Kohler 2000ROZD — Reactive Droop Compensation Adjustment Procedure (20--300 kW)
Adjustments · Reactive droop rheostat and voltage-sensing lead
For the Kohler 2000ROZD, from the Kohler operator's manual.
Applies to: Kohler 2000ROZD
Before you start
- Read the entire procedure before beginning.
Procedure
- Set the generator set master switch to the OFF/RESET position.
- Set the reactive droop rheostat at minimum (full counterclockwise position).
- Move the voltage-sensing lead inside the controller from terminal V7 to terminal V9.
- Start the generator set and adjust the voltage to the rated system voltage using the voltage-adjusting potentiometer.
- Apply a resistive load (1.0 power factor) at rated current and adjust the reactive droop rheostat to achieve a 6%--8% droop in voltage.
- Remove the load from the generator set.
- Shut down the generator set by placing the master switch in the OFF/RESET position.
- Move the voltage-sensing lead inside the controller from terminal V9 to terminal V7. Repeat for additional generator sets.
Specs & values
- 6%--8% droop in voltage
- Resistive load at 1.0 power factor to rated current
Full service-parts list: Kohler 2000ROZD →
Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.