Home›Repair guides›Generac›ATS Manual Operation Test

Generac G-Force 400 Series / RTG16EZA3 — ATS Manual Operation Test

Operation · Transfer switch mechanism

For the Generac G-Force 400 Series / RTG16EZA3, from the Generac owner's manual.

Applies to: Generac G-Force 400 Series engine, Generac G-Force 800 Series engine, Generac G-Force 1000 Series engine

Before you start

  • Do not use excessive force while manually operating the transfer switch.

Procedure

  1. Ensure generator is in OFF mode.
  2. Turn OFF utility service disconnect and generator main line circuit breaker.
  3. Note position of main contacts via movable contact carrier arm.
  4. Handle UP: LOAD terminals T1/T2 connected to UTILITY N1/N2.
  5. Handle DOWN: LOAD terminals T1/T2 connected to EMERGENCY E1/E2.
  6. Insert handle and move to desired position, holding it through center of travel.
  7. Remove handle and return it to storage bracket.

Tools required

  • Manual operating handle Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.