Generac G-Force 1000 Series — Return to Service
Maintenance · Generator
For the Generac G-Force 1000 Series, from the Generac owner's manual.
Applies to: Generac G-Force 400 Series engine, Generac G-Force 800 Series engine, Generac G-Force 1000 Series engine
Before you start
- Explosion. Always connect positive battery cable first to avoid spark.
- Do not make battery connections in reverse.
Procedure
- Check tag on engine for oil viscosity and classification; drain and fill with correct oil if necessary.
- Verify state of battery; fill unsealed cells with distilled water and charge battery to 100% state of charge.
- Clean and wipe down generator enclosure.
- Verify 7.5A fuse is removed from generator control panel.
- Connect battery, observing polarity; install positive cable first.
- Connect battery charger AC input T1/Neutral cable (with white sleeve) at controller.
- Open fuel shutoff valve.
- Insert 7.5 A fuse into generator control panel.
- Complete Install Wizard procedure.
- Press MANUAL to start unit; allow unit to warm up for a few minutes.
- Press OFF button to stop unit.
- Set MLCB (generator disconnect) to ON (CLOSED).
- Press AUTO button on control panel.
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.