Kohler 2000ROZD — Inner Fuel Tank Leak Alarm Resetting Procedure
Maintenance · Subbase double-wall fuel tank leak alarm
For the Kohler 2000ROZD, from the Kohler operator's manual.
Applies to: Kohler 2000ROZD
Before you start
- If the alarm switch is in the SILENCE position the alarm horn will not sound should a fuel leak occur.
Procedure
- Move the alarm switch to the SILENCE position to stop the alarm horn. The lamp remains lit.
- Disconnect the generator set from the load with the line circuit breaker or automatic transfer switch.
- Repair or replace the inner fuel tank.
- Move the generator master switch to the OFF/RESET position and then to RUN for startup. Alarm horn sounds and lamp goes out.
- Reconnect the generator to the load via the line circuit breaker or automatic transfer switch.
- Move the master switch to AUTO for remote startup and move the alarm switch to the NORMAL position.
Full service-parts list: Kohler 2000ROZD →
Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.