Generac G-Force 400 Series / RTG16EZA3 — Remove From Service (Storage Over 90 Days)
Maintenance · Generator
For the Generac G-Force 400 Series / RTG16EZA3, from the Generac owner's manual.
Applies to: Generac G-Force 400 Series engine, Generac G-Force 800 Series engine, Generac G-Force 1000 Series engine
Before you start
- Explosion. Always disconnect negative battery cable first to avoid spark.
Procedure
- Start engine and allow it to warm up.
- Close fuel shutoff valve and allow engine to stop.
- Set generator MLCB to OFF (OPEN).
- Disconnect battery charger AC input T1/Neutral cable at controller.
- Remove 7.5A fuse from control panel.
- Disconnect battery cables, negative first.
- Drain oil while warm and refill crankcase with oil.
- Remove spark plugs, spray fogging agent into openings, reinstall plugs.