Kohler 2000ROZD — Controller Resetting After a Fault Shutdown
Operation · Microprocessor controller
For the Kohler 2000ROZD, from the Kohler operator's manual.
Applies to: Kohler 2000ROZD
Before you start
- Place the generator set master switch in the AUTO position before silencing the alarm horn.
Procedure
- Move the controller alarm horn switch to the SILENCE position; silence the audiovisual annunciator if equipped.
- Disconnect the generator set from the load using the line circuit breaker or automatic transfer switch.
- Correct the cause of the fault shutdown.
- Start the generator set by moving the master switch to OFF/RESET and then to RUN.
- Verify that the cause of the shutdown was corrected by test operating the generator set.
- Reconnect the generator set to the load using the line circuit breaker or automatic transfer switch.
- Move the master switch to the AUTO position for startup by remote transfer switch or remote start/stop switch.
- Move the controller alarm horn switch to the NORMAL position.