento A
Battery conditionCheck200 hr24 moSchedule A.
Battery condition and chargeCheck200 hr24 moSchedule A maintenance
Engine oilChange200 hr24 moFirst service — Up to 2 year/200 hour oil change interval
Huile à moteur et filtre à huileChange200 hr24 moFirst service — Calendrier A: tous les deux ans ou toutes les 200 heures. Changer l'huile et le filtre après les 25 premières heures. En conditions froides (moins de 4,4 °C/40 °F) ou fonctionnant en continu à plus de 29,4 °C/85 °F, changer annuellement ou toutes les 100 heures.
Óleo lubrificante e filtro de óleoChange200 hr24 moFirst service — Trocar após as primeiras 25 horas; Programação A (2 anos ou 200 h); em clima frio (<4,4 °C) ou quente contínuo (>29,4 °C) anualmente ou 100 h
Aceite del motor y filtro de aceiteReplace400 hr48 moFirst service — Programa B: cada cuatro años o 400 horas.
Air filterReplace400 hr48 moSchedule B maintenance
Battery condition, electrolyte level, and state of chargeInspect400 hr48 moSchedule B
Bougies d'allumageClean400 hr48 moNettoyer les bougies, vérifier l'écartement ou les remplacer. Calendrier A et Calendrier B.
Bujía(s)Replace400 hr48 moPrograma B: cada cuatro años o 400 horas.
BujíasReplace400 hr48 moPrograma B; limpiar, comprobar separación y sustituir
Engine air filterReplace400 hr48 moSchedule B; emissions-critical maintenance
Engine oil and oil filterChange400 hr48 moFirst service — Schedule B.
Engine oil and oil filterReplace400 hr48 moFirst service — Schedule B
Filtre à air du moteurReplace400 hr48 moCalendrier B: tous les quatre ans ou toutes les 400 heures.
Filtro de aire del motorReplace400 hr48 moPrograma de mantenimiento B
Filtro de ar do motorReplace400 hr48 moProgramação B (4 anos ou 400 h)
Folga da válvulaAdjust400 hr48 moFirst service — Inspecionar/ajustar após as primeiras 25 h e depois a cada 400 h; Programação B; exclui 14/18 kW com motor 816 cc
Jeu des soupapesAdjust400 hrFirst service — Vérifier et régler après les 25 premières heures de fonctionnement, puis toutes les 400 heures.
Luz de válvulasAdjust400 hr48 moFirst service — Programa B; inspeccionar/ajustar cada 400 horas
Sediment trapClean400 hr48 moSchedule B maintenance
Separación de la válvulaAdjust400 hr48 moFirst service — Programa B. Inspeccione y ajuste después de las primeras 25 horas y luego cada 400 horas. No necesario en unidades 14/18 kW con motor 816 cc.
Spark plug gap / spark plugClean400 hr48 moSchedule B; inspect gap and replace if necessary; emissions-critical maintenance
Spark plug(s)Clean400 hr48 moSchedule B; inspect gap and replace if necessary
Spark plug(s)Inspect400 hr48 moSchedule B maintenance; clean, inspect gap, replace if necessary
Spark plug(s)Replace400 hr48 moSchedule B. Emissions-critical.
Spark plugsReplace400 hr48 moEvery Four Years or 400 Hours (Schedule B); clean, check gap, replace
Valve clearanceAdjust400 hr48 moFirst service — Schedule B; inspect/adjust valve clearance after first 25 hours of operation, then at 400 hour intervals. Where applicable; excludes units with hydraulic lifters (14 or 18 kW with 816cc engine).
Valve clearanceInspect400 hr48 moFirst service — Where applicable; excludes units with hydraulic lifters (14 kW and 18 kW with 816cc engine).
Vela(s) de igniçãoReplace400 hr48 moProgramação B (4 anos ou 400 h)
BateriaCheck12 moEstado da bateria; todos os anos
Batterie (état, niveau d'électrolyte et état de chargement)Check12 moChaque année, Calendrier A (tous les deux ans ou toutes les 200 heures) et Calendrier B (tous les quatre ans ou toutes les 400 heures).
Battery condition, electrolyte level, and state of chargeCheck12 moEvery Year (Schedule A and B)
Battery condition, electrolyte level, state of chargeCheck12 moListed under Daily, Every Year, and Schedule A columns
Condición de la bateríaInspect12 moAnualmente (revisión de batería y carga).

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
GapFolga da vela de ignição0,020pol
GapFolga da vela de ignição0,040pol
GapFolga da vela de ignição0,508mm
GapFolga da vela de ignição1,02mm
GapSeparación de electrodos de bujía (11 kW)0.030in (0.76 mm)
GapSeparación de electrodos de bujía (16/20/22 kW)0.040in (1.02 mm)
GapSeparación de electrodos de bujía (9 kW)0.020in (0.508 mm)
GapSeparación de las bujías0.508mm (0.020 pulg.)
GapSeparación de las bujías1.02mm (0.040 pulg.)
GapSpark Plug Gap0.030in (0.76 mm)11 kW (GTH-530)
GapSpark plug gap0.020in (0.508 mm)
GapSpark plug gap0.020 in (0.508 mm)in (mm)
GapSpark plug gap0.040in (1.02 mm)
GapSpark plug gap0.040 in (1.02 mm)in (mm)
GapSpark plug gap0.508mm
GapSpark plug gap1.02mm
GapSpark plug gap (10 kW)0.020in (0.508 mm)
GapSpark plug gap (11 kW)0.030in (0.76 mm)
GapSpark plug gap (14-24 kW)0.040in (1.02 mm)
GapSpark plug gap (14–24 kW)0.040in (1.02 mm)cold
GapSpark plug gap (16/20/22 kW)0.040in (1.02 mm)
GapSpark plug gap (9 kW)0.020in (0.508 mm)
GapÉcartement de bougie0,508mm (0,020 po)
GapÉcartement de bougie1,02mm (0,040 po)
GapÉcartement des électrodes des bougies d'allumage0.508mm (0,020 po)
GapÉcartement des électrodes des bougies d'allumage0.76mm (0,030 po)
GapÉcartement des électrodes des bougies d'allumage1.02mm (0,040 po)
OtherCold Smart Start fixed temperature20 F (-7 C)F (C)22-26 kW
OtherCold Smart Start fixed temperature50 F (10 C)F (C)10-20 kW
OtherCompression ratio9.5:1
OtherExercise time length (16-22 kW)5minutes
OtherExercise time length (9-11 kW)12minutes
OtherFusível do painel de controle7,5A
OtherOrdem de partida (10 kW)15 s de arranque, 7 s de repouso, seguidos por quatro ciclos adicionais de 7 s de arranque e 7 s de repousocinco ciclos de manivela
OtherOrdem de partida (14 a 24 kW)16 s de arranque, 7 s de repouso, 16 s de arranque, 7 s de repouso, seguidos por três ciclos adicionais de 7 s de arranque e 7 s de repousocinco ciclos de manivela
OtherPerda de potência do motor por altitude3,5% a cada 304,8 m (1.000 pés) acima do nível do mar
OtherPerda de potência do motor por temperatura1% a cada 6 °C (10 °F) acima de 15 °C (60 °F)
OtherRedução de classificação GN vs PL10 a 20%
OtherRetardo de calentamiento con Arranque inteligente en frío30segundostemperatura ambiente por debajo de la temperatura fijada
OtherRetardo de calentamiento normal6segundostemperatura ambiente en o sobre la temperatura fijada
OtherTamanho mínimo de tanque de PL ao converter de GN946L (250 gal)
OtherUtility failure detection threshold65% of nominal (for five consecutive seconds)
OtherUtility restoration threshold80% of nominal (for 15 consecutive seconds)
PressureFuel pressure at regulator - LP10-12in water column (19-22 mm Hg)
PressureFuel pressure at regulator - Natural Gas3.5-7.0in water column (9-13 mm Hg)
PressureFuel pressure at regulator, LP gas10-12 in water column (2.49-2.99 kPa)in water column (kPa)
PressureFuel pressure at regulator, NG3.5-7.0 in water column (0.87-1.74 kPa)in water column (kPa)
PressureFuel pressure to generator fuel inlet – LP10–12in water column (2.49–2.99 kPa)all load ranges
PressureFuel pressure to generator fuel inlet – NG3.5–7.0in water column (0.87–1.74 kPa)all load ranges
PressureFuel pressure to regulator (LP)10-12in water column (19-22 mm Hg)LP gas
PressureFuel pressure to regulator (NG)3.5-7.0in water column (9-13 mm Hg)natural gas
PressureFuel pressure to regulator, LP10–12in water column (2.49–2.99 kPa)
PressureFuel pressure to regulator, LP gas10–12in water column (2.49–2.99 kPa)
PressureFuel pressure to regulator, NG3.5–7.0in water column (0.87–1.74 kPa)
PressureLP gas required fuel pressure at generator fuel inlet10–12 in water column (2.49–2.99 kPa)in water column
PressureLiquid propane fuel inlet pressure10-12in water column
PressureLiquid propane fuel inlet pressure2.49-2.99kPa
PressureNatural gas fuel inlet pressure0.87-1.74kPa
PressureNatural gas fuel inlet pressure3.5-7.0in water column
PressureNatural gas required fuel pressure at generator fuel inlet3.5–7.0 in water column (0.87–1.74 kPa)in water column

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilAPI SJ, SL ou mieuxChanger l'huile chaque année ou toutes les 100 heures par temps froid (< 4,4 °C) ou exploitation continue par temps chaud (> 29,4 °C)
Engine oil5W-20Aceite 5W-20 propiedad de Generac para uso continuo, después del período de asentamiento de 25 horas.
Engine oil5W-20 (Generac proprietary)API Service Class SJ, SL, or better1.03 LOil capacity including filter. Use for continuous use after the 25 hour break-in period; specifically formulated for gaseous powered Generac generators. Do not use special additives. Change every year or 100 hours in cold weather (below 40 F) or continuous hot weather (above 85 F).
Engine oil5W-30Aceite orgánico 5W-30 (la unidad se entrega de fábrica llena con este aceite)Compruebe el nivel de aceite y, de ser necesario, añada la cantidad apropiada con la viscosidad correcta. No llene en exceso. Consulte 'Recomendaciones para el aceite de motor' para tipo/viscosidad.
Engine oil5W-30 (factory fill) / 5W-20 GEO (continuous)Generac proprietary gaseous engine oil (GEO)Unit comes filled with 5W-30 organic oil; after 25 hour break-in use 5W-20 GEO
Engine oilGenerac 5W-20 exclusiveAPI SJ, SL ou mieuxAprès la période de rodage de 25 heures et à chaque intervalle; spécialement formulée pour les génératrices Generac alimentées au gaz
Engine oilSAE 5W-30 SyntheticAPI Service Class SJ, SL or betterDo not use special additives
Engine oilSAE 5W-30 sintéticoAPI SJ, SL o mejor1.03 l9 kW; no usar aditivos especiales
Engine oilSAE 5W-30 synthétiqueAPI classe de service SJ, SL ou supérieureHuile SAE 5W-30 synthétique pour toutes les plages de température. N'utilisez aucun additif spécial.
Engine oilSynthetic SAE 5W-30API Service Class SJ, SL, or betterSynthetic SAE 5W-30 for all temperature ranges. Do not use special additives. Capacities incl. filter: approx. 1.1 qt (1.03 L) 9 kW; approx. 1.7 qt (1.6 L) 11 kW; approx. 1.9 qt (1.8 L) 16/20/22 kW.
FuelGas natural: contenido de BTU de por lo menos 1000 BTU/ft3 (37,26 MJ/m3). Gas LP: por lo menos 2500 BTU/ft3 (93,15 MJ/m3)250.0 gal (946 l)Tamaño mínimo del tanque de LP es 250 gal (946 l), salvo que los cálculos de la unidad indiquen uno mayor. Solo sistema de extracción de vapor para LP.
FuelGas naturalmínimo 1000 BTU por pie cúbico (37.26 megajulios por metro cúbico)Reducciones típicas de gas natural 10-20 % respecto a LP
FuelGaz naturel37.26 mégajoules par mètre cube (1 000 BTU par pied cube) minimumTeneur en BTU minimale du gaz naturel.
FuelGaz naturel d'au moins 37,26 mégajoules par mètre cube (1 000 BTU par pied cube)NFPA 54
FuelGaz propane liquide (gazeux)93.15 mégajoules par mètre cube (2 500 BTU par pied cube) minimumCapacité de réservoir de gaz propane liquide minimum recommandée de 946 litres (250 gallons).
FuelGaz propane liquide d'au moins 93,15 mégajoules par mètre cube (2 500 BTU par pied cube)NFPA 58 / ICC IFGCRéservoir de gaz propane liquide d'une capacité minimale de 946 litres (250 gallons).
FuelLP (vapor)mínimo 2500 BTU por pie cúbico (93.15 megajulios por metro cúbico)946.0 lSe recomienda tanque de LP de 250 gal. (946 l) de tamaño mínimo si se convierte de NG a LP
FuelLP gas (vapor), minimum 2,500 BTUs per ft3 (93.15 megajoules per m3)Vapor withdrawn liquid propane.
FuelLiquid Propane (LP) vapor withdrawn or pipeline Natural GasNG min 1000 BTU/cu ft (37.26 MJ/m3); LP min 2500 BTU/cu ft (93.15 MJ/m3); min LP tank size 250 gal (946 L) recommended if converting from NG
FuelLiquid Propane (vapor)2500.0 BTU/ft3 (93.15 MJ/m3) minimumVapor withdrawn; minimum tank size 250 gal (946 L) when converting from NG
FuelLiquid propane (LP) vaporBTU content at least 2,500 BTUs per ft3 (93.15 megajoules per m3)If converting to LP gas from NG, a minimum LP tank size of 250 gal (946 L) is recommended.
FuelNatural Gas1000.0 BTU/ft3 (37.26 MJ/m3) minimumPipeline natural gas
FuelNatural gas (NG)BTU content at least 1,000 BTUs per ft3 (37.26 megajoules per m3)Unit factory-configured to run on NG.
FuelNatural gas (NG) or liquid propane (LP) vaporMinimum 1,000 BTUs per ft3 (37.26 MJ per m3) for NG; minimum 2,500 BTUs per ft3 (93.15 MJ per m3) for LPDual fuel carburetion; factory configured for NG. If converting to LP, minimum LP tank size of 250 gal (946 L) recommended
FuelNatural gas (vapor) or liquid propane vaporNG at least 1,000 BTU/ft3 (37.26 MJ/m3); LP at least 2,500 BTU/ft3 (93.15 MJ/m3)Factory configured for NG; minimum 250 gal (946 L) LP tank recommended if converting to LP
FuelNatural gas or LP gasRequired fuel pressure to generator fuel inlet: 3.5–7.0 in water column for NG; 10–12 in water column for LP
FuelNatural gas, minimum 1,000 BTUs per ft3 (37.26 megajoules per m3)Dual fuel carburetion; factory-configured for NG. Minimum LP tank size 250 gal (946 L) if converting to LP.
FuelNatural gas: at least 1,000 BTU/ft3 (37.26 MJ/m3); LP gas: at least 2,500 BTU/ft3 (93.15 MJ/m3)LP gas should only use a vapor withdrawal system
FuelPropano líquido (vapor)Contenido de BTU de al menos 93.15 MJ/m3 (2,500 BTU/pie3); presión de suministro 2.49 a 2.99 kPa (10 a 12 pulg. de columna de agua) en la entrada de combustible946.0 L (tamaño mínimo de tanque recomendado, 250 gal)Solo sistema de recuperación de vapor. No conectar a un tanque de propano líquido de 20 o 30 lb (9 o 14 kg).
OtherFluido detector de fugas de gas no corrosivoPara comprobación de fugas en todos los puntos de conexión durante las pruebas y el mantenimiento normal.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

46
CodeNameMeaningSeverityAction
AUXILIARY SHUTDOWNAuxiliary ShutdownUnit will not startShutdownSet auxiliary shutdown switch(es) to CLOSED (I); clear alarm
BATERÍA BAJABATERÍA BAJAIndicador LED amarillo encendido en cualquier estado.WarningBorre la alarma. Navegue hasta BATTERY MENU del MAIN MENU para revisar la batería. Si indica GOOD, comuníquese con un IASD. Si indica CHECK BATTERY, reemplace la batería.
Battery ProblemBattery FaultBattery condition poor or battery charger issueWarningInspect battery condition and connections. Contact IASD if needed.
BATTERY PROBLEMProblema de bateríaEl LED amarillo se ilumina en cualquier estadoWarningContactar un IASD
CARGADOR SIN CACARGADOR SIN CAIndicador LED amarillo encendido en cualquier estado.WarningComuníquese con un IASD.
CHARGER MISSING ACCharger Missing ACYellow LED illuminated in any stateWarningContact an IASD
CHARGER WARNINGAdvertencia del cargadorEl LED amarillo se ilumina en cualquier estadoWarningContactar un IASD
Controller FaultControl Module FailureInternal controller fault detectedShutdownContact IASD for assistance
CONTROLLER FAULTController FaultAlarm message listed on controller menu.ShutdownContact an IASD.
DESCONEXIÓN AUXILIARDESCONEXIÓN AUXILIARLa unidad no arranca.ShutdownColoque los interruptores de desconexión auxiliar en posición CERRADA (I).
EMERGENCY STOPEmergency StopAlarm message listed on controller menu.ShutdownCheck emergency shutdown switch and reset.
FUSE PROBLEMFuse ProblemUnit will not start in AUTO with utility loss. (Firmware 1.11 and older only.)ShutdownCheck the 7.5 amp fuse. If blown, replace with an ATO 7.5 amp fuse. If intact, contact an IASD.
High TemperatureOverheatEngine operating temperature too highShutdownInspect ventilation around generator, intake, exhaust, and rear. Ensure no obstructions present.
HIGH TEMPERATUREHigh TemperatureUnit shuts down during operation.ShutdownCheck ventilation around the generator, intake, exhaust, and rear of generator. If no obstructions are present, contact an IASD.
INSPECCIONE LA BATERÍAINSPECCIONE LA BATERÍAIndicador LED amarillo encendido en cualquier estado.WarningInspeccione la batería. Presione ENTER para borrar.
INSPECT BATTERYInspeccionar bateríaEl LED amarillo se ilumina en cualquier estadoWarningInspeccionar la batería; pulsar ENTER para desactivar
Low BatteryBattery Voltage LowStarting battery voltage below acceptable levelWarningInspect battery and battery cables. Charge or replace battery if necessary.
LOW BATTERYBatería bajaEl LED amarillo se ilumina en cualquier estadoWarningDesactivar la alarma; comprobar batería en BATTERY MENU; si GOOD contactar un IASD, si CHECK BATTERY sustituir la batería
Low Oil PressureLow Oil Level or PressureInsufficient oil pressure in engineShutdownCheck engine oil level and top up if necessary. Contact IASD if problem persists.
LOW OIL PRESSURELow Oil PressureUnit will not start in AUTO with utility loss.ShutdownCheck oil level and add oil as needed. If oil level is correct, contact an IASD.
LOW VOLTS REMOVE LOADLow VoltsUnit will not start in AUTO with utility loss.ShutdownClear alarm and remove household loads from the generator. Put in AUTO and restart.
MISWIREMiswire / Wiring ErrorUnit will not start in AUTO with utility loss.ShutdownContact an IASD.
NOT ACTIVATEDNot ActivatedUnit will not start in AUTO with utility loss.Refer to 'Activation' in installation manual.
OvercrankExtended CrankingEngine failing to start after extended crank attemptsShutdownCheck fuel supply, spark plugs, and fuel system. Contact IASD for further diagnosis.
OVERCRANKOvercrankUnit will not start in AUTO with utility loss.ShutdownCheck fuel line shutoff valve is ON. Clear alarm. Start the unit in MANUAL. If it does not start or runs rough, contact an IASD.
OverloadOverload DetectedElectrical load exceeds generator capacityShutdownRemove household electrical loads from generator
OVERLOAD REMOVE LOADOverloadUnit shuts down during operation.ShutdownClear alarm and remove household loads from the generator. Put in AUTO and restart.
OVERLOAD WARNINGAviso de sobrecargaAviso de sobrecarga.WarningRemova as cargas domésticas do gerador.
OverspeedRPM OverspeedEngine running at excessive RPMShutdownContact IASD for assistance
OVERSPEEDOverspeedUnit will not start in AUTO with utility loss.ShutdownContact an IASD.
OvervoltageOutput Voltage HighGenerator voltage exceeding nominal ratingShutdownReduce electrical load and restart. Contact IASD if issue persists.
OVERVOLTAGEOvervoltageUnit will not start in AUTO with utility loss.ShutdownContact an IASD.
PROBLEMA DE BATERÍAPROBLEMA DE BATERÍAIndicador LED amarillo encendido en cualquier estado.WarningComuníquese con un IASD.
RPM SENSE LOSSPérdida de detección de rpmLa unidad se para e intenta volver a ponerse en marchaShutdownDesactivar la alarma, retirar cargas, poner en AUTO y reanudar; si no arranca contactar un IASD
RPM Sensor LossRPM Signal LossRPM sensor signal not detectedShutdownContact IASD for assistance
SERVICE AService AYellow LED illuminated in any state.WarningPerform SERVICE A maintenance. Press ENTER to clear.
SERVICE BService BYellow LED illuminated in any state.WarningPerform SERVICE B maintenance. Press ENTER to clear.
SHUTDOWN SWITCHShutdown SwitchUnit will not start. Flashing red LED.ShutdownCheck emergency shutdown switches. Set switch(es) to CLOSED (I). Clear alarm.
STEPPER OVERCURRENTStepper OvercurrentUnit will not start in AUTO with utility loss.ShutdownContact an IASD.
UnderspeedEngine Speed Too LowEngine RPM below nominal specificationShutdownContact IASD for assistance
UNDERSPEEDUnderspeedUnit will not start in AUTO with utility loss.ShutdownContact an IASD.
UndervoltageOutput Voltage LowGenerator voltage below nominal ratingShutdownReduce electrical load and restart. Contact IASD if issue persists.
UNDERVOLTAGEUndervoltageUnit will not start in AUTO with utility loss.ShutdownContact an IASD.
USB WARNINGAviso de USBAviso relacionado ao dispositivo USB.WarningTente novamente com USB de melhor qualidade. Os nomes dos ficheiros no USB não podem ter mais de 8 caracteres.
Wiring ErrorElectrical Wiring FaultWiring configuration error detectedShutdownContact IASD for assistance
WIRING ERRORWiring ErrorUnit will not start in AUTO with utility lossShutdownContact an IASD

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjust Valve Clearance adjustment

⚠ Allow engine to cool before adjusting valve clearance.

Tools: feeler gauge, 10 mm wrench, 13 mm wrench, 14 mm wrench, 8 mm wrench, 10 mm Allen wrench, torque wrench

  1. Make sure piston is at TDC of compression stroke (both valves closed).
  2. Remove spark plug wire(s) and position away from plugs.
  3. Remove spark plug(s).
  4. Remove the four screws attaching valve cover; remove and discard gasket.
  5. Loosen rocker jam nut (10 mm wrench 9-11 kW; 13 mm wrench 16-22 kW).
  6. Turn pivot ball stud (14 mm wrench 9 kW; 8 mm wrench 11 kW; 10 mm Allen 16-22 kW) while checking clearance with feeler gauge.
  7. Hold rocker arm jam nut in place as pivot ball stud is turned.
  8. When clearance correct, hold pivot ball stud and tighten rocker arm jam nut to torque spec.
  9. Recheck valve clearance after tightening jam nut.
  10. Install new valve cover gasket.
  11. Install valve cover; tighten fasteners in cross pattern to torque spec.
  12. Install spark plugs and torque to 18 ft-lbs (25 Nm).
  13. Reattach spark plug wire to spark plug.
  14. Repeat process for other cylinder if necessary.
Adjusting Valve Clearance adjustment

⚠ Risk of Burn. Allow the engine to cool before performing the following procedure.

Tools: Feeler gauge, 10 mm wrench, 13 mm wrench, 14 mm wrench, 10 mm hex key

  1. Allow engine to cool before adjusting valve clearance.
  2. Remove spark plug wire(s) away from plugs and remove spark plug(s).
  3. Remove the four screws attaching the valve cover; remove and discard gasket.
  4. Verify piston is at TDC of its compression stroke (both valves closed).
  5. Loosen rocker jam nut using a 10 mm wrench (10 kW) or 13 mm wrench (20–22 kW).
  6. Turn pivot ball stud with a 14 mm wrench (10 kW) or 10 mm hex key (20–22 kW) while checking clearance with a feeler gauge.
  7. Hold pivot ball stud and tighten rocker arm jam nut to specification.
  8. After tightening jam nut, verify valve clearance did not change.
  9. Install new valve cover gasket and valve cover; tighten fasteners in a cross pattern.
  10. Install spark plugs and tighten to 18 ft-lbs (25 Nm).
  11. Attach spark plug wire to spark plug.
  12. Repeat process for other cylinder if equipped.
Ajustar a folga das válvulas adjustment

⚠ Risco de queimaduras. Deixe o motor esfriar antes de executar o procedimento.

Tools: Chave de 10 mm, Chave de 13 mm, Chave de 14 mm, Chave sextavada de 10 mm, Calibrador

  1. Remova os fios das velas de ignição e remova as velas de ignição.
  2. Remova os quatro parafusos que prendem a tampa da válvula; descarte a junta.
  3. Verifique se o pistão está no TDC do seu curso de compressão.
  4. Solte a contraporca do balanceiro (C) com chave de 10 mm ou 13 mm.
  5. Gire o pino de esfera articulada (D) com chave de 14 mm ou sextavada de 10 mm e ajuste a folga.
  6. Aperte a contraporca do braço oscilante e inspecione a folga novamente.
  7. Instale a nova junta e as tampas das válvulas; aperte em padrão transversal.
  8. Instale as velas e aperte a 25 Nm; conecte os fios das velas.
Ajuste de la luz de válvulas adjustment

⚠ Dejar enfriar el motor antes de ajustar.

⚠ Iniciar los cuatro tornillos antes de apretar.

Tools: Calibre de espesores, Llaves de 8/10/13/14 mm, Llave de casquillo, Casquillo grande

  1. Cerrar la válvula de combustible y desconectar la batería.
  2. Retirar cable(s) de bujía y alejarlos.
  3. Retirar la(s) bujía(s).
  4. Llevar el pistón al PMS de la carrera de compresión.
  5. Retirar los cuatro tornillos de la cubierta de válvulas y desechar la junta.
  6. Aflojar la contratuerca del balancín.
  7. Girar el prisionero de bola pivote para ajustar la luz con calibre.
  8. Sostener el prisionero y apretar la contratuerca; verificar y reinstalar con junta nueva.
Ajuste de la separación de la válvula adjustment

⚠ Deje que el motor se enfríe antes del procedimiento.

⚠ Desconecte el cable negativo y luego el positivo de la batería.

⚠ No necesario en unidades 14 o 18 kW con motor de 816 cc.

Tools: Llave de 10 mm, Llave de 13 mm, Llave de 14 mm, Llave hexagonal de 10 mm, Galga de espesores

  1. Retire los hilos de las bujías y las bujías.
  2. Retire los cuatro tornillos de la cubierta de la válvula y deseche la junta.
  3. Verifique que el pistón esté en el PMS de su carrera de compresión.
  4. Suelte la contratuerca del balancín (llave 10 mm en 10 kW, 13 mm en 20 a 24 kW).
  5. Gire el espárrago del pivote (llave 14 mm en 10 kW, hexagonal 10 mm en 20 a 24 kW) ajustando la separación.
  6. Sostenga el espárrago y apriete la contratuerca del balancín.
  7. Inspeccione la separación para verificar que no cambió.
  8. Instale una junta nueva y la cubierta de la válvula; apriete en patrón cruzado.
  9. Instale las bujías y apriete a 25 Nm (18 lb-pie).
  10. Conecte los hilos de las bujías.
Ajuster le jeu des soupapes adjustment

⚠ Risque de brûlure : laisser le moteur refroidir avant d’exécuter la procédure.

⚠ Réglage non requis sur les modèles de 14 ou 18 kW à moteur de 816 cc.

Tools: Clé de 10 mm ou 13 mm, Clé de 14 mm ou clé hexagonale de 10 mm, Jauge d’épaisseur

  1. Laisser le moteur refroidir.
  2. Débrancher les câbles de bougie et les placer à l’écart.
  3. Retirer les bougies.
  4. Retirer les quatre vis du cache-culbuteurs et mettre le joint au rebut.
  5. S’assurer que le piston est au point mort haut (PMH) de sa course de compression.
  6. Desserrer le contre-écrou de culbuteur.
  7. Faire tourner le goujon pivot tout en contrôlant le jeu avec une jauge d’épaisseur.
  8. Ajuster le jeu conformément à la section Moteur.
  9. Tenir le goujon pivot et serrer le contre-écrou au couple spécifié.
  10. Poser un joint de cache-culbuteurs neuf et remonter le cache-culbuteurs.
  11. Mettre les bougies en place au couple de 25 Nm (18 pi-lb).
Checking Valve Clearance adjustment

⚠ Risk of Burn. Allow the engine to cool before performing the following procedure.

⚠ Accidental start-up. Disconnect spark plug wires when working on unit.

Tools: Feeler gauge, Large socket and socket wrench

  1. Close fuel valve and disconnect battery to avoid accidental startup.
  2. Remove spark plug wire(s) and position away from plug(s).
  3. Remove spark plug(s).
  4. Remove the four screws attaching the valve cover; remove and discard gasket.
  5. Verify piston is at top dead center (TDC) of its compression stroke (both valves closed).
  6. Inspect valve clearance between each rocker arm and valve stem with a feeler gauge.
  7. Install replacement valve cover gasket(s).
  8. Install valve cover(s); tighten fasteners in a cross pattern.
Conversion de carburant adjustment

⚠ Explosion et incendie. Le carburant et ses vapeurs sont extrêmement inflammables et explosifs.

  1. Localiser le bouton orange de conversion (A).
  2. Tourner le bouton vers la flèche indiquant la source de carburant jusqu'à l'arrêt.
  3. Le bouton tourne sur 180° et glisse dans le corps du mélangeur pour le propane liquide.
  4. Saisir la sélection du carburant (PL ou GN) sur l'automate de contrôle (Assistant d'installation ou menu EDIT > Fuel Selection).
Conversión de combustible adjustment

⚠ Explosiones e incendio: no se permiten fugas de combustible.

  1. Ubique la perilla naranja de conversión de combustible (debajo del mezclador en 9 kW, sobre el mezclador en 11 kW–22 kW).
  2. Gire la válvula hacia la marca de flecha de la fuente de combustible hasta que se detenga.
  3. Introduzca la selección de combustible (LP/gas natural) en el controlador mediante el Asistente de instalación o el menú EDIT, 'Fuel Selection'.
Conversión de combustible (GN a PL) adjustment

⚠ La perilla del selector de combustible debe ajustarse al combustible correcto para que el generador funcione correctamente.

  1. Ubique la perilla de conversión de combustible naranja (bajo el mezclador en 10 kW; sobre el mezclador en 14 a 24 kW).
  2. Gire la perilla de conversión hacia la flecha del tipo de combustible marcado hasta que se detenga.
  3. La perilla gira 180° y se desliza hacia dentro del mezclador al convertir a propano líquido.
  4. Ingrese la selección de combustible (PL/GN) en el controlador mediante el Asistente de instalación o el menú EDITAR.
Fuel Conversion (NG to LP) adjustment

⚠ Fuel and vapors are extremely flammable and explosive; no leakage permitted.

  1. Turn fuel conversion knob toward marked fuel source arrow until it stops (rotates 180° and slides into mixer body).
  2. Enter fuel selection (LP/NG) on controller using Install Wizard or EDIT menu under Fuel Selection.
Réglage du jeu des soupapes adjustment

⚠ Laisser le moteur refroidir avant d'ajuster le jeu des soupapes.

Tools: Clé à douille, Clés de 8/10/13/14 mm, Jauge d'épaisseur

  1. Amener le piston au PMS de sa course de compression (les deux soupapes fermées).
  2. Retirer les fils des bougies d'allumage et les écarter.
  3. Retirer les bougies.
  4. Retirer les quatre vis du couvercle des soupapes et jeter le joint.
  5. Desserrer le contre-écrou du culbuteur (clé de 10 mm pour 9-11 kW ou 13 mm pour 16-22 kW).
  6. Tourner le pivot à rotule tout en vérifiant le jeu avec une jauge d'épaisseur.
  7. Maintenir le pivot et serrer le contre-écrou selon les spécifications.
  8. Vérifier de nouveau le jeu.
  9. Installer un nouveau joint sur le couvercle des soupapes.
  10. Installer le couvercle et serrer les attaches en tracé croisé au couple spécifié.
  11. Installer les bougies d'allumage et serrer à 25 N.m (18 pi-lb).
  12. Rebrancher le câble de bougie.
  13. Répéter au besoin pour l'autre cylindre.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
0 – c.c. (-)NOIR no 3Fil de mise à la terre normal; obligatoire si jumelé à un commutateur de transfert de gestion intelligente de l'alimentation de Generac.
23BLANCO Núm. 5Cable de señal lógica del control de transferencia
Generator control wiring - 1-115 ft (1-35 m)N1, N2, T1, 23, 194No. 18 AWG
Generator control wiring - 116-185 ft (36-56 m)N1, N2, T1, 23, 194No. 16 AWG
Generator control wiring - 186-295 ft (57-89 m)N1, N2, T1, 23, 194No. 14 AWG
Generator control wiring - 296-460 ft (90-140 m)N1, N2, T1, 23, 194No. 12 AWG
Longueur de fil 1 à 35 m (1 à 115 pi)Calibre 18 AWGConducteurs en cuivre seulement.
Longueur de fil 35 à 56 m (115 à 185 pi)Calibre 16 AWGConducteurs en cuivre seulement.
Longueur de fil 56 à 89 m (185 à 295 pi)Calibre 14 AWGConducteurs en cuivre seulement.
Longueur de fil 89 à 140 m (295 à 460 pi)Calibre 12 AWGConducteurs en cuivre seulement.
Neutral for battery chargerWHITE NEU/00Must be connected to keep battery charged whether unit is running or not
0 VCC0NEGRO Núm. 3CC (-) Cable común de conexión a tierra. Requerido si el generador está apareado con un interruptor de transferencia de gestión de alimentación inteligente Generac.
12 V c.c.194 – c.c. (+)ROUGE no 4Pour les commandes de transfert.
12 VCC194ROJO núm. 4CC (+) para los controles de transferencia
12 VDCDC (+) 12 VDC for transfer controlsRED 194
12 VDCDC (-) common ground wireBLACK 0
12 VDCTransfer control signal wireWHITE 23Required if generator is paired with optional Digital Power Management (DPM) smart technology
120 V c.a.T1BLEU no 3Avec fusible 120 V c.a. pour le chargeur de la batterie; doit être branché pour que la batterie demeure chargée.
120 VACFused 120 VAC for battery chargerBLUE T1Must be connected to keep battery charged whether unit is running or not
120 VCAT1AZUL Núm. 3Con fusible para el cargador de baterías (debe estar conectado para mantener la batería cargada, esté o no funcionando la unidad)
240 V c.a.N1 et N2JAUNE no 1 et no 2Détectent les chutes et les hausses du réseau public.
240 VACUtility dropout and pickup sensingYELLOW N1 & N2
240 VAC1Customer load to T1 and T2 terminalsT1, T2Load leads are pre-wired at the factory
240 VAC1Generator (standby) source to E1 and E2 terminalsE1, E2
240 VAC1Utility (normal) source to N1 and N2 terminalsN1, N2Single-phase neutral connected to neutral lug, not switched
240 VCAN1 y N2AMARILLO Núm. 1 y Núm. 2Detección de desenganche y activación del servicio público

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Generac G-Force 400 family

27
Part #DescriptionCategory
0E9371AAir FilterAir filter
0E9371ASAir filterAir filter
0J8478Air FilterAir filter
0J8478SAir filterAir filter
G005819-026R Wet Cell BatteryBattery
0C2979GASKET, VALVE COVERGasket
0K8946Joint de cache-culbuteursGasket
10000014927Joint de cache-culbuteursGasket
070185EOil FilterOil filter
070185ESFiltre à huile recommandéOil filter
0D7178TControl panel fuseService part / kit
0H3421S26R Exide batteryService part / kit
G005621-0Auxiliary Transfer Switch Contact KitService part / kit
G005703-0Paint KitService part / kit
G006482-0Scheduled Maintenance KitService part / kit
G007000-0Smart Management Module (50 amp)Service part / kit
G007005-0Wi-Fi LP Fuel Level MonitorService part / kit
G007006-0Smart Management Module (100 amp)Service part / kit
G007027-0Fascia Base Wrap KitService part / kit
G007101-0Battery Pad WarmerService part / kit
G007102-0Oil WarmerService part / kit
G007103-1Breather WarmerService part / kit
G007169-0Mobile Link® Cellular Accessories - 4G LTEService part / kit
G007170-0Mobile Link® Cellular Accessories - Wi-Fi/EthernetService part / kit
G007216-0Scheduled Maintenance KitService part / kit
0G0767ASpark Plug (RC12YC or equivalent)Spark plug
0G0767BSpark PlugSpark plug

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Generac G-Force 400 Series?

The Generac G-Force 400 Series engine has an oil capacity of 1.03 liters.

What is the displacement of the Generac G-Force 400 Series?

The Generac G-Force 400 Series has a displacement of 0.46 liters with 1 cylinders.

Which generators use the Generac G-Force 400 Series engine?

The Generac G-Force 400 Series powers 5 generator set(s), including Generac G007029-1, Generac G007030-1, Generac G007171-0, Generac G007172-0, Generac G0072100.

How often should you change the oil in the Generac G-Force 400 Series?

The Generac G-Force 400 Series oil change interval is every 100 hours.

What is a common problem with the Generac G-Force 400 Series engine?

A commonly reported issue on generators using the Generac G-Force 400 Series is: Unit will not start in AUTO with utility loss — LED RED. Cause: Check LEDs / screen for alarms.. Fix: Check oil level and add oil as needed. If oil level is correct, contact an IASD..