Generac G-Force 1000 Series — Inspecting the Battery
Maintenance
For the Generac G-Force 1000 Series, from the Generac owner's manual.
Applies to: Generac G-Force 400 Series engine, Generac G-Force 800 Series engine, Generac G-Force 1000 Series engine
Before you start
- Electrical shock. Disconnect battery ground terminal before working on battery or battery wires.
- Batteries contain sulfuric acid and can cause severe chemical burns. Wear protective gear.
Procedure
- Press OFF to shut down generator, then lift lid and remove front panel.
- Remove 7.5A fuse from control panel.
- Remove intake side panel.
- Inspect battery posts and cables for tightness and corrosion; tighten and clean as necessary.
- Unsealed batteries only: disconnect battery, check fluid level, fill with distilled water only if necessary.
- Connect battery cables, install intake side panel, and install 7.5 A fuse.
- Press AUTO button on controller.
- Install front panel and close generator lid.
Tools required
- Insulated tools Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- 12 volts, Group 26R Wet Cell 540CCA minimum or Group 35 AGM 650CCA minimum
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.