PowerCommand 1.1 Controller

The PowerCommand 1.1 is a generator-set controller. It is used on generator sets from Cummins/Onan, including the 4B3.9, C10 D6, C100 D6 and C100 N6.

121
Generator sets
Cummins/Onan
Brand
10–450 kW
Power range
3
Fuel types

Troubleshooting

60

Fault codes

CodeMeaningCauseRemedy
1HIGH COOLANT TEMP — Lamp: Shutdown; Indicates engine has overheated (coolant temperature has risen above the shutdown trip point)Allow engine to cool down completely before proceeding with the following checks: Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary; Check for obstructions to cooling airflow and correct as necessary; Check fan belt and repair or tighten if necessary; Check blower fan and circulation pumps on remote radiator installations; Reset control and restart after locating and correcting problem.
1/202HIGH OR PRE-HIGH COOLANT TEMPERATURE (SHUTDOWN/SHUTDOWN) — Calibration-dependent. No action is taken by the Control for code 202. Engine will shut down for code 1Fault simulation was enabled with a PC based service toolWith a PC based service tool, verify that the fault simulation is not enabled for the coolant sensor. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
102VOLTAGE BIAS OOR — Lamp: Shutdown; Indicates the voltage bias circuit output is out of range (OOR), high or low. (I/O Module option.)
103SPEED BIAS OOR — Lamp: Shutdown; Indicates the speed bias circuit output is out of range (OOR), high or low. (I/O Module option.)
106I/O MODULE LOST — Lamp: Shutdown; Indicates the data link between the I/O module and the Base board is lost
1117ECM Power Lost — "keyswitch" to the Engine Control Module (ECM) was not removed for 30 seconds before removing battery power to the ECM (removing connectors or battery cable)ECM power lostTo reset, press the Off button, press the Emergency Stop button, and wait 30 seconds
12HIGH AC VOLTAGE (SHUTDOWN) — Engine will shut downFault simulation was enabled with a PC based service toolWith a PC based service tool, verify that the related fault simulation is not enabled. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
12HIGH AC VOLTAGE — Lamp: Shutdown; Indicates that one or more of the phase voltages has exceeded 130% of nominal for 0 second, or has exceeded high ac voltage threshold of nominal for time delay seconds
121Loss of Speed Sense (Shutdown) — No engine speed signal detected from one of two signals: engine crankshaft speed or engine camshaft positionFaulty Magnetic Pickup (MPU) sensor connections and wiring; improper installation of the MPU sensor; faulty MPU sensor; incorrect calibrations in PowerCommand controls; faulty control board; damaged flywheel ring gearInspect the MPU sensor and the main harness connector pins: disconnect the main harness connector from the MPU sensor; inspect for corroded, bent, broken, pushed back, expanded, or loose pins
1244Engine Normal Shutdown — The engine has received a normal shutdown requestThe generator set is going through a normal shutdownThe generator set is going through a normal shutdown and there are no active shutdown fault(s) in the ECM for at least 2 seconds
1245Engine Shutdown Fault — An engine shutdown fault has occurred in the Engine Control Module (ECM), and no other active shutdown faults exist on the PCCEvent/fault code 1245 is activated by another active shutdown fault in the ECMConnect to the ECM with E-Controls GCP Display or 4G Display to determine the actual shutdown fault that is generating event/fault code 1245; troubleshoot the shutdown fault(s)
1246CAN Unknown Engine Fault — The PCC received an unknown message from the ECMECM/engine faultRefer to the E-Controls service tool
1248Engine Warning — An engine warning fault has occurred in the Engine Control Module (ECM), and there are no active warning faults on the PCCAnother active warning fault in the ECM activates event/fault code 1248Connect to the ECM with E-Controls GCP Display or 4G Display to determine the actual warning fault that is generating event/fault code 1248; troubleshoot the shutdown fault(s)
13LOW AC VOLTAGE — Lamp: Shutdown; Indicates that one or more of the phase voltages has dropped below low ac voltage threshold for time delay seconds
13LOW ACE VOLTAGE (SHUTDOWN) — Engine will shut downFault simulation was enabled with a PC based service toolWith a PC based service tool, verify that the related fault simulation is not enabled. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
1311Customer Input #1 (Warning or Shutdown) — The nature of the fault is an optional customer selectionProgram the fault function using the InPower service tool: enable/disable input (default: enable); status, warning, or shutdown (default: #1-None, #2-Warning and #3-Warning); active closed or open (default: closed [ground])
1311Customer Input #1 (Warning or Shutdown) — The nature of the fault is an optional customer selection. Examples of inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Fault condition exists at customer inputs
1312Customer Input #2 (Warning or Shutdown) — The nature of the fault is an optional customer selectionProgram the fault function using the InPower service tool: enable/disable input (default: enable); status, warning, or shutdown (default: #1-None, #2-Warning and #3-Warning); active closed or open (default: closed [ground])
1312Customer Input #2 (Warning or Shutdown) — The nature of the fault is an optional customer selection. Examples of inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Fault condition exists at customer inputs
1317Low Coolant Level (Warning or Shutdown) — This fault is used when an optional coolant level sensor is installed. The nature of the fault is an optional customer selectionLow coolantStop the engine and allow the engine to cool down; Visually inspect and verify that the engine coolant is at the appropriate level; If the coolant level is too low, add coolant per specifications
1318Low Fuel (Warning or Shutdown) — This fault is used when an optional low fuel level switch is installedLow fuel pressureMeasure the fuel pressure at the fuel pump inlet
1318Low Fuel (Warning or Shutdown) — This fault is used when an optional low fuel level switch is installed. The nature of the fault is an optional customer selectionLow fuel levelAdd the manufacturer's prescribed fuel
135Oil Pressure Sensor OOR - High — Engine oil pressure sensor signal is out of range – shorted highFaulty oil pressure sensor and/or circuit; Faulty ECM; Faulty ECM connection or harness
14OVER FREQUENCY — Lamp: Shutdown; Indicates frequency is 10% above base frequency for approximately 10 seconds
14Over Frequency (Shutdown) — Generator set will shut down.Fault threshold is not set correctly with PC based service tool; Fuel or air delivery problem; Governor fault; Loose connector or Base board is badReset the threshold to the highest allowable setting. Determine the required operating range before adjusting the threshold; Refer to the engine service manual; Check governor frequency adjustment (Refer to Section 7); Repair connections (P12/P13) or replace the Base board if necessary
1417Power Down Failure — The PCC has failed to go to sleepIncorrect calibrations in PowerCommand controlsUsing the display or the InPower Service tool, verify the calibration in the PCC; If the calibration in the PCC matches the latest calibration on the InCal website, then the calibration is correct. If it does not, update the calibration to the latest
143Engine Oil Pressure Low (Warning)Lubricating oil level is lowCheck the oil level. Add oil, if necessary
143Engine Oil Pressure Low (Warning) — Engine oil pressure is below the low oil pressure warning threshold.Lubricating oil level is lowCheck the oil level. Add oil, if necessary.
1433Local E-Stop — The state of the Local Emergency Stop (E-Stop) has been changedThe local E-Stop button has been activatedReset the Local E-Stop: pull the Local E-Stop button out; press the Off button; press the Reset button; select Manual or Auto as required
1434Remote E-Stop — The state of the Remote Emergency Stop has been changedThe Remote Emergency Stop button has been activatedReset the Remote Emergency Stop
1438Fail to Crank (Shutdown)Dead or weak batteryVerify battery voltage is at least 12 VDC; Charge or replace the battery as necessary
1438Fail to Crank (Shutdown) — The engine failed to crank after the generator control received a start signal.Dead or weak batteryVerify battery voltage is at least 12 VDC (or 24 VDC if applicable); Charge or replace the battery as necessary.
144Engine Coolant Temperature OOR Low (Warning) — Engine coolant temperature signal voltage is out of range - shorted lowFor the troubleshooting procedure, refer to DTC 118 in the E-Controls Service Manual
144Engine Coolant Temperature OOR Low (Warning) — Engine coolant temperature signal voltage is out of range – shorted lowFaulty coolant temperature sensor connectionsInspect the coolant temperature sensor and the main harness connector pins; Disconnect the main harness connector from the coolant temperature sensor; Inspect for corroded pins, bent or broken pins, pushed back or expanded pins; Inspect for evidence of moisture in or on the connector; Dry the connectors with Cummins electronic cleaner, Part Number 3824510; Inspect for missing or damaged connector seals; Inspect for dirt or debris in or on the connector pins
145Engine Coolant Temperature OOR High (Warning) — Engine coolant temperature signal voltage is out of range - shorted highFor the troubleshooting procedure, refer to DTC 117 in the E-Controls Manual
145Engine Coolant Temperature OOR High (Warning) — Engine coolant temperature signal voltage is out of range – shorted highFaulty coolant temperature sensor connectionsInspect the coolant temperature sensor and the harness connector pins; Disconnect the engine harness connector from the coolant temperature sensor; Inspect for corroded pins, bent or broken pins, pushed back or expanded pins; Inspect for evidence of moisture in or on the connector; Dry the connectors with Cummins electronic cleaner, Part Number 3824510; Inspect for missing or damaged connector seals
146Engine Coolant Temperature Above Normal (Warning)High ambient temperatureReduce loads or recirculation of discharge air to generator in elevated ambient
146Engine Coolant Temperature Above Normal (Warning) — Engine coolant temperature has exceeded the warning threshold (220 °F [105 °C]) for high coolant temperatureHigh ambient temperatureMeasure the air temperature entering the air intake louver of the generator set enclosure if enclosed, or cooling air to the radiator if not enclosed; verify the expected cooling system ambient temperature capability; inspect for recirculation of cooling discharge air into the generator set enclosure air inlet or the area surrounding the radiator cooling air inlet
1472High AC Current (Shutdown)Generator set overloadReduce the generator set load by powering off to unneccessary household appliances (examples: washer, dryer, air conditioning, etc.)
1472High AC Current (Shutdown) — The generator output current has exceeded at least 150% of rated current.Generator set overloadReduce the generator set load by powering off to unnecessary household appliances (examples: washer, dryer, air conditioning, etc.).
15UNDER FREQUENCY — Lamp: Shutdown; Indicates that engine speed has dropped below 90% of nominal for approximately 10 secondsCheck fuel supply, intake air supply and load.
15Under Frequency (Shutdown) — Generator set will shut down.Fault threshold is not set correctly with PC based service tool; Overload; Fuel or air delivery problem; Governor fault; Loose connector or Base board is badReset the threshold to the lowest allowable setting. Determine the required operating range before adjusting the threshold; Check the load and correct any overload. Check operation by disconnecting load and restarting generator set; Refer to the engine service manual; Check fuel shutoff solenoid adjustment; Repair connections (P13) or replace the Base board if necessary
151Engine Coolant Temperature High (Shutdown)High ambient temperatureReduce loads or recirculation of discharge air to generator in elevated ambient
151Engine Coolant Temperature High (Shutdown) — Engine coolant temperature has exceeded the alarm (shutdown) threshold for high coolant temperature.High ambient temperatureReduce loads or recirculation of discharge air to generator in elevated ambient.
151Engine Coolant Temperature High (Shutdown) — The engine coolant temperature has exceeded the alarm (shutdown) threshold for high coolant temperatureFor the troubleshooting procedure, refer to DTC 217 in the E-Controls Manual
153Intake Manifold Temperature OOR High (Warning) — Engine intake manifold temperature sensor signal is out of range – shorted highFor the troubleshooting procedure, refer to DTC 113 in the E-Controls Manual
154Intake Manifold Temperature OOR Low (Warning) — Engine intake manifold temperature sensor signal is out of range – shorted lowFor the troubleshooting procedure, refer to DTC 112 in the E-Controls Manual
155Intake Manifold Temperature High (Shutdown)High ambient temperatureReduce loads or recirculation of discharge air to generator in elevated ambient
155Intake Manifold Temperature High (Shutdown) — Engine intake manifold temperature has exceeded 203 °F (95 °C) for greater than 10 seconds.For the troubleshooting procedure, refer to DTC 127 in the E-Controls Manual.
155Intake Manifold Temperature High (Shutdown) — The engine intake manifold temperature has exceeded 95 °C (203 °F) for greater than 10 secondsFor the troubleshooting procedure, refer to DTC 127 in the E-Controls Manual
163 - 170BASE I/O MODULE INPUT 1 – 8 — Lamp: None; The nature of the Base I/O Module event is an optional customer selectionEach event function can be programmed (using InPower service tool or access to Setup menu), as follows: Change display name using up to 32 characters; Select active low or high input.
171 - 174AUX I/O MODULE INPUT 9 – 12 — Lamp: None; The nature of the Aux I/O Module event is an optional customer selectionEach event function can be programmed (using InPower service tool or access to Setup menu), as follows: Change display name using up to 32 characters; Select active low or high input.
1854Customer Input 2 — Event/fault code 1854 (customer input 2) becomes active when there is a ground input at TB1-2 on the back of the universal annunciatorIncorrectly configured or wiring issueMake sure that the universal annunciator is correctly configured; for setup and configuration instructions, refer to the universal annunciator operator's manual; Check the wiring at TB1-2 and make sure that customer input 2 is wired correctly. Depending on the configuration of the annunciator, make sure that there is not a short or open circuit at the TB1-2 connection; Check the sender, relay, or device that is activating input 2 on the universal annunciator. Replace if faulty
1855Annunciator Input 3 Fault — Customer fault 3 (input 3, LED 3) on the universal annunciator is activeCondition for which "Annunciator Input #3" is configured for is activeCheck the condition for which "Annunciator Input #3" has been configured for. For example, if "Annunciator Input #3" was configured to become active when the fuel level is low, check the fuel level and add fuel if needed. After the issue is resolved, press the Reset button on the operator panel in order to clear the fault. If the fault does not clear, go to the next step
1855Customer Input 3 — Event/fault code 1855 (customer input 3) becomes active when there is a ground input at TB1-3 on the back of the universal annunciatorIncorrect annunciator configuration or wiring; Faulty sender, relay, or device activating Input 3; Faulty annunciatorMake sure that the universal annunciator is correctly configured; check the wiring at TB1-3 and make sure that customer input 3 is wired correctly, make sure that there is not a short or open circuit at the TB1-3 connection; check the sender, relay, or device that is activating Input 3 on the universal annunciator, replace if faulty; if the wiring and configuration is satisfactory, replace the universal annunciator
1944Annunciator Configuration Error (Warning) — More than one network device is configured to activate one of the annunciator output relaysBad network configurationCheck the setup of devices on the network against duplicate use of the same annunciator relay output
197Coolant Level Low (Warning)Low coolantRemove radiator cap and check that coolant is up to the required level
197Coolant Level Low (Warning) — Coolant level sensor signal is showing a low coolant level for greater 10 seconds.Low coolantRemove radiator cap and check that coolant is up to the required level.
2LOW OIL PRESSURE — Lamp: Shutdown; Indicates engine oil pressure has dropped below the shutdown trip pointCheck oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. If oil switch is used, check switch performance.
2/215LOW OIL OR PRE-LOW PRESSURE (WARNING/SHUTDOWN) OIL PRESSURE SENSOR TYPE : SENDER — Calibration-dependent. No action is taken by the Control for code 215. Engine will shut down for code 2Fault simulation was enabled with a PC based service toolWith a PC based service tool, verify that the fault simulation is not enabled for the oil pressure sensor. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.