PowerCommand 1301 Controller

The PowerCommand 1301 is a generator-set controller. It is used on generator sets from Cummins/Onan, including the C30 D6, C33 D5, C35 D6 and C38 D5.

14
Generator sets
Cummins/Onan
Brand
24–44 kW
Power range
2
Fuel types

Generator sets using this controller

14

Also fitted to: Cummins/Onan 1301, Cummins/Onan PowerCommand™ (1301).

Troubleshooting

45

Fault codes

CodeMeaningCauseRemedy
202Lamp: WarningIndicates engine is operating near cooling system capacity (monitor condition). Increase in load or higher ambient temperature may cause High Coolant Temp (1) shutdown.Review code 1 correction list for other possible causes.
220Shutdown lamp remains lit even though the set continues to runOverridden shutdown fault occurs when Battle Short mode is enabledPress ▲, ▼ or ◄ button to acknowledge the fault
27Excitation Fault (Loss of Voltage Sense)Battle Short mode is suspended and a shutdown occurs immediately
27Low AC voltage shutdown (Voltage on any phase has dropped below a preset value).
31Battle Short is suspended and a shutdown occurs immediatelyOverspeed fault
31OverspeedBattle Short mode is suspended and a shutdown occurs immediately
45Speed Signal Lost (Loss of Speed Sense)Battle Short mode is suspended and a shutdown occurs immediately
59High AC voltage shutdown (Output voltage on any phase exceeds pre-set values).
61Emergency StopBattle Short mode is suspended and a shutdown occurs immediately
77Battle Short feature is disabled after an overridden shutdown fault occurred whilst in Battle Short mode
81 uGenerator set output frequency cannot be maintained.
96Lamp: ShutdownIndicates that the engine oil temperature is above normal and has reached the shutdown trip point.
Code 135Oil Pressure Sensor OOR - High
Code 141Oil Pressure Sensor OOR - Low
Code 143Engine Oil Pressure Low (Warning)
Code 144Engine Coolant Temperature OOR Low (Warning)
Code 145Engine Coolant Temperature OOR High (Warning)
Code 146Engine Coolant Temperature Above Normal (Warning)
Code 151Engine Coolant Temperature High (Shutdown)
Code 234Engine Speed High (Shutdown)
Code 359Engine Fail to Start
Code 415Engine Oil Pressure Low (Shutdown)
Code 441Low Battery Voltage
Code 442High Battery Voltage
Configurable Alarm and Status InputsConfigurable Alarm and Status Inputs - Power Command 1301 will accept up to two alarm or status inputs (configurable contact closed to ground or open) to indicate customer-specified conditions. The control is programmable for warning, shutdown or

Symptoms & remedies

SymptomCauseRemedy
Batteries can explodeDo not dispose of the battery in a fire, because it is capable of exploding. Do not open or mutilate the battery. Do not charge frozen batteries. Batteries present the risk of high short circuit current when servicing the generator set: remove watches, rings, or other metal objects; use tools with insulated handles.
DizzinessIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
Equipment damage due to wrong calibration fileDo not swap Baseboards from another genset model and only use the calibration file shown on the nameplate.
Exhaust gases are deadlyProvide an adequate exhaust system to properly expel discharged gases away from enclosed or sheltered areas, and areas where individuals are likely to congregate. Visually and audibly inspect the exhaust system daily for leaks per the maintenance schedule. Ensure that exhaust manifolds are secured and not warped. Do not use exhaust gases to heat a compartment. Make sure the unit is well ventilated.
Features not available for troubleshooting base boardConfirm that the feature is installed and enabled prior to trouble-shooting the base board for symptoms related to a feature.
Fuel contact with hot engine or exhaustDo not permit any flame, cigarette, pilot light, spark, arcing equipment, or other ignition source near the generator set or fuel tank. Fuel lines must be adequately secured and free of leaks. Use an approved flexible line for fuel connection at the engine. Do not use copper piping on flexible lines as it will become brittle if continuously vibrated or repeatedly bent. Ensure all fuel supplies have a positive shutoff valve.
Inability to Think CoherentlyIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
Increase in load or higher ambient temperature may cause High Coolant Temp (1) shutdown.Review code 1 correction list for other possible causes.
L not start in remote mode, but starts in manual mode.The remote start switch or configurable wiring is faulty.Reset the control. Attempt to start, and check for ground at TB1-11. If ground level is not present, isolate to the remote switch or configurable wiring. Repair as necessary. If ground is present, go to next step.
Low oil pressure or high coolant temperatureThe control (with graphical display) will light a yellow Warning lamp or a red Shutdown lamp and display a message on the graphical display. A control without the graphical display indicates a shutdown condition by intermittent flashing of the status indicator.
Muscular TwitchingIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
Output voltage on any phase exceeds pre-set values.Values adjustable from 105-125% of nominal voltage, with time delay adjustable from 1-10 seconds. Default value is 110% for 5 seconds.
Shutdown conditionMake sure that parameter adjustments and time delays, related to the fault condition, have been appropriately set for the application. It may be necessary to write the initial capture file to the device or update the calibration file.
Shutdown or unexpected start-upPress the button to switch to the Off mode. Turnoff or remove AC power from the battery charger. Remove the negative (–) battery cable from the generator set starting battery.
The menu display Auto button, harness or the Base board is bad.Check for continuity between P11-16 (AUTO) to P11-8 (GND). If no continuity when pressing the menu display Auto button, isolate to front membrane panel or wiring harness. If there is continuity, the Base board is bad.
Unexpected start-up or failure to crankRemote inputVerify that the remote input is not causing the symptom or isolate the control from these inputs before troubleshooting the control.
Voltage on any phase has dropped below a preset value.Adjustable over a range of 50-95% of voltage, time delay 2-20 seconds. Default value is 90% for 5 seconds.
VomitingIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
Warning or shutdown by lighting the appropriate LEDThe associated fault symbol/text and fault code will also be displayed on the digital display. The nature of the fault and time of occurrence are logged in the control.
Weakness and SleepinessIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.