Home›Engines›MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16)

MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16) Engine

The MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16) is a 65 L turbocharged, intercooled engine rated at 1800 rpm. It powers generator sets from Kohler, including the 2000ROZD. It holds 465 L (122.8 gal) of oil and 151 L (39.9 gal) of coolant.

Also known as: Detroit Diesel/MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16)

Part of the MTU 16V4000 engine family — 66 variants share parts & fitment.

65.0 L
Displacement
1800 rpm
Rated speed
465.0 L
Oil capacity

Engine specifications

Oil capacity465.0 L
Coolant capacity151.0 L
Displacement65.0 L
AspirationTurbocharged, Intercooled
Rated speed1800 rpm

Service intervals

7
ItemActionHoursMonthsNotes
Change oilChange50 hr50 Hours or Yearly
Replace filter(s)Replace50 hr50 Hours or Yearly; service more frequently if operated in dusty areas
Lubricate fan bearings (1200--2000 kW)Lubricate200 hr6 mo200 Hours or Six Months
Blow dust out of alternatorClean300 hr2 Years or 300 Hours; service more frequently if operated in dusty areas
Bolt torqueAdjust500 hr3 Years or 500 Hours
Valve clearanceAdjust500 hr3 Years or 500 Hours
Wire-cable insulation breakdownTest500 hr3 Years or 500 Hours

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

19
TypeItemValueUnitCondition
OtherBattery specific gravity, charge required below1.215at electrolyte temperature 26.7°C (80°F)
OtherBattery specific gravity, fully charged1.260at electrolyte temperature 26.7°C (80°F)
OtherFan bearing grease column at bearing pressure relief port3--6mm (0.13--0.25 in.)
OtherLoad-sharing module droop3% droopat 100% load
OtherPoly V-belt tension, 1200-2000 kW, new belt2450--2890N (550--650 lbf)new belt
OtherPoly V-belt tension, 1200-2000 kW, used belt1650--1910N (370--430 lbf)used belt (after 50 hours of service)
OtherReactive droop, 20--300 kW reactive droop compensation adjustment6%--8% droop in voltageat rated current, 1.0 power factor resistive load
OtherSpecific gravity variation between cells±0.01
PressureAutomatic fuel changeover switchpoint (primary fuel pressure)0.6 kPa (1.4 oz./in.2) or 6.4 cm (2.5 in.) water columnkPa
PressureLP liquid withdrawal fuel system leak test pressureat least 90 psi (621 kPa)psileak test with soap and water solution
PressureLP vapor or natural gas fuel system leak test pressure6--8 ounces per square inch (10--14 inches water column)oz./in.2leak test with soap and water solution
SpeedOverspeed shutdown (50 and 60 Hz models)70 Hz (2100 rpm)governed frequency exceeds
SpeedRated engine speed1800 rpm at 60 Hz or 1500 rpm at 50 Hzrpm
TemperatureCoolant freezing protection, 50% ethylene glycol solution--37°C (--34°F)
TemperatureCoolant overheating protection, 50% ethylene glycol solution129°C (265°F)
VoltageOvervoltage calibration output voltage115% of the nominal output voltage
VoltageOvervoltage shutdownat least 15% over the nominal voltage for longer than 2 seconds
VoltageOvervoltage shutdown calibration, 139/240 V (low wye) or 277/480 V (high wye), 3-phase, 4-wire, 60 Hzapproximately 160Vacross terminals V0 and V7 at 115% of nominal output voltage
VoltageOvervoltage shutdown calibration, all other voltagesapproximately 140Vacross terminals V0 and V7 at 115% of nominal output voltage

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50% ethylene glycol and 50% clean, softened waterabove -37°CProvides freezing protection to --37°C (--34°F) and overheating protection to 129°C (265°F). Do not use alcohol or methanol antifreeze. See generator set spec sheet for coolant capacity.
Engine oil10W40 or 10W50API classification SH/CD, SG/CD, SH/CC, or SG/CCabove -23°CFor air temperatures consistently above --23°C (--10°F); Ford-powered 30, 80, and 100 kW models
Engine oil20W50 or 10W40API classification SH/CD, SG/CD, SH/CC, or SG/CCabove 0°CFor air temperatures consistently above 0°C (32°F); Ford-powered 30, 80, and 100 kW models
GreaseMobil Mobilith AW2 NLGI Grade 2 or equivalentLithium-complex base, multi-purpose grease with antirust, antifoam, and extreme-pressure additives, minimum dropping point 204°C (400°F)Radiator fan shaft and idler shaft bearings, 1200--2000 kW models
GreaseChevron SRI or equivalentAntifriction, high-quality grease with lubrication temperature range --30° to 175°C (--22° to 350°F)-30°C to 175°C350--2000 kW models with single-bearing alternator

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Gaseous Carburetor (Fuel Mixer) Adjustment Procedure adjustment

⚠ Verify that engine compression and the ignition system meet specifications before adjusting the carburetor.

⚠ Some engines have sealed carburetors that are not adjustable.

  1. Start the generator set and run it at approximately half load.
  2. Adjust the engine fuel mixture screw until the engine runs smoothly.
  3. Apply varying loads and readjust the carburetor as necessary to achieve smooth engine performance at all load levels.
  4. Stop the generator set.
LP Fuel Conversion Procedure adjustment

⚠ Not all fuel regulators require spring and retainer removal for fuel conversion. A hang tag on the fuel regulator identifies the conversion procedure.

  1. Remove the fuel regulator cover plug.
  2. Remove the adjustment screw and spring from the fuel regulator. Save them for conversion back to natural gas.
  3. Reinstall the cover plug.
Natural Gas Fuel Conversion Procedure adjustment

⚠ Lower-than-specified pressures may result in poor response to load changes or lack of power.

Tools: Manometer

  1. Remove the fuel regulator cover plug.
  2. Replace the spring and adjustment screw.
  3. Connect a manometer to check fuel supply pressure on the carburetor side of the regulator, downstream of accessories.
  4. With the generator set running at full load, rotate the adjustment screw until manometer pressure matches the specified pressure.
  5. Reinstall the cover plug.
Overvoltage Shutdown Adjustment (Decision-Maker 3 Controller) adjustment

⚠ Do not contact electrical connections with tools or jewelry while making adjustments or repairs.

  1. With the generator set idle, open the output line circuit breaker to disconnect the load.
  2. Remove the controller cover.
  3. Install the J1 jumper if the set is connected for 139/240 V (low wye) or 277/480 V (high wye) 3-phase, 4-wire, 60 Hz. Remove it for all other voltages.
  4. Replace the cover.
Overvoltage Shutdown Adjustment (Decision-Maker 3+ Controller) adjustment

⚠ Do not use the safeguard circuit breaker in place of the line circuit breaker.

⚠ Do not contact electrical connections with tools or jewelry while making adjustments or repairs.

Tools: Digital AC voltmeter, Insulated-handle screwdriver, RTV sealant

  1. Disconnect the engine starting battery, negative (--) lead first. Disconnect power to the battery charger.
  2. With the generator set idle, open the output line circuit breaker to disconnect the load.
  3. Remove the controller cover.
  4. Wrap the shaft of an insulated-handle screwdriver with electrical tape. Turn potentiometer R41 or R42 fully clockwise.
  5. Connect a digital AC voltmeter to terminals V0 and V7 on the controller terminal block.
  6. Reconnect the battery, negative (--) lead last.
  7. Start the generator set by placing the master switch in the RUN position.
  8. Adjust output voltage to 115% of nominal (approximately 160 V across V0 and V7 for low wye/high wye; approximately 140 V for all other voltages).
  9. Slowly rotate R41 or R42 counterclockwise until red LED4 lights. The set should shut down on overvoltage in approximately 2 seconds.
  10. Turn the voltage adjustment potentiometer counterclockwise to reduce output voltage, restart, and slowly increase voltage to verify the shutdown setting.
  11. Reduce output voltage, restart, and readjust the generator set output to nominal voltage.
  12. Stop the generator set. Seal potentiometer R41 with RTV sealant or equivalent. Replace the controller cover.
Reactive Droop Compensation Adjustment Procedure (20--300 kW) adjustment

⚠ Read the entire procedure before beginning.

  1. Set the generator set master switch to the OFF/RESET position.
  2. Set the reactive droop rheostat at minimum (full counterclockwise position).
  3. Move the voltage-sensing lead inside the controller from terminal V7 to terminal V9.
  4. Start the generator set and adjust the voltage to the rated system voltage using the voltage-adjusting potentiometer.
  5. Apply a resistive load (1.0 power factor) at rated current and adjust the reactive droop rheostat to achieve a 6%--8% droop in voltage.
  6. Remove the load from the generator set.
  7. Shut down the generator set by placing the master switch in the OFF/RESET position.
  8. Move the voltage-sensing lead inside the controller from terminal V9 to terminal V7. Repeat for additional generator sets.
Voltage Reconnection Procedure adjustment

⚠ Verify that the voltage ratings of the transfer switch, line circuit breakers, and other accessories match the selected line voltage.

⚠ Affix a notice to the generator set after reconnecting to a voltage different from the nameplate voltage.

Tools: Voltmeter, Screwdriver

  1. Place the generator set master switch in the OFF/RESET position.
  2. Disconnect the engine starting battery, negative (--) lead first. Disconnect power to the battery charger.
  3. Use the reconnection schematics to determine the voltage configuration. Route leads through current transformers and connect per the diagram.
  4. If the controller has meters, reposition the meter scale lamp jumper to match the desired voltage.
  5. Recalibrate the overvoltage shutdown if reconnecting to or from 139/240 V (low wye) or 277/480 V (high wye) 3-phase 4-wire 60 Hz.
  6. Set the phase selector switch to L1-L2 or connect a voltmeter across leads L1 and L2.
  7. Reconnect the starting battery, negative (--) lead last. Start the generator set and verify the voltage changed to the desired value; adjust if needed.
  8. Stop the generator set after completing the voltage adjustment. Replace the controller cover.
Bleeding Air from the Fuel System maintenance

⚠ Correct any fuel leaks encountered during the priming procedure.

⚠ Trapped air in the fuel system causes difficult starting and/or erratic engine operation.

Tools: Hand prime pump kit

  1. Place the fuel valves in the fuel system prime position. Close the fuel valve between the pipe tee and the engine.
  2. Open the fuel valves on each side of the fuel prime pump.
  3. Loosen the bleed screw at the engine. Refer to the engine operation manual for bleed screw location.
  4. Rotate the hand prime pump handle counterclockwise until fuel flows from the bleed screw. Stop pumping.
  5. Tighten the bleed screw. Wipe up any fuel leakage.
  6. Place the fuel valves in the normal operation position: open the engine-side valve, close the prime pump valves.
Cooling System Drainage Procedure maintenance

⚠ Dispose of all waste materials (oil, fuel, coolant, filters, and gaskets) in an environmentally safe manner.

  1. Deenergize the block heater, if equipped.
  2. Remove the pressure cap to allow the entire system to drain and prevent air pockets from restricting coolant flow.
  3. Open the radiator and/or engine block coolant drain valve(s) and allow the system to drain.
  4. If the radiator has mineral deposits or the coolant contains dirt or grease, flush and clean the system.
Cooling System Refilling Procedure maintenance

⚠ Do not add coolant to a hot engine.

⚠ Do not use alcohol or methanol antifreeze or mix them with the specified coolant.

⚠ Check the coolant level in the recovery tank after each operation until the level stabilizes.

  1. Remove the pressure cap.
  2. Close the radiator and/or engine block coolant drain valve(s) and tighten the cooling system hose clamps.
  3. Open the air-bleed petcocks, if equipped. Close them when coolant begins to flow.
  4. Add coolant additives or water pump lubricants per the engine manufacturer's recommendations.
  5. Fill the cooling system with the recommended 50% ethylene glycol and 50% clean, softened water mixture.
  6. Replace the pressure cap.
  7. Fill the coolant recovery tank to the low mark.
  8. Operate the generator set until the thermostat opens when the upper cooling system hose warms.
  9. Stop the engine and allow it to cool.
  10. Remove the pressure cap.
  11. Add coolant to bring the level to just below the overflow tube opening of the filler neck.
  12. Replace the pressure cap.
  13. Maintain the coolant level in the coolant recovery tank between the high and low marks.
  14. Reenergize the block heater, if equipped.
Fan Bearing Lubrication and Drive Belt Adjustment Procedure maintenance

⚠ The fan shaft and idler shaft bearings have pressure relief ports to prevent bearing damage caused by overlubrication.

Tools: Grease gun, Poly V-belt tension gauge

  1. Place the generator set master switch in the OFF/RESET position.
  2. Disconnect the engine starting battery(ies), negative (--) lead first, and disconnect power to the battery charger.
  3. Remove the belt guards to expose the fan shaft and idler shaft bearings.
  4. Inject grease into the two fan shaft bearings and the two idler shaft bearings until a 3--6 mm (0.13--0.25 in.) grease column shows at each pressure relief port.
  5. Remove excess grease from the bearing pressure relief ports.
  6. Inspect the fan drive belt and replace if damaged or worn. Check belt tension with a poly V-belt tension gauge and adjust if necessary.
  7. Reinstall the belt guards using the original hardware.
  8. Reconnect the starting battery(ies), negative (--) lead last.
  9. Test run the generator set for a few minutes and listen for belt noise (squeal) indicating a slipping belt. Stop the generator set.
Inner Fuel Tank Leak Alarm Resetting Procedure maintenance

⚠ If the alarm switch is in the SILENCE position the alarm horn will not sound should a fuel leak occur.

  1. Move the alarm switch to the SILENCE position to stop the alarm horn. The lamp remains lit.
  2. Disconnect the generator set from the load with the line circuit breaker or automatic transfer switch.
  3. Repair or replace the inner fuel tank.
  4. Move the generator master switch to the OFF/RESET position and then to RUN for startup. Alarm horn sounds and lamp goes out.
  5. Reconnect the generator to the load via the line circuit breaker or automatic transfer switch.
  6. Move the master switch to AUTO for remote startup and move the alarm switch to the NORMAL position.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the MTU 16V4000 family

46
Part #DescriptionCategory
274623Cleaner, AirAir filter
274821Air CleanerAir filter
347667Air Cleaner AssemblyAir filter
347810Air CleanerAir filter
WM00076Air filter elementAir filter
12V4000Gx3-07BatteryBattery
12V4000Gx3-06BeltBelt
347423Belt, Poly VBelt
347429V-BeltBelt
12V4000Gx3-02Engine oil filterFilter
12V4000Gx3-03Fuel filterFilter
12V4000Gx3-04Air filterFilter
12V4000Gx3-01Engine oilFluid
12V4000Gx3-05CoolantFluid
WM00086Easy-change fuel filterFuel filter
347442Gasket, InletGasket
5272030080GASKETGasket
X00021730GASKETGasket
347437Tube, Upper RadiatorHose
347440Tube, Lower RadiatorHose
X-507-6Lower Radiator HoseHose
X-6006-4Upper Radiator HoseHose
279260Filter, oilOil filter
WM00067Oil filter elementOil filter
243273Fuse, 3 ampService part / kit
283645Fuse, 15 AmpService part / kit
291207Fuse, 1.5 ampService part / kit
291740Rectifier or CoilService part / kit
328725Voltage RegulatorService part / kit
A-347395-1Engine Assembly, 2000 kWService part / kit
A-347485Radiator AssemblyService part / kit
007603014102COPPER SEALING RINGSeal
007603030101COPPER SEALING RINGSeal
05132155SEALSeal
52420300037THERMAL ACTUATOR DICHTRING AUS FKMSeal
700429070000O-RINGSeal
700429072000O-RINGSeal
700429076000O-RINGSeal
735252070000O-RINGSeal
735252085001O-RINGSeal
735252090000O-RINGSeal
735252100000O-RINGSeal
347646Sensor, Liquid LevelSensor
12V4000Gx3-08Spark plugSpark plug
M128RStarterStarter
59420300059THERMAL ACTUATORThermostat

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Also used in

1
  • Belaz 75302 — Dump Truck

Other equipment known to use this engine, via filter-application cross-reference — useful for sourcing parts even when your exact machine isn't listed elsewhere on this page.

Common questions

What is the oil capacity of the MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16)?

The MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16) engine has an oil capacity of 465.0 liters.

What is the displacement of the MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16)?

The MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16) has a displacement of 65.0 liters.

Which generators use the MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16) engine?

The MTU 16V4000 (T163-7K36) / 16V4000 (T163-7K16) powers 1 generator set(s), including Kohler 2000ROZD.