Kohler 2000ROZD Generator Set

The Kohler 2000ROZD is a 2000 kW (2500 kVA) diesel standby generator set powered by a MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16) engine. It is available at 220/380 V, 240/416 V, 277/480 V, 347/600 V, 2400/4160 V and 1905/3300 V, 3-phase, 60 Hz and rated 3798 A. It holds about 465 L (122.8 gal) of oil and 565 L (149.3 gal) of coolant, with a maximum ambient rating of 40 °C. Starting uses 2 group-24 batteries rated 950 CCA at 24 V.

2000 kW
Standby
65.0 L
Displacement
465.0 L
Oil capacity
4
Document types

How to read your Kohler serial & model number →

Typical fuel consumption for 2000–2005 kW Diesel generators →

Compare with other 2000–2005 kW Diesel generators →

Service parts for the 2000ROZD

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required
347667Air filtersee priceAmazon

Fuel system

1 required
274821Fuel filter (secondary)$100.00eBay

Oil system

1 required

Belts

1 required
347423Beltsee priceAmazon

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

Fueldiesel
Frequency60.0 Hz
Standby power2000 kW
Standby kVA2500
Prime power1820 kW
ControllerElectronic engine controls
Oil capacity465.0 L
Alternator4-Pole, Rotating-Field (4-pole, Class Class H insulation)
Voltage options220/380 V, 240/416 V, 277/480 V, 347/600 V, 2400/4160 V, 1905/3300 V
Phase3
Rated current3798 A
Power factor0.8
Circuit breaker3798 A
Battery group24
Battery cranking950 CCA
Battery voltage24 V
Battery quantity2
Coolant capacity565.0 L
Engine jacket water151.0 L
Max ambient40 °C

Engine

MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16)
Oil capacity465.0 L
Coolant capacity151.0 L
Displacement65.0 L
AspirationTurbocharged, Intercooled
Rated speed1800 rpm

Filters for the MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16)

1

Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.

Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:

SystemFilterDescriptionCross-references
Fuel / water separatorP552006Fuel Filter, Water Separator Spin-On Twist&DrainMTU 4202934, NAPA 3645, BALDWIN BF1262, SISU 1273400331 FridayParts $42.88

Maintenance & consumables

for the MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16)
ItemSpecCapacityPart #Interval
Air filterAir Cleaner Assembly347667 Amazon eBay
Fuel filterSecondary274821 eBay $100.00
Oil filter279260 Amazon eBay $20.47 NAPA $37.15
BeltBelt, Poly V347423 Amazon eBay

Service intervals

7
ItemActionHoursMonthsNotes
Change oilChange50 hr50 Hours or Yearly
Replace filter(s)Replace50 hr50 Hours or Yearly; service more frequently if operated in dusty areas
Lubricate fan bearings (1200--2000 kW)Lubricate200 hr6 mo200 Hours or Six Months
Blow dust out of alternatorClean300 hr2 Years or 300 Hours; service more frequently if operated in dusty areas
Bolt torqueAdjust500 hr3 Years or 500 Hours
Valve clearanceAdjust500 hr3 Years or 500 Hours
Wire-cable insulation breakdownTest500 hr3 Years or 500 Hours

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

19
TypeItemValueUnitCondition
OtherBattery specific gravity, charge required below1.215at electrolyte temperature 26.7°C (80°F)
OtherBattery specific gravity, fully charged1.260at electrolyte temperature 26.7°C (80°F)
OtherFan bearing grease column at bearing pressure relief port3--6mm (0.13--0.25 in.)
OtherLoad-sharing module droop3% droopat 100% load
OtherPoly V-belt tension, 1200-2000 kW, new belt2450--2890N (550--650 lbf)new belt
OtherPoly V-belt tension, 1200-2000 kW, used belt1650--1910N (370--430 lbf)used belt (after 50 hours of service)
OtherReactive droop, 20--300 kW reactive droop compensation adjustment6%--8% droop in voltageat rated current, 1.0 power factor resistive load
OtherSpecific gravity variation between cells±0.01
PressureAutomatic fuel changeover switchpoint (primary fuel pressure)0.6 kPa (1.4 oz./in.2) or 6.4 cm (2.5 in.) water columnkPa
PressureLP liquid withdrawal fuel system leak test pressureat least 90 psi (621 kPa)psileak test with soap and water solution
PressureLP vapor or natural gas fuel system leak test pressure6--8 ounces per square inch (10--14 inches water column)oz./in.2leak test with soap and water solution
SpeedOverspeed shutdown (50 and 60 Hz models)70 Hz (2100 rpm)governed frequency exceeds
SpeedRated engine speed1800 rpm at 60 Hz or 1500 rpm at 50 Hzrpm
TemperatureCoolant freezing protection, 50% ethylene glycol solution--37°C (--34°F)
TemperatureCoolant overheating protection, 50% ethylene glycol solution129°C (265°F)
VoltageOvervoltage calibration output voltage115% of the nominal output voltage
VoltageOvervoltage shutdownat least 15% over the nominal voltage for longer than 2 seconds
VoltageOvervoltage shutdown calibration, 139/240 V (low wye) or 277/480 V (high wye), 3-phase, 4-wire, 60 Hzapproximately 160Vacross terminals V0 and V7 at 115% of nominal output voltage
VoltageOvervoltage shutdown calibration, all other voltagesapproximately 140Vacross terminals V0 and V7 at 115% of nominal output voltage

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50% ethylene glycol and 50% clean, softened waterabove -37°CProvides freezing protection to --37°C (--34°F) and overheating protection to 129°C (265°F). Do not use alcohol or methanol antifreeze. See generator set spec sheet for coolant capacity.
Engine oil10W40 or 10W50API classification SH/CD, SG/CD, SH/CC, or SG/CCabove -23°CFor air temperatures consistently above --23°C (--10°F); Ford-powered 30, 80, and 100 kW models
Engine oil20W50 or 10W40API classification SH/CD, SG/CD, SH/CC, or SG/CCabove 0°CFor air temperatures consistently above 0°C (32°F); Ford-powered 30, 80, and 100 kW models
GreaseMobil Mobilith AW2 NLGI Grade 2 or equivalentLithium-complex base, multi-purpose grease with antirust, antifoam, and extreme-pressure additives, minimum dropping point 204°C (400°F)Radiator fan shaft and idler shaft bearings, 1200--2000 kW models
GreaseChevron SRI or equivalentAntifriction, high-quality grease with lubrication temperature range --30° to 175°C (--22° to 350°F)-30°C to 175°C350--2000 kW models with single-bearing alternator

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Gaseous Carburetor (Fuel Mixer) Adjustment Procedure adjustment

⚠ Verify that engine compression and the ignition system meet specifications before adjusting the carburetor.

⚠ Some engines have sealed carburetors that are not adjustable.

  1. Start the generator set and run it at approximately half load.
  2. Adjust the engine fuel mixture screw until the engine runs smoothly.
  3. Apply varying loads and readjust the carburetor as necessary to achieve smooth engine performance at all load levels.
  4. Stop the generator set.
LP Fuel Conversion Procedure adjustment

⚠ Not all fuel regulators require spring and retainer removal for fuel conversion. A hang tag on the fuel regulator identifies the conversion procedure.

  1. Remove the fuel regulator cover plug.
  2. Remove the adjustment screw and spring from the fuel regulator. Save them for conversion back to natural gas.
  3. Reinstall the cover plug.
Natural Gas Fuel Conversion Procedure adjustment

⚠ Lower-than-specified pressures may result in poor response to load changes or lack of power.

Tools: Manometer

  1. Remove the fuel regulator cover plug.
  2. Replace the spring and adjustment screw.
  3. Connect a manometer to check fuel supply pressure on the carburetor side of the regulator, downstream of accessories.
  4. With the generator set running at full load, rotate the adjustment screw until manometer pressure matches the specified pressure.
  5. Reinstall the cover plug.
Overvoltage Shutdown Adjustment (Decision-Maker 3 Controller) adjustment

⚠ Do not contact electrical connections with tools or jewelry while making adjustments or repairs.

  1. With the generator set idle, open the output line circuit breaker to disconnect the load.
  2. Remove the controller cover.
  3. Install the J1 jumper if the set is connected for 139/240 V (low wye) or 277/480 V (high wye) 3-phase, 4-wire, 60 Hz. Remove it for all other voltages.
  4. Replace the cover.
Overvoltage Shutdown Adjustment (Decision-Maker 3+ Controller) adjustment

⚠ Do not use the safeguard circuit breaker in place of the line circuit breaker.

⚠ Do not contact electrical connections with tools or jewelry while making adjustments or repairs.

Tools: Digital AC voltmeter, Insulated-handle screwdriver, RTV sealant

  1. Disconnect the engine starting battery, negative (--) lead first. Disconnect power to the battery charger.
  2. With the generator set idle, open the output line circuit breaker to disconnect the load.
  3. Remove the controller cover.
  4. Wrap the shaft of an insulated-handle screwdriver with electrical tape. Turn potentiometer R41 or R42 fully clockwise.
  5. Connect a digital AC voltmeter to terminals V0 and V7 on the controller terminal block.
  6. Reconnect the battery, negative (--) lead last.
  7. Start the generator set by placing the master switch in the RUN position.
  8. Adjust output voltage to 115% of nominal (approximately 160 V across V0 and V7 for low wye/high wye; approximately 140 V for all other voltages).
  9. Slowly rotate R41 or R42 counterclockwise until red LED4 lights. The set should shut down on overvoltage in approximately 2 seconds.
  10. Turn the voltage adjustment potentiometer counterclockwise to reduce output voltage, restart, and slowly increase voltage to verify the shutdown setting.
  11. Reduce output voltage, restart, and readjust the generator set output to nominal voltage.
  12. Stop the generator set. Seal potentiometer R41 with RTV sealant or equivalent. Replace the controller cover.
Reactive Droop Compensation Adjustment Procedure (20--300 kW) adjustment

⚠ Read the entire procedure before beginning.

  1. Set the generator set master switch to the OFF/RESET position.
  2. Set the reactive droop rheostat at minimum (full counterclockwise position).
  3. Move the voltage-sensing lead inside the controller from terminal V7 to terminal V9.
  4. Start the generator set and adjust the voltage to the rated system voltage using the voltage-adjusting potentiometer.
  5. Apply a resistive load (1.0 power factor) at rated current and adjust the reactive droop rheostat to achieve a 6%--8% droop in voltage.
  6. Remove the load from the generator set.
  7. Shut down the generator set by placing the master switch in the OFF/RESET position.
  8. Move the voltage-sensing lead inside the controller from terminal V9 to terminal V7. Repeat for additional generator sets.
Voltage Reconnection Procedure adjustment

⚠ Verify that the voltage ratings of the transfer switch, line circuit breakers, and other accessories match the selected line voltage.

⚠ Affix a notice to the generator set after reconnecting to a voltage different from the nameplate voltage.

Tools: Voltmeter, Screwdriver

  1. Place the generator set master switch in the OFF/RESET position.
  2. Disconnect the engine starting battery, negative (--) lead first. Disconnect power to the battery charger.
  3. Use the reconnection schematics to determine the voltage configuration. Route leads through current transformers and connect per the diagram.
  4. If the controller has meters, reposition the meter scale lamp jumper to match the desired voltage.
  5. Recalibrate the overvoltage shutdown if reconnecting to or from 139/240 V (low wye) or 277/480 V (high wye) 3-phase 4-wire 60 Hz.
  6. Set the phase selector switch to L1-L2 or connect a voltmeter across leads L1 and L2.
  7. Reconnect the starting battery, negative (--) lead last. Start the generator set and verify the voltage changed to the desired value; adjust if needed.
  8. Stop the generator set after completing the voltage adjustment. Replace the controller cover.
Bleeding Air from the Fuel System maintenance

⚠ Correct any fuel leaks encountered during the priming procedure.

⚠ Trapped air in the fuel system causes difficult starting and/or erratic engine operation.

Tools: Hand prime pump kit

  1. Place the fuel valves in the fuel system prime position. Close the fuel valve between the pipe tee and the engine.
  2. Open the fuel valves on each side of the fuel prime pump.
  3. Loosen the bleed screw at the engine. Refer to the engine operation manual for bleed screw location.
  4. Rotate the hand prime pump handle counterclockwise until fuel flows from the bleed screw. Stop pumping.
  5. Tighten the bleed screw. Wipe up any fuel leakage.
  6. Place the fuel valves in the normal operation position: open the engine-side valve, close the prime pump valves.
Cooling System Drainage Procedure maintenance

⚠ Dispose of all waste materials (oil, fuel, coolant, filters, and gaskets) in an environmentally safe manner.

  1. Deenergize the block heater, if equipped.
  2. Remove the pressure cap to allow the entire system to drain and prevent air pockets from restricting coolant flow.
  3. Open the radiator and/or engine block coolant drain valve(s) and allow the system to drain.
  4. If the radiator has mineral deposits or the coolant contains dirt or grease, flush and clean the system.
Cooling System Refilling Procedure maintenance

⚠ Do not add coolant to a hot engine.

⚠ Do not use alcohol or methanol antifreeze or mix them with the specified coolant.

⚠ Check the coolant level in the recovery tank after each operation until the level stabilizes.

  1. Remove the pressure cap.
  2. Close the radiator and/or engine block coolant drain valve(s) and tighten the cooling system hose clamps.
  3. Open the air-bleed petcocks, if equipped. Close them when coolant begins to flow.
  4. Add coolant additives or water pump lubricants per the engine manufacturer's recommendations.
  5. Fill the cooling system with the recommended 50% ethylene glycol and 50% clean, softened water mixture.
  6. Replace the pressure cap.
  7. Fill the coolant recovery tank to the low mark.
  8. Operate the generator set until the thermostat opens when the upper cooling system hose warms.
  9. Stop the engine and allow it to cool.
  10. Remove the pressure cap.
  11. Add coolant to bring the level to just below the overflow tube opening of the filler neck.
  12. Replace the pressure cap.
  13. Maintain the coolant level in the coolant recovery tank between the high and low marks.
  14. Reenergize the block heater, if equipped.
Fan Bearing Lubrication and Drive Belt Adjustment Procedure maintenance

⚠ The fan shaft and idler shaft bearings have pressure relief ports to prevent bearing damage caused by overlubrication.

Tools: Grease gun, Poly V-belt tension gauge

  1. Place the generator set master switch in the OFF/RESET position.
  2. Disconnect the engine starting battery(ies), negative (--) lead first, and disconnect power to the battery charger.
  3. Remove the belt guards to expose the fan shaft and idler shaft bearings.
  4. Inject grease into the two fan shaft bearings and the two idler shaft bearings until a 3--6 mm (0.13--0.25 in.) grease column shows at each pressure relief port.
  5. Remove excess grease from the bearing pressure relief ports.
  6. Inspect the fan drive belt and replace if damaged or worn. Check belt tension with a poly V-belt tension gauge and adjust if necessary.
  7. Reinstall the belt guards using the original hardware.
  8. Reconnect the starting battery(ies), negative (--) lead last.
  9. Test run the generator set for a few minutes and listen for belt noise (squeal) indicating a slipping belt. Stop the generator set.
Inner Fuel Tank Leak Alarm Resetting Procedure maintenance

⚠ If the alarm switch is in the SILENCE position the alarm horn will not sound should a fuel leak occur.

  1. Move the alarm switch to the SILENCE position to stop the alarm horn. The lamp remains lit.
  2. Disconnect the generator set from the load with the line circuit breaker or automatic transfer switch.
  3. Repair or replace the inner fuel tank.
  4. Move the generator master switch to the OFF/RESET position and then to RUN for startup. Alarm horn sounds and lamp goes out.
  5. Reconnect the generator to the load via the line circuit breaker or automatic transfer switch.
  6. Move the master switch to AUTO for remote startup and move the alarm switch to the NORMAL position.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What size generator is the Kohler 2000ROZD?

The Kohler 2000ROZD is rated 2000 kW standby (2500.0 kVA).

What engine does the Kohler 2000ROZD use?

The Kohler 2000ROZD is powered by the MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16) engine.

What fuel does the Kohler 2000ROZD use?

The Kohler 2000ROZD runs on diesel.

What's the oil capacity on a Kohler 2000ROZD?

The MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16) engine in the Kohler 2000ROZD has an oil capacity of 465.0 liters.

What is the cooling system capacity of the Kohler 2000ROZD?

The Kohler 2000ROZD cooling system holds 565 liters (149.3 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the prime power rating of the Kohler 2000ROZD?

The Kohler 2000ROZD is rated 1820 kW prime (2275 kVA), against 2000 kW standby.

What voltages is the Kohler 2000ROZD available in?

The Kohler 2000ROZD is offered in 220/380 V, 240/416 V, 277/480 V, 347/600 V, 2400/4160 V, 1905/3300 V, 3-phase.

What battery does the Kohler 2000ROZD use?

The Kohler 2000ROZD uses 2 batteryies, 24 V each, 950 CCA, group 24, per the manufacturer specification sheet.

Which alternator is fitted to the Kohler 2000ROZD?

The Kohler 2000ROZD uses a 4-Pole, Rotating-Field alternator. It has 4 poles. Insulation class Class H.

What oil filter does the Kohler 2000ROZD use?

The Kohler 2000ROZD uses oil filter part number 279260.

What fuel filter fits the Kohler 2000ROZD?

The Kohler 2000ROZD uses fuel filter part number 274821.

Which air filter part number does the Kohler 2000ROZD take?

The Kohler 2000ROZD uses air filter part number 347667.

Parts

20
Part #DescriptionQtySystem
274623Cleaner, Air2Air filter Amazon eBay
274821Air Cleaner26Air filter eBay $100.00
279260Filter, oil2Oil filter Amazon eBay $20.47 NAPA $37.15
347423Belt, Poly V1Belt Amazon eBay
347429V-Belt1Belt Amazon eBay
347437Tube, Upper Radiator1Hose Amazon eBay
347440Tube, Lower Radiator1Hose Amazon eBay
347442Gasket, Inlet1Gasket Amazon eBay
347646Sensor, Liquid Level1Sensor Amazon eBay
347667Air Cleaner Assembly24Air filter Amazon eBay
347810Air Cleaner6Air filter Amazon eBay
X-507-6Lower Radiator Hose1Hose Amazon eBay
X-6006-4Upper Radiator Hose1Hose Amazon eBay
243273Fuse, 3 amp5Service part / kit Amazon eBay
283645Fuse, 15 Amp5Service part / kit Amazon eBay
291207Fuse, 1.5 amp1Service part / kit Amazon eBay
291740Rectifier or Coil1Service part / kit Amazon eBay
328725Voltage Regulator1Service part / kit Amazon eBay
A-347395-1Engine Assembly, 2000 kW1Service part / kit Amazon eBay
A-347485Radiator Assembly1Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime50%38.510.2
Prime75%56.314.9
Prime100%503.0132.88
Standby50%42.011.1
Standby75%61.716.3
Standby100%441.0116.5

Available documents

Spec sheet (Kohler)Spec sheet — Kohler-2000ROZD4-spec-sheet (Kohler)Operator's manual — Kohler-20-2000-kW-operation-manual-decision-maker-3 -16-light (Kohler)Reference — Mantanince Kits (Kohler)Parts manual — g260412 (Kohler)Parts manual — tp5816 (Kohler)Service manual — tp5722 (Kohler)Service manual — tp5851 (Kohler)

This page was generated from the 8 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.

Full service, cheapest listings

Priced items from this model's own parts manual.

Fuel filter (secondary) 274821$100.00
Oil filter 279260$20.47
2 priced items$120.47