Generac G-Force 1000 Series — Shutting Generator Down While Under Load or During a Utility Outage

Operation

For the Generac G-Force 1000 Series, from the Generac owner's manual.

Applies to: Generac G-Force 400 Series engine, Generac G-Force 800 Series engine, Generac G-Force 1000 Series engine

Before you start

  • To avoid equipment damage, follow these steps in order during utility outages.

Procedure

  1. Set main utility disconnect to OFF (OPEN).
  2. Set generator MLCB (generator disconnect) to OFF (OPEN).
  3. Allow generator to run for cool-down approximately one minute.
  4. Set generator to OFF at the controller.
  5. Remove 7.5A fuse from controller.

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.