Kohler 2000ROZD — Emergency Stop Switch Resetting Procedure
Operation · Emergency stop switch and air damper
For the Kohler 2000ROZD, from the Kohler operator's manual.
Applies to: Kohler 2000ROZD
Before you start
- The generator set does not crank until the resetting procedure is completed.
Procedure
- Investigate the cause of the emergency stop and correct the circuit or wiring problem(s).
- If the remote emergency stop switch was activated, reset it by replacing the glass piece. If the controller-mounted switch was activated, rotate it clockwise until it springs back.
- If the controller air damper lamp is lit, reset the engine air damper by rotating the air damper lever until the light goes out.
- Toggle the generator set master switch to OFF/RESET and then to RUN or AUTO to restart the generator set.
Tools required
- Replacement glass piece Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Full service-parts list: Kohler 2000ROZD →
Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.