Generac G-Force 1000 Series — Manual Transfer to Generator Power Source
Operation · Transfer switch
For the Generac G-Force 1000 Series, from the Generac owner's manual.
Applies to: Generac G-Force 400 Series engine, Generac G-Force 800 Series engine, Generac G-Force 1000 Series engine
Before you start
- Electrocution. Do not manually transfer under load. Disconnect transfer switch from all power sources prior to manual transfer.
Procedure
- Verify generator is OFF.
- Set MLCB (generator disconnect) to OFF (OPEN).
- Turn off utility power supply to transfer switch using means provided.
- Use manual transfer handle inside transfer switch to move main contacts to STANDBY.
- Press MANUAL button on control panel to crank and start engine.
- Allow engine to stabilize and warm up for a few minutes.
- Set MLCB (generator disconnect) to ON (CLOSED).
Tools required
- Manual transfer handle Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.