| 5 | Starting failed | STARTING FAILS / STARTABBRUCH | Shutdown | Acknowledge with Start/Stop button. |
| 9 | Watchdog Error | WATCHDOG | Shutdown | Acknowledge with Start/Stop button. |
| 12 | Winding temperature fault | FAULT: WINDING / TEMP. WICKLUNG | Shutdown | Acknowledge with Start/Stop button. |
| 13 | Winding temperature out of range | OUT: WINDING / OUT: WICKLUNG | Shutdown | Acknowledge with Start/Stop button. |
| 14 | Exhaust temperature fault | FAULT: EXHAUST / TEMP. ABGAS | Shutdown | Acknowledge with Start/Stop button. |
| 15 | Exhaust temperature out of range | OUT: EXHAUST / OUT: ABGAS | Shutdown | Acknowledge with Start/Stop button. |
| 16 | Engine temperature fault | FAULT: CYL.HEAD / TEMP. MOTOR | Shutdown | Acknowledge with Start/Stop button. |
| 17 | Oil pressure fault | FAULT: OILPRESS / FEHLER: OELDRUCK | Shutdown | Acknowledge with Start/Stop button. |
| 18 | Battery voltage low | BATTERY LOW / BATTERIE ENTLADEN | Shutdown | Controller shuts down completely to prevent battery discharge; acknowledge after charging. |
| 22 | Emergency stop | EMERGENCY STOP! / NOT-HALT! | Shutdown | Release emergency stop; acknowledge with Start/Stop button. |
| 23 | Engine temperature out of range | OUT: CYL.HEAD / OUT: MOTOR | Shutdown | Acknowledge with Start/Stop button. |
| 30 | Inverter overtemp | Inverter overtemp / Inverter Uebertemp. | Shutdown | Acknowledge with Start/Stop button. |
| 31 | inverter overload | Inverter overload / Inverter Ueberlast | Shutdown | Acknowledge with Start/Stop button. |
| 32 | inverter communication lost | Inverter com. lost / Inverter Kom. defekt | Shutdown | Acknowledge with Start/Stop button. |
| 33 | inverter synchronisation lost | INV. SYNC. FAILED / INV. SYNC. FEHLER | Shutdown | Acknowledge with Start/Stop button. |
| 34 | Engine fault (EDC) | ENGINE FAULT / MOTOR FEHLER | Shutdown | Acknowledge with Start/Stop button. |
| 35 | CAN communication lost | CAN. COMM.LOST / CAN KOMM. FEHLER | Shutdown | Acknowledge with Start/Stop button. |
| 36 | inverter overload slave 1 | L1 OVERLOAD / L1 UEBERLAST | Shutdown | Acknowledge with Start/Stop button. |
| 37 | inverter overload slave 2 | L2 OVERLOAD / L2 UEBERLAST | Shutdown | Acknowledge with Start/Stop button. |
| 38 | inverter overload slave 3 | L3 OVERLOAD / L3 UEBERLAST | Shutdown | Acknowledge with Start/Stop button. |
| 39 | inverter overload slave DC | DC OVERLOAD / DC UEBERLAST | Shutdown | Acknowledge with Start/Stop button. |
| 40 | Overvoltage | FAULT: OVERVOLTAGE / Fehler: Ueberspg. | Shutdown | Acknowledge with Start/Stop button. |
| 41 | Undervoltage | FAULT: LOWVOLTAGE / Fehler: Unterspg. | Shutdown | Acknowledge with Start/Stop button. |
| 42 | DC-Overvoltage | DC OVERVOLTAGE / DC UEBERSPG. | Shutdown | Acknowledge with Start/Stop button. |
| 66 | RedundantTempSwitchOff | NOTSTOP! / NOTSTOPP! | Shutdown | Acknowledge with Start/Stop button. |
| 100 | Communication Error | NO CONNECTION / BUS ERROR! / KEINE VERBINDUNG / BUS FEHLER! | Shutdown | Secure generator, open battery disconnect switches, check plug-in connections and cables; acknowledge after connection is restored. |
| 207 | Init failed (no generator type is selected) | INIT FAILED! | Shutdown | Acknowledge with Start/Stop button. |
| BATTERY LOW | Battery power too low | Battery power too low | Shutdown | Controller is completely shut down to prevent battery discharging too much. |
| CA00 | AC voltage above threshold | AC voltage is above threshold | Shutdown | |
| CA01 | AC voltage below threshold | AC voltage is below threshold | Shutdown | |
| CA02 | AC current above threshold | AC current is above threshold | Shutdown | |
| CA03 | AC power above threshold | AC power is above threshold | Shutdown | |
| CA04 | DC voltage above threshold | DC voltage is above threshold | Shutdown | |
| CA05 | Coolant in temperature above threshold | Coolant in temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Shutdown | |
| CA07 | Cylinder head temperature above threshold | Cylinder head temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Shutdown | |
| CA08 | Exhaust elbow temperature above threshold | Exhaust elbow temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Shutdown | |
| CA09 | Winding temperature above threshold | Winding temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Shutdown | |
| CA10 | Oil pressure below threshold | Oil pressure is below threshold; will not be set if sensor is missing, shorted or disabled | Shutdown | |
| CA11 | Alternator bearing temperature above threshold | Alternator bearing temperature is above threshold; missing current sensing device equals missing sensor | Shutdown | |
| CA12 | Internal 5V supply voltage below threshold | Internal 5V supply voltage is below threshold | Shutdown | |
| CA13 | Actuator current above threshold | Actuator current is above threshold | Shutdown | |
| CA14 | Engine speed above threshold | Engine speed is above threshold | Shutdown | |
| CA15 | Internal 5V supply voltage above threshold | Internal 5V supply voltage is above threshold | Shutdown | |
| CW00 | AC voltage above threshold | AC voltage is above threshold | Warning | |
| CW01 | AC voltage below threshold | AC voltage is below threshold | Warning | |
| CW02 | AC current above threshold | AC current is above threshold | Warning | |
| CW03 | AC power above threshold | AC power is above threshold | Warning | |
| CW04 | DC voltage above threshold | DC voltage is above threshold | Warning | |
| CW05 | Coolant in temperature above threshold | Coolant in temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Warning | |
| CW07 | Cylinder head temperature above threshold | Cylinder head temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Warning | |
| CW08 | Exhaust elbow temperature above threshold | Exhaust elbow temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Warning | |
| CW09 | Winding temperature above threshold | Winding temperature is above threshold; will not be set if sensor is missing, shorted or disabled | Warning | |
| CW10 | Oil pressure below threshold | Oil pressure is below threshold; will not be set if sensor is missing, shorted or disabled | Warning | |
| CW11 | Alternator bearing temperature above threshold | Alternator bearing temperature is above threshold; missing current sensing device equals missing sensor | Warning | |
| CW12 | Internal 5V supply voltage below threshold | Internal 5V supply voltage is below threshold | Warning | |
| CW13 | Actuator current above threshold | Actuator current is above threshold | Warning | |
| CW14 | Engine speed above threshold | Engine speed is above threshold | Warning | |
| CW15 | Internal 5V supply voltage above threshold | Internal 5V supply voltage is above threshold | Warning | |
| FAULT: CYL.HEAD | Cylinder head temperature too high | Cylinder head temperature too high | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| FAULT: EXHAUST | Exhaust manifold temperature too high | Exhaust manifold temperature too high | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| FAULT: OILPRESS | Oil pressure error | Oil pressure error | Shutdown | |
| FAULT: WINDING | Winding temperature too high | Winding temperature too high | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| HIGH cylinder head | Cylinder head temperature too high | HIGH flashes alternating with cylinder head temperature value | Warning | |
| HIGH cylinder head temperature | Cylinder head temperature is too high | Warning threshold reached | Warning | |
| INIT FAILED! | Parameters were not correctly adopted into EEPROM | Parameters were not correctly adopted into EEPROM when generator type was initialised. Generator type must be reset. | Shutdown | Reset generator type. |
| Inverter overload | Generator was overloaded | Error message on display: Inverter overload | Shutdown | Switch off generator and disconnect all load; overload protection will reset |
| Inverter overtemp | Inverter temperature too high | Inverter temperature too high | Shutdown | |
| MS0 | VCS is in re-start delay | VCS is in re-start delay | Info | |
| MS01 | USB port connected to host PC | USB port on VCS board is connected to host PC | Info | Will precede CAN communication |
| MS02 | VCS powered up via CAN bus | VCS is powered up via CAN bus (panel) | Info | |
| MS03 | Battle short active | Battle short is active (input from panel, static) | Info | Military applications only |
| MS04 | Cumulative data not synced | Cumulative data in VCS memory not synced | Info | VCS board will retrieve data from panels |
| MS05 | Actuator current peak | Actuator current has reached peak level | Info | VCS will retract actuator |
| MS06 | Not used | Not used on this control system | Info | |
| MS07 | Coolant temperature above max level | Coolant temperature above max. level | Info | User needs to check coolant system |
| MW00 | Battery voltage low | Battery voltage is low | Warning | |
| MW01 | Frequency out of range | Frequency is out of range | Warning | |
| MW02 | VCS temperature high | VCS temperature is high | Warning | |
| MW03 | CT board temperature high | CT board temperature is high | Warning | |
| MW04 | Tank level low | Tank level is low | Warning | |