Home›Repair guides›Kohler›Bleeding Air from the Fuel System

Kohler 2000ROZD — Bleeding Air from the Fuel System

Maintenance · Diesel fuel system

For the Kohler 2000ROZD, from the Kohler operator's manual.

Applies to: Kohler 2000ROZD

Before you start

  • Correct any fuel leaks encountered during the priming procedure.
  • Trapped air in the fuel system causes difficult starting and/or erratic engine operation.

Procedure

  1. Place the fuel valves in the fuel system prime position. Close the fuel valve between the pipe tee and the engine.
  2. Open the fuel valves on each side of the fuel prime pump.
  3. Loosen the bleed screw at the engine. Refer to the engine operation manual for bleed screw location.
  4. Rotate the hand prime pump handle counterclockwise until fuel flows from the bleed screw. Stop pumping.
  5. Tighten the bleed screw. Wipe up any fuel leakage.
  6. Place the fuel valves in the normal operation position: open the engine-side valve, close the prime pump valves.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Kohler 2000ROZD →

Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.