Service parts for the Panda 15 mini PMS Digital
Grouped by system, with how many of each the parts manual calls for.
Air intake
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
| Frequency | 60.0 Hz |
|---|---|
| Standby power | 15 kW |
| Standby kVA | 24 |
| Prime power | 15 kW |
| Oil capacity | 3.7 L |
| Voltage options | 120 V, 240 V, 60 V, 16 V, 230 V, 50 V, 15 V |
Engine
| Oil capacity | 3.7 L |
|---|---|
| Coolant capacity | 4.1 L |
| Displacement | 0.898 L |
| Aspiration | Water cooled |
| Rated speed | 3600 rpm |
Filters for the Kubota D902
5Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Oil filter | P550162 | Lube Filter, Spin-On Full Flow | KUBOTA 1524132040, KUBOTA 1542132090, NAPA 1301, NAPA 1334 | FridayParts $10.50 |
| Oil filter | P550318 | Lube Filter, Spin-On Full Flow | KUBOTA 1505632432, KUBOTA 1609831291, NAPA 21521, NAPA H10W02 | FridayParts $23.27 |
| Fuel filter | P550127 | Fuel Filter, Spin-On | KUBOTA 1522143170, KUBOTA 1522143171, NAPA 3390, WALGAHN-MOTORENTECHN 00811936 | KuduParts $16.00 |
| Fuel filter | P550012 | Fuel Filter, In-Line | KUBOTA 1258143010, KUBOTA 1258143011, BALDWIN BF840-K1, RENAULT VI 0005490862 | KuduParts $13.00 FridayParts $15.50 |
| Fuel / water separator | P551039 | Fuel Filter, Water Separator Spin-On Twist&Drain | NAPA 3192, BALDWIN BF1257, CLUB CAR 102614001, CLUB CAR 102703401 | FridayParts $25.40 KuduParts $97.00 |
Same engine, other brands
4 brandsThe Kubota D902 in this set also powers 8 generator sets sold under 4 other brands. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| Atlas Copco | XAS 110 KD, XAS 48, XAS 48 Kd |
| Kubota | GL 14000, GL14000-USA |
| MQ Power | TGL12SPX2, TLG-12SPX3 |
| Vmac | MF-KUBOTA M200077 |
Maintenance & consumables
for the Kubota D902| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | RG15842930 | 1000 hr | Amazon eBay $15.50 PartsGeek $23.97 FridayParts $16.50 | ||
| Fuel filter | — | 500 hr | |||
| Oil filter | — | 1000 hr | |||
| Battery | — | 24000 hr | |||
| Belt | — | 500 hr | |||
| Coolant | 5.0 | — | 24000 hr | ||
| Coolant filter | — | ||||
| Fuel | drain from tank and refill with a protective mixture (90 % diesel and 10 % preservative oil) (level to full). | — | |||
| Oil | 3.6 | — | 100 hr | ||
| Spark plug | — | 1000 hr |
Compatible filters for the Kubota D902 — cross-referenced via Donaldson. Options to verify against your serial number, not confirmed for this exact unit.
- Fuel filter: Kubota 1258143013 Kubota 1522143081 Donaldson P550012 Donaldson P551039 Donaldson P550127
- Oil filter: Kubota 7665025430 Kubota 1641432434 Donaldson P550162 Donaldson P550318 Wix 51334
Service intervals
8| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Engine oil | Change | 150 hr | First service — First oil change after 35 to 50 hours | |
| Engine oil filter | Change | 150 hr | First service — First oil change after 35 to 50 hours | |
| Generator | Inspect | 150 hr | Complete 150 h inspection after long-term standstill | |
| V-belt | Check | 150 hr | V-belt must be checked every 150 hours | |
| Oil screen | Clean | 500 hr | EA300 engines only | |
| Hoses and rubber parts | Inspect | 12 mo | Regularly; may require renewal once a year | |
| Servo motor trapezoid thread-spindle | Lubricate | 1 mo | Once a month grease/oil | |
| Starter battery | Check | 2 mo | Charge at least every 2 months |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
29| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Minimum distance exhaust elbow to water level | 600 | mm | waterlock in ideal position |
| Clearance | V-belt deflection | approx. 10 | mm | |
| Other | Battery electrolyte density | 1,08 | kg/l | tropical, discharged, immediately charge |
| Other | Battery electrolyte density | 1,12 | kg/l | normal, discharged, immediately charge |
| Other | Battery electrolyte density | 1,20 | kg/l | normal, semi-charged, re-charge |
| Other | Battery electrolyte density | 1,23 | kg/l | tropical, well charged |
| Other | Battery electrolyte density | 1,28 | kg/l | normal, well charged |
| Other | Compression ratio | 24:1 | ||
| Other | Fuel pump max pump head | 2500 | mm | |
| Other | Fuel pump max suction lift | 500 | mm | |
| Other | Max power (SAEJ1349) | 17,5 | kW | at 3600 rpm |
| Other | Pre-glow time | 5-6 | sec | at 20 °C or more |
| Other | Pre-glow time maximum | 20 | sec | |
| Other | Recommended oil level | 2/3 | between minimum and maximum | |
| Other | Standard exhaust system total length maximum | 6,3 | m | |
| Pressure | Exhaust backpressure at exhaust out of sound isolation cover | 80 | mbar | installation design condition |
| Pressure | Max exhaust backpressure | 9,3 | kPa | 93 mbar also stated |
| Resistance | Capacitor discharge reactor | 5-10 | kOhm | |
| Speed | Idle running speed | 3500 | rpm | progressive speed by VCS |
| Speed | Rated speed | 3600 | rpm | |
| Torque | Cylinder head nut torque | 42 | Nm | |
| Valve clearance | Valve clearance | 0,2 | mm | engine cold |
| Voltage | AC voltage normal range | 100-130 | V | 60 Hz |
| Voltage | AC voltage normal range | 200-240 | V | 50 Hz |
| Voltage | Battery open-circuit voltage, flat | 11,7 | V | 12 V battery |
| Voltage | Battery open-circuit voltage, flat | 23,4 | V | 24 V battery |
| Voltage | Conservation charging voltage | 13,2 | V | 12 V battery |
| Voltage | Conservation charging voltage | 26,4 | V | 24 V battery |
| Voltage | Insulation test maximum voltage | 50 | mV | between generator housing and AC-Control box/ground |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | GLYSANTIN PROTECT PLUS / G48 | suitable for aluminium | Mixture ratios: 70:30 -20 °C; 65:35 -25 °C; 60:40 -30 °C; 55:45 -35 °C; 50:50 -40 °C | ||
| Engine oil | SAE10W or SAE10W-30; SAE10W-40 | above API CF | below 0°C | 3.7 l | below 0 °C; oil change section also states SAE30 over 20 °C, SAE20 between 5 °C and 20 °C, SAE10W or 10W-30 under 5 °C |
| Engine oil | SAE20 or SAE10W-30; SAE10W-40 | above API CF | 0°C to 25°C | 3.7 l | 0 °C to 25 °C |
| Engine oil | SAE30 or SAE10W-30; SAE10W-40 | above API CF | above 25°C | 3.7 l | over 25 °C |
| Fuel | Diesel fuel oil according to DIN590:1999 or better | DIN590:1999; DIN590:2009 for common rail or particle filter | Do not use alternative fuel. Troubleshooting recommends 2-D Diesel. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
80| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| CA00 | AC voltage above threshold | AC voltage is above threshold | Shutdown | |
| CA01 | AC voltage below threshold | AC voltage is below threshold | Shutdown | |
| CA02 | AC current above threshold | AC current is above threshold | Shutdown | |
| CA03 | AC power above threshold | AC power is above threshold | Shutdown | |
| CA04 | DC voltage above threshold | DC voltage is above threshold | Shutdown | |
| CA05 | Coolant in temperature above threshold | Coolant in temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Shutdown | |
| CA07 | Cylinder head temperature above threshold | Cylinder head temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Shutdown | |
| CA08 | Exhaust elbow temperature above threshold | Exhaust elbow temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Shutdown | |
| CA09 | Winding temperature above threshold | Winding temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Shutdown | |
| CA10 | Oil pressure below threshold | Oil pressure is below threshold; will not be set if sensor is missing, shorted or disabled | Shutdown | |
| CA11 | Alternator bearing temperature above threshold | Alternator bearing temperature is above threshold; missing current sensing device equals missing sensor | Shutdown | |
| CA12 | Internal 5V supply voltage below threshold | Internal 5V supply voltage is below threshold | Shutdown | |
| CA13 | Actuator current above threshold | Actuator current is above threshold | Shutdown | |
| CA14 | Engine speed above threshold | Engine speed is above threshold | Shutdown | |
| CA15 | Internal 5V supply voltage above threshold | Internal 5V supply voltage is above threshold | Shutdown | |
| CW00 | AC voltage above threshold | AC voltage is above threshold | Warning | |
| CW01 | AC voltage below threshold | AC voltage is below threshold | Warning | |
| CW02 | AC current above threshold | AC current is above threshold | Warning | |
| CW03 | AC power above threshold | AC power is above threshold | Warning | |
| CW04 | DC voltage above threshold | DC voltage is above threshold | Warning | |
| CW05 | Coolant in temperature above threshold | Coolant in temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Warning | |
| CW07 | Cylinder head temperature above threshold | Cylinder head temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Warning | |
| CW08 | Exhaust elbow temperature above threshold | Exhaust elbow temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Warning | |
| CW09 | Winding temperature above threshold | Winding temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Warning | |
| CW10 | Oil pressure below threshold | Oil pressure is below threshold; will not be set if sensor is missing, shorted or disabled | Warning | |
| CW11 | Alternator bearing temperature above threshold | Alternator bearing temperature is above threshold; missing current sensing device equals missing sensor | Warning | |
| CW12 | Internal 5V supply voltage below threshold | Internal 5V supply voltage is below threshold | Warning | |
| CW13 | Actuator current above threshold | Actuator current is above threshold | Warning | |
| CW14 | Engine speed above threshold | Engine speed is above threshold | Warning | |
| CW15 | Internal 5V supply voltage above threshold | Internal 5V supply voltage is above threshold | Warning | |
| MS0 | VCS is in re-start delay | VCS is in re-start delay | Info | |
| MS01 | USB port connected to host PC | USB port on VCS board is connected to host PC | Info | Will precede CAN communication |
| MS02 | VCS powered up via CAN bus | VCS is powered up via CAN bus (panel) | Info | |
| MS03 | Battle short active | Battle short is active (input from panel, static) | Info | Military applications only |
| MS04 | Cumulative data not synced | Cumulative data in VCS memory not synced | Info | VCS board will retrieve data from panels |
| MS05 | Actuator current peak | Actuator current has reached peak level | Info | VCS will retract actuator |
| MS06 | Not used | Not used on this control system | Info | |
| MS07 | Coolant temperature above max level | Coolant temperature above max. level | Info | User needs to check coolant system |
| MW00 | Battery voltage low | Battery voltage is low | Warning | |
| MW01 | Frequency out of range | Frequency is out of range | Warning | |
| MW02 | VCS temperature high | VCS temperature is high | Warning | |
| MW03 | CT board temperature high | CT board temperature is high | Warning | |
| MW04 | Tank level low | Tank level is low | Warning | |
| MW05 | CAN bus hardware problem | HW problem with CAN bus in VCS | Warning | |
| MW06 | Oil pressure above plausible value | Oil pressure above plausible value | Warning | Differs from checking supply voltage for sensor |
| MW07 | AC voltage does not build up | Engine is running but AC voltage does not build up | Warning | Reading AC frequency but not voltage |
| MW08 | CT data invalid | CT data invalid; running on VCS | Warning | |
| MW09 | Fuel pump current low | Fuel pump current is low | Warning | |
| MW10 | Fuel pump current high | Fuel pump current is high | Warning | |
| MW11 | Missing coil temperature sensor | Missing coil temperature sensor | Warning | |
| MW12 | Actuator misaligned or not calibrated | Actuator is misaligned or not calibrated | Warning | |
| MW13 | Current GND breaker too high | Current GND breaker too high, output is off | Warning | Will reset if below warning level, will latch if above shutdown. Will unlatch with POR only |
| MW14 | Missing coolant-in temperature sensor | Missing temperature sensor for coolant in | Warning | |
| MW15 | Missing CT board | Missing CT board. Using VCS readings for control | Warning | |
| MW16 | Panel not programmed | Panel is not programmed | Warning | |
| MW17 | Missing alternator bearing temperature sensor | Missing alternator bearing temp. sensor | Warning | |
| MW18 | Tank sensor not working | Tank sensor is enabled but it is not working | Warning | |
| MW19 | AC voltage not balanced | AC voltage is not balanced | Warning | |
| MW20 | Missing cylinder head temperature sensor | Missing temp. sensor for cylinder head | Warning | |
| MW21 | No panel connected | No panel connected to the VCS | Warning | |
| MW22 | CT board not programmed or calibrated | CT board is not programmed / not calibrated | Warning | |
| MW23 | CT board no pulses | CT board sensing AC current but no pulses | Warning | |
| MW24 | AC inputs read DC | AC inputs on CT board read DC | Warning | |
| MW25 | CT terminal temperature sensors not OK | None of the CT terminal temp. sensors reading OK | Warning | |
| MW26 | VCS not reporting AC readings | VCS not reporting AC readings | Warning | Using CT board instead |
| MW27 | VCS not reading AC voltage or frequency | VCS is not reading AC voltage or AC frequency | Warning | |
| ST00 | Internal VCS hardware problem | Internal VCS hardware problem, generator will not start | Shutdown | Problem while accessing SPI bus or reverse polarity protection MOSFET not engaging |
| ST01 | Fuel pump output short-circuit | Fuel pump output is in short-circuit | Shutdown | Will not reset other than through power cycle |
| ST02 | VCS not programmed or calibrated | VCS is not programmed or not calibrated | Shutdown | |
| ST03 | External stop switch active | External stop switch on VCS is active | Shutdown | As per ABYC requirement. Local switch for disabling the generator is set into Disable |
| ST04 | Current sensing device over-temperature | Current sensing device reads >130°C on one or both terminal temperature sensors | Shutdown | Miss-connection of generator output |
| ST05 | Battery voltage too low for start | Battery voltage too low to perform start attempt | Shutdown | Internal threshold, not programmable |
| ST06 | Water leak sensor tripped | Water leak sensor tripped | Shutdown | Will not be set if sensor is disabled |
| ST07 | Start attempt failed | Start attempt failed | Shutdown | |
| ST08 | Cannot stop engine | Cannot stop engine | Shutdown | Fault on stop solenoid |
| ST10 | Maximum failed starts achieved | Maximum number of consecutive failed starts achieved | Shutdown | |
| ST11 | Unexpected engine stop | Unexpected engine stop | Shutdown | |
| ST12 | Missing engine temperature sensors | Missing both, cylinder head and coolant in temperature sensor | Shutdown | Will not be triggered if sensor is not enabled |
| ST13 | Missing exhaust elbow sensor | Missing sensor for exhaust elbow | Shutdown | Will not be triggered if sensor is not enabled |
| ST14 | Glow plug or fuel pump short-circuit | One of the glow plugs is in SC or the fuel pump is in short-circuit to ground | Shutdown | Will not reset other than through power cycle |
Showing the first 80 of 90 codes.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Check fuel solenoid valve diagnostic
- Locate fuel solenoid valve in front of injection pump.
- Remove small retention screw and plug from valve briefly while operating.
- Replace plug immediately; motor should react by revving high.
- If motor does not react sharply, solenoid valve may be faulty.
Insulation test diagnostic
Tools: voltmeter
- Switch off all on-board electrical devices.
- Start the generator.
- Measure AC voltage with voltmeter between generator housing and AC-Control box.
- Measure AC voltage between generator housing and ground.
- Measured voltage must not exceed 50 mV.
- Check safety systems and leakage current relay if installed.
- Ensure all electrical devices are connected to common ground.
Connection of two 12 V batteries to a 24 V battery bank installation
- Connect (+) cable of first battery.
- Connect (-) cable of second battery.
- Connect (+) cable of second battery.
- Connect (-) cable of first battery.
- Disconnect batteries in reverse procedure.
Check and discharge capacitors maintenance
⚠ Charged capacitors can be lethal. Do not touch capacitor contacts.
Tools: multimeter with capacitor measuring, discharge reactor 5-10 kOhm, insulated pliers/screwdriver
- Never check capacitors while generator motor is running.
- Disconnect terminal lead wires using insulated pliers or screwdriver.
- Discharge capacitor terminals by bridging with discharge reactor.
- For three-phase capacitors discharge between L1-L2, L2-L3, L1-L3.
- Switch multimeter to capacitor measuring; connect probes to terminals.
- Measure capacity of each capacitor.
- Check all capacitors in electrical cabinet.
Checking oil-level maintenance
⚠ Generator and coolant can be hot during and after operation.
Tools: paper towels / cloth for oil dipstick
- Place generator/ship level.
- Run generator about 10 minutes to warm engine; wait 3 minutes.
- Assure generator against accidental start.
- Open generator casing.
- Pull oil dipstick, clean, reinsert, wait 10 seconds.
- Pull and read oil level at lower end.
- Refill if under 1/3; recommended 2/3; do not exceed MAX.
Checking water separator in fuel supply maintenance
- Locate pre-filter with water separator and cock underneath.
- Drain water via cock; water sinks to bottom due to density difference.
- Close cock after draining.
Refilling oil maintenance
Tools: engine oil
- Check oil-level.
- Pull oil dipstick out of check rail.
- Open oil filler cap.
- Fill in oil approx. 1/2 litre; wait about 2 minutes.
- Wipe oil dipstick and put into check rail.
- Pull dipstick and check oil-level.
- If still under 2/3, repeat filling steps.
Replace air filter mat maintenance
Tools: spanner size 8 mm
- Open air suction housing by loosening six screws on housing cover.
- Change air filter mat.
- Close suction air housing.
Replacement of engine oil and engine oil filter maintenance
⚠ Generator and coolant can be hot during and after operation.
Tools: open-ended wrench 17 mm, oil filter wrench, container, oil resistant mat, paper towels
- Warm engine 10 minutes; wait 3 minutes.
- Assure no accidental start; open casing.
- Place oil resistant mat and container; release/open oil drain hose.
- Unscrew oil filling cap.
- Open oil drain screw with 17 mm wrench; drain oil.
- Remove oil filter with filter wrench; clean oil screen if EA300.
- Oil new filter seal; screw in by hand.
- Refit drain screw with new sealing.
- Fill engine oil; check level every 2 litres.
- Run engine 10 minutes; check level.
- Clean up oil splashes and check drain screw for leaks.
Replacement of impeller maintenance
Tools: multigrip pliers
- Close raw water stop cock.
- Remove cover of raw water pump by loosening screws.
- Pull impeller from shaft with multigrip pliers; mark position.
- Check impeller for damage; replace if necessary.
- Lubricate impeller with glycerin or non-mineral oil based lubricant.
- Attach impeller to pump shaft.
- Fasten cover and use new seal.
V-belt replacement for internal cooling water pump maintenance
Tools: spanner
- Loosen screw on upper alternator mounting.
- Loosen screw underneath alternator.
- Press alternator toward thermostat housing.
- Exchange V-belt.
- Tighten V-belt so it can be pressed about 10 mm.
- Tighten screws above and underneath alternator.
Ventilation of coolant circuit / freshwater maintenance
⚠ The ventilation screw above the cooling water pump casing may not be opened while the generator is running.
Tools: spanner size 10 mm
- Switch off generator before opening vent points.
- Ensure external expansion tank is connected and at sufficient height.
- Open vent screw above cooling water pump casing if present.
- Open vent screw on thermostat casing.
- Pour cooling water into filling necks or external expansion tank.
- When level no longer drops, close filler cover and vent screws; start generator.
- Run generator approx. 60 seconds; switch off.
- Refill cooling water via compensation tank.
- Repeat procedure 1-5 times.
- If no change, run 5 minutes and repeat de-aeration two to three times.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 120 V | single-phase | Alternator coils in parallel | H1.1/H1.2, H2.1/H2.2 | For generators up to 9 kVA: use J3; jump J6 with AWG6 wire; connect one neutral N1 or N2 to PE; 120 V between L1 or L2 and the other neutral. |
| 120/240 V | single-phase | Alternator coils in series | H1.1/H1.2, H2.1/H2.2 | For generators up to 9 kVA: use J3; do not jump J6; connect one neutral N1 or N2 to PE; 2x120 V between L1/L2 and the other neutral; 240 V between L1 and L2. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the Fischer Panda Panda 15 mini PMS Digital?
The Fischer Panda Panda 15 mini PMS Digital is rated 15 kW standby (24.0 kVA).
What engine does the Fischer Panda Panda 15 mini PMS Digital use?
The Fischer Panda Panda 15 mini PMS Digital is powered by the Kubota D902 engine.
How much oil does the Fischer Panda Panda 15 mini PMS Digital take?
The Kubota D902 engine in the Fischer Panda Panda 15 mini PMS Digital has an oil capacity of 3.7 liters.
What is the cooling system capacity of the Fischer Panda Panda 15 mini PMS Digital?
The Fischer Panda Panda 15 mini PMS Digital cooling system holds 4.1 liters (1.1 US gallons) for the engine, per the manufacturer specification sheet.
What voltages is the Fischer Panda Panda 15 mini PMS Digital available in?
The Fischer Panda Panda 15 mini PMS Digital is offered in 120 V, 240 V, 60 V, 16 V, 230 V, 50 V.
What oil filter fits the Fischer Panda Panda 15 mini PMS Digital?
The Fischer Panda Panda 15 mini PMS Digital uses oil filter part numbers KUBOTA 7665025430, KUBOTA 1641432434.
What fuel filter fits the Fischer Panda Panda 15 mini PMS Digital?
The Fischer Panda Panda 15 mini PMS Digital uses fuel filter part numbers KUBOTA 1258143013, KUBOTA 1522143081.
Which air filter part number does the Fischer Panda Panda 15 mini PMS Digital take?
The Fischer Panda Panda 15 mini PMS Digital uses air filter part number RG15842930.
Repair guides
15- Check and discharge capacitors
- Check fuel solenoid valve
- Checking oil-level
- Checking water separator in fuel supply
- Connection of two 12 V batteries to a 24 V battery bank
- Daily routine checks before starting
- Insulation test
- Re-magnetising rotor
- Re-start with Failure Bypass Switch
- Refilling oil
- Replace air filter mat
- Replacement of engine oil and engine oil filter
- Replacement of impeller
- V-belt replacement for internal cooling water pump
- Ventilation of coolant circuit / freshwater
Step-by-step procedures compiled from the Fischer Panda service manual for this model.
Parts
24| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 100-0245-000 | Air Filter | 1 | Air filter | Amazon |
| 100-0247-000 | Fuel Filter | 1 | Fuel filter | Amazon eBay |
| 100-0248-000 | Belt | 1 | Belt | Amazon eBay |
| 100-025-000 | Air Filter | 1 | Air filter | Amazon eBay |
| 100-030-000 | Oil Filter | 1 | Oil filter | Amazon eBay |
| 100-0368-000 | Oil Filter | 1 | Oil filter | Amazon eBay |
| 100-0369-000 | Coolant Filter | 1 | Coolant filter | Amazon eBay |
| 100-0370-000 | Spark Plug | 1 | Spark plug | Amazon |
| 100-045-000 | Fuel Filter | 1 | Fuel filter | Amazon eBay |
| 100-060-000 | Coolant Filter | 1 | Coolant filter | Amazon eBay |
| 100-075-000 | Belt | 1 | Belt | Amazon eBay |
| 100-090-000 | Spark Plug | 1 | Spark plug | Amazon eBay |
| 100-105-000 | Spark Plug | 1 | Spark plug | Amazon eBay |
| P01-025 | Air filter mat | 1 | Air filter | Amazon eBay |
| P01-026 | Pull out holder for air filter mat | 1 | Air filter | Amazon eBay |
| P01-027 | Air filter housing with snap fasteners | 1 | Air filter | Amazon eBay |
| P01-028 | Air filter | 1 | Air filter | Amazon eBay |
| P01-030 | Fuel filter with sight glass | 1 | Fuel filter | Amazon eBay |
| P01-032 | Water separator in the fuel supply | 1 | Fuel filter | Amazon eBay |
| P01-034 | Spring, By-Pass Valve | 1 | Belt | Amazon eBay |
| P01-036 | Spark plug | 1 | Spark plug | Amazon eBay |
| R1/2 | Drain Plug (R1/2) | Oil filter | buy | |
| W0301-00008 | Starter Key (2 pieces) | 2 | Starter | Amazon eBay |
| 21.03.10.008P | Service Kit 8 | Service part / kit | buy |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.