Cummins/Onan C35 D6 Generator Set

The Cummins/Onan C35 D6 is a 35 kW (43.8 kVA) standby generator set powered by a Cummins/Onan C35 D6 engine. It is available at 120/240 V, 120/208 V, 277/480 V and 347/600 V, 3-phase and 50 Hz. It holds 50 L (13.2 gal) of coolant, with a maximum ambient rating of 50 °C. The set measures 2224×864×1121 mm (87.6×34.0×44.1 in) and weighs about 552 kg (1217 lb). An integrated tank holds 170 L (44.9 gal).

35 kW
Standby
3.3 L
Displacement
5
Document types

How to read your Cummins/Onan serial & model number →

Specifications

Frequency50.0 Hz
Standby power35 kW
Standby kVA43
Prime power32 kW
ControllerPowerCommand 1.1, PowerCommand 1301, PowerStart
AlternatorCummins/Onan Brushless, 4 pole, drip proof, revolving field
Voltage options120/240 V, 120/208 V, 277/480 V, 347/600 V
Phase3
Power factor1.0
Battery voltage12 V
Coolant capacity50 L
Max ambient50 °C
Dimensions (L×W×H)2224×864×1121 mm
Dry weight552 kg
Fuel tank170.0 L

Engine

Cummins/Onan C35 D6
Displacement3.3 L
Aspirationnaturally aspirated

Maintenance & consumables

for the Cummins/Onan C35 D6
ItemSpecCapacityPart #Interval
Air filter find
Fuel filter find
Oil filter find
Belt find
Coolant
Oil

Common questions

What is the power rating of the Cummins/Onan C35 D6?

The Cummins/Onan C35 D6 is rated 35 kW standby (43.8 kVA).

What engine does the Cummins/Onan C35 D6 use?

The Cummins/Onan C35 D6 is powered by the Cummins/Onan C35 D6 engine.

What alternator does the Cummins/Onan C35 D6 use?

The Cummins/Onan C35 D6 uses a Cummins/Onan Brushless, 4 pole, drip proof, revolving field alternator.

Troubleshooting

16

Fault codes

CodeMeaningCauseRemedy
81 uGenerator set output frequency cannot be maintained.
59High AC voltage shutdown (Output voltage on any phase exceeds pre-set values).
27Low AC voltage shutdown (Voltage on any phase has dropped below a preset value).
96Lamp: ShutdownIndicates that the engine oil temperature is above normal and has reached the shutdown trip point.
202Lamp: WarningIndicates engine is operating near cooling system capacity (monitor condition). Increase in load or higher ambient temperature may cause High Coolant Temp (1) shutdown.Review code 1 correction list for other possible causes.

Symptoms & remedies

SymptomCauseRemedy
Output voltage on any phase exceeds pre-set values.Values adjustable from 105-125% of nominal voltage, with time delay adjustable from 1-10 seconds. Default value is 110% for 5 seconds.
Voltage on any phase has dropped below a preset value.Adjustable over a range of 50-95% of voltage, time delay 2-20 seconds. Default value is 90% for 5 seconds.
Low oil pressure or high coolant temperatureThe control (with graphical display) will light a yellow Warning lamp or a red Shutdown lamp and display a message on the graphical display. A control without the graphical display indicates a shutdown condition by intermittent flashing of the status indicator.
Unexpected start-up or failure to crankRemote inputVerify that the remote input is not causing the symptom or isolate the control from these inputs before troubleshooting the control.
Equipment damage due to wrong calibration fileDo not swap Baseboards from another genset model and only use the calibration file shown on the nameplate.
Features not available for troubleshooting base boardConfirm that the feature is installed and enabled prior to trouble-shooting the base board for symptoms related to a feature.
Shutdown conditionMake sure that parameter adjustments and time delays, related to the fault condition, have been appropriately set for the application. It may be necessary to write the initial capture file to the device or update the calibration file.
Shutdown or unexpected start-upPress the button to switch to the Off mode. Turnoff or remove AC power from the battery charger. Remove the negative (–) battery cable from the generator set starting battery.
L not start in remote mode, but starts in manual mode.The remote start switch or configurable wiring is faulty.Reset the control. Attempt to start, and check for ground at TB1-11. If ground level is not present, isolate to the remote switch or configurable wiring. Repair as necessary. If ground is present, go to next step.
The menu display Auto button, harness or the Base board is bad.Check for continuity between P11-16 (AUTO) to P11-8 (GND). If no continuity when pressing the menu display Auto button, isolate to front membrane panel or wiring harness. If there is continuity, the Base board is bad.
Increase in load or higher ambient temperature may cause High Coolant Temp (1) shutdown.Review code 1 correction list for other possible causes.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

8
Part #DescriptionQtySystem
P01-001Air Filter1Air filter PartsGeek
P02-001Oil Filter1Oil filter PartsGeek
P03-001Fuel Filter1Fuel filter PartsGeek
P04-001Coolant Filter1Coolant filter PartsGeek
P05-001Belt2Belt PartsGeek
P06-001Spark Plug1Spark plug PartsGeek
234-237AUX I/O MODULE INPUT 9-12Service part / kit PartsGeek
961-0518(Issue1)1Service part / kit PartsGeek

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime
Standby

Available documents

Spec sheet — 0057984Spec sheet — 0058677 (Cummins/Onan)Spec sheet — 0069812Spec sheet — Cummins-C38D5-Spec-Sheet (Cummins/Onan)Spec sheet — NAS-5872-EN (Cummins/Onan)Spec sheet — SS23-CPGKSpec sheet — diesel-gen-set-rating-cards-international-60hz-2025 (Cummins/Onan)Installation manual — C30D6 Installation Manual (Cummins/Onan)Reference — 102S-103387Reference — 51070-01Parts manual — 906-0103 Cummins C22D5 C25D6 C30D6 C33D5 Parts (8-2006) (Cummins/Onan)Service manual — 900-0910 Cummins C33D5 - C35D6 Repair Times (Cummins/Onan)Service manual — C3xDx Generator Service Manual (Cummins/Onan)Service manual — C60D6 Service Manual (Cummins/Onan)